Cdd

"

Min. 0 min
Max. 15 min
Default 0 min

Compressor Door Open Delay/Cdd 

This parameter sets the delay in minutes before the compressor stops 
when the door is opened. If set to zero, the function is disabled.

"

Srt

"

Min. 0 min
Max. 60 min
Default 0 min

System resume after door open

Fan and Compressor resume after cut out by door open.

"

Pod

"

Min. 0 s
Max. 300 s
Default 300 s

Power ON Delay

This is the delay in seconds between power-on and the compressor being 
activated.

 

Depends on the power ON temperature setting as explained below. 

"

Pot

"

Min. -100.0°C
Max. 200.0°C
Default -100.0°C

Power ON Temperature

This parameter is used to accelerate the first application test on the 
OEM assembly line; if the cabinet temperature is higher than this 
parameter the power ON Delay is overruled and the outputs are activated 
without delay.

Con

Condenser Protection settings

NOTE: A condensor temperature sensor is required to use these parameters.
Condenser protection is generally used in dusty environments where 
the condenser may accumulate a layer of dust or dirt and therefore be 
at risk of overheating.

"

CAL

"

Min. 0°C
Max. 200°C
Default 80°C

Condenser Alarm Limit/CAL

This parameter sets the temperature for the condenser at which an alarm 
will be generated.

"

CbL

"

Min. 0°C
Max. 200°C
Default 85°C

Condenser Block Limit/CbL

This parameter sets the temperature which if reached will cause the 
compressor to switch OFF.

"

CoL

"

Min. 0°C
Max. 200°C
Default 60°C

Condenser OK Limit/CoL

This parameter sets the temperature at which the compressor is 
allowed to start again after the temperature set in "

CbL

" above has been 

exceeded and the compressor stopped.

"

CLL

"

Min. -100°C
Max. 20°C
Default -5°C

Condenser Low Limit/CLL

This parameter sets the lowest (condenser) temperature at which the 
compressor is allowed to start.

diS

Display settings

NOTE: some display parameters can be set in such as way that they 
may be illegal in some jurisdictions. Please check local legislation.

"

diC

"

Min. no
Max. yes
Default no

Display intensity auto control

"

no

": display intensity use fixed value.

"

din

"

Min. 2 
Max. 10
Default 10

Display Intensity

The controller can have its display intensity (brightness) set in one of 
two ways:
A) With a Danfoss ambient light sensor attached, the brightness of the 

display is adjusted automatically according to the ambient light level 
(see the assignments section).

B) When no ambient light sensor is attached, the display intensity can 

be set to a fixed intensity. 
Both options are on a scale of 1 to 10, where 10 is the brightest.

User Guide | ERC 112 Refrigeration Controller

© Danfoss | DCS (vt) | 2019.07

BC200686422115en-000802 | 15

Содержание erc 112

Страница 1: ...eration Controller ERC 112 This user guide is intended to be used by OEMs for the purpose of programming ERC 112 It may also be useful for technicians However it is not intended as a user guide for en...

Страница 2: ...2 24 annex CC and EN IEC 60335 2 89 annex BB Glow wire according to EN IEC 60335 1 IEC EN 60730 UL60730 NSF CQC EAC Ukraine The access level can be set separately for each parameter using KoolProg Koo...

Страница 3: ...ass Door Merchandiser No frost freezer sub zero cooler S2 S3 S4 are optional S3 S4 are optional Gastro No frost freezer Cooler S2 S3 S4 are optional User Guide ERC 112 Refrigeration Controller Danfoss...

Страница 4: ...abinet S2 Temperature sensor for defrost S3 Temperature sensor for condenser light sensor or Motion sensor S4 Temperature sensor Pt 1000 ohm 0 C or door signal di Door signal or Motion sensor Defrost...

Страница 5: ...determined a specific parameter file is saved to the USB key for later mass programming through the docking station Mass programming on an assembly line The docking station is used for high volume pr...

Страница 6: ...le Keypad 4 buttons integrated IP65 design 2 left 2 right user programmable Operating Conditions 0 C to 55 C 93 rH Storage Conditions 40 C to 85 C 93 rH Range of Measurement 40 C to 85 C with standard...

Страница 7: ...000 ohm Door Cabinet temp sensor Evaporator temp sensor Condenser Pt 1000 ohm Door Motion Cabinet temp sensor Evaporator temp sensor Condenser Pt 1000 ohm Door Motion Cabinet temp sensor Evaporator te...

Страница 8: ...zer 27 080G3212 ERC 112D Red LED with buzzer 27 080G3213 ERC 112C Blue LED with buzzer 27 080G3216 ERC 112D Blue LED with buzzer 27 080G3217 ERC 112C Blue LED with buzzer 27 080G3233 ERC 112D Blue LED...

Страница 9: ...Press variable direct function e g ECO Night mode Sub function back 1 Press variable direct function e g light Sub function OK 1 Press temperature set point Sub function up 1 Press temperature set po...

