SdF

"

Min. no
Max. yes
Default yes

Show Defrost

If set to "

yES

", this parameter causes the display to show DEF when the

system is in defrost mode. If set to "

nO

", the temperature continues to 

be displayed.

"

SCS

"

Min. no
Max. yes
Default yes

Show compressor symbol

"

no

": compressor symbol will not show on display.

"

yES

": show compressor symbol on display.

"

SFS

"

Min. no
Max. yes
Default yes

Show Fan symbol

"

no

": san symbol will not show on display.

"

yES

": show fan symbol on display.

"

SdS

"

Min. no
Max. yes
Default yes

Show Defrost symbol

"

no

": defrost symbol will not show on display.

"

yES

": show defrost symbol on display.

"

SES

"

Min. no
Max. yes
Default yes

Show ECO symbol

"

no

": ECO symbol will not show on display.

"

yES

": show ECO symbol on display.

"

Ld

"

Min. -100.0°C
Max. 200.0°C
Default -100

Minimum Display value 

If the probe value is less than minimum display value mentioned in this para-
meter, it doesn't show the actual value and instead show this minimum only 
until the probe starts reading a higher value than minimum display value set 
here.

"

Hd

"

Min. -100.0°C
Max. 200.0°C
Default  200

Maximum display value 

• Controller will display actual temperature, if the probe value is between 

Maximum display value and Signaling threshold value and the trend of the 
probe is increasing (trend is based on past 10 readings)

• Controller will display Error “Err”, if the probe value is more than Signaling 

threshold value and the trend of the probe is increasing (based on the past 
10 readings)

• Controller will display “---“if the probe value is more than signaling thres-

hold and trend of the probe is decreasing (based on the past 10 readings)

• Controller will display “---“if the probe value is bigger than Max display va-

lue and the trend of the probe is decreasing (based on the past 10 readings)

"

St

"

Min. -100.0°C
Max. 200.0°C
Default 200

Signalling threshold value 

Temperature limit for Maximum display visualization

ALA

Alarm settings

"

HAt

"

Min. -100.0°C
Max. 200°C
Default 15.0°C

High Temp Alarm

Absolute value.
By setting "

HAt

" to the maximum alarms will be deactivated.

"

LAt

"

Min. -100.0°C
Max. 200°C
Default -50.0°C

Low Temp Alarm

Absolute value.
By setting "

LAt

" to the minimum value, alarms will be deactivated.

In most situations, the low alarm delay will be set to 0 to warn about
too low a temperature immediately.

"

Htd

"

Min. 0 min
Max. 240 min
Default 30 min

Alarm delay on high temperature alarm

The number of minutes to wait before sounding an alarm once the 
high temperature alarm temperature is reached.

"

Ltd

"

Min. 0 min
Max. 240 min
Default 0 min

Alarm delay on low temperature alarm

The number of minutes to wait before sounding an alarm once the
low temperature alarm temperature is reached.

User Guide | ERC 112 Refrigeration Controller

© Danfoss | DCS (vt) | 2019.07

BC200686422115en-000802 | 17

Содержание erc 112

Страница 1: ...eration Controller ERC 112 This user guide is intended to be used by OEMs for the purpose of programming ERC 112 It may also be useful for technicians However it is not intended as a user guide for en...

Страница 2: ...2 24 annex CC and EN IEC 60335 2 89 annex BB Glow wire according to EN IEC 60335 1 IEC EN 60730 UL60730 NSF CQC EAC Ukraine The access level can be set separately for each parameter using KoolProg Koo...

Страница 3: ...ass Door Merchandiser No frost freezer sub zero cooler S2 S3 S4 are optional S3 S4 are optional Gastro No frost freezer Cooler S2 S3 S4 are optional User Guide ERC 112 Refrigeration Controller Danfoss...

Страница 4: ...abinet S2 Temperature sensor for defrost S3 Temperature sensor for condenser light sensor or Motion sensor S4 Temperature sensor Pt 1000 ohm 0 C or door signal di Door signal or Motion sensor Defrost...

Страница 5: ...determined a specific parameter file is saved to the USB key for later mass programming through the docking station Mass programming on an assembly line The docking station is used for high volume pr...

Страница 6: ...le Keypad 4 buttons integrated IP65 design 2 left 2 right user programmable Operating Conditions 0 C to 55 C 93 rH Storage Conditions 40 C to 85 C 93 rH Range of Measurement 40 C to 85 C with standard...

Страница 7: ...000 ohm Door Cabinet temp sensor Evaporator temp sensor Condenser Pt 1000 ohm Door Motion Cabinet temp sensor Evaporator temp sensor Condenser Pt 1000 ohm Door Motion Cabinet temp sensor Evaporator te...

Страница 8: ...