Страница 10: ...K Max 25 K Default 0 Seasonal offset temperature This parameter is only available from Product version PV03 onwards Please check product label for Product version of your controller Offset value for s...

Страница 11: ...an be set to one of these alternatives to control the light in the cabinet on always ON oFF always OFF dor door sensor only Lod Min 0 s Max 300 s Default 0 s Light OFF delay Number of seconds the ligh...

Страница 12: ...rator sensor or by the cabinet temperature sensor if no evaporator sensor is used drt Min 0 0 C Max 200 0 C Default 5 0 C Defrost reset temperature The defrost counter is saved and restored at power u...

Страница 13: ...t Times based on elapsed time doC Min 0 hour Max 24 hour Default 0 hour Defrost by Comp running time Continuous compressor running can cause defrost 0 deactived dEt Min 50 0 C Max 0 0 C Default 50 0 C...

Страница 14: ...n Default 1 min Error Stop Time The parameter only become active in the unlikely event of a broken temperature sensor It is used to run the application in safety mode At the same time the sensor error...

Страница 15: ...denser at which an alarm will be generated CbL Min 0 C Max 200 C Default 85 C Condenser Block Limit CbL This parameter sets the temperature which if reached will cause the compressor to switch OFF CoL...

Страница 16: ...e a realistic temperature appearance for an application a display delay can be set The parameter sets the time constant tau of the moving average filter for the display Physically one time constant re...

Страница 17: ...10 readings Controller will display Error Err if the probe value is more than Signaling threshold value and the trend of the probe is increasing based on the past 10 readings Controller will display i...

Страница 18: ...have an alarm If set to 999 the alarm will continue to sound until the reason for the alarm is cleared for example the temperature has dropped enough or the door closed In some cases it may be necess...

Страница 19: ...of Door action or activity through PIR sensor mentioned in EDA and EPA parameters to exit the ECO mode Edd Min 0 min Max 180 min Default 180 min Door delay Door delay after door close to trigger ente...

Страница 20: ...respect to normal mode during holiday mode diE Min 0 0 K Max 10 0 K Default 2 0 K ECO Differential Thermostat differential for ECO FoE Min 0 s Max 960 s Default 0 s ECO Fan on cycle On time for fan du...

Страница 21: ...perature sensor input S1C Default Stn S1 Config S1C S2 Config S2C S3 Config S3C S4 Config S4C Available options are Stn for a standard temperature sensor NTC 5 K 25 C and TPE precision Htn for a high...

Страница 22: ...Default noP Button 5 Config short press b5C Button 5 Config long press b5L Button 5 is an external button option which can be connected and configured through S4 sensor b5L Default noP Short press fu...

Страница 23: ...product code ACt Accumulated Comp run time AFt Accumulated Fan run time ALt Accumulated Light run time AEt Accumulated ERC up time Sdi DI physcial DI pin state ON OFF uAC Voltage value Current main p...

Страница 24: ...nsor Et1 Evaporator1 Temp Temperature of the evaporator sensor1 Et2 Evaporator2 Temp Temperature of the evaporator sensor2 AuS AUX Temp Temperature of the AUX sensor invisible LLu Light level value Ac...

Страница 25: ...ighest temperature If configured cut in alarm relay beep the buzzer High temperature alarm Lo Air temperature is lower than LAt for Ltd User configured Blink Lo with the lowest temperature If configur...

Страница 26: ...0 mm 077F8766 3000 mm 080G3392 3000 mm 080G3342 3000 mm 080G3324 2000 mm 077F8765 3000 mm 077F8798 3000 mm 077F8768 4000 mm 080G3393 4000 mm 080G3343 2200 mm 077F8767 6000 mm 080G2029 6000 mm 080G2039...

Страница 27: ...0 mm 077F8798 3000 mm 077F8768 4000 mm 080G3343 2200 mm 077F8767 6000 mm 080G2029 6000 mm 080G2039 3000 mm 077F8769 3500 mm 077F8723 6000 mm 080G2019 Temperature Sensor for Cabinet Temperature Control...

Страница 28: ...l Evaporator Condenser or Ambient Light or Motion detection Door or Motion detection CFF refrigerator ERC 112C Comp Fan Lamp Control Defrost Condenser Door CFF freezer ERC 112D Comp Heater Fan Lamp Co...

Страница 29: ...peratures sensor placement in the evaporator outlet air can be considered Vertical freezers with fan Placement in the return air or in the freezer compartment Coolers without fan The best results are...

Страница 30: ...liquid side of the condenser Use a metal bracket or metal tape to ensure good thermal conductivity Be sure that the cable does not pass hot spots at the compressor or condenser that exceeds 80 C Plac...

Страница 31: ...User Guide ERC 112 Refrigeration Controller Danfoss DCS vt 2019 07 BC200686422115en 000802 31...

Страница 32: ...Danfoss DCS vt 2019 07 BC200686422115en 000802 32 ADAP KOOL...

Отзывы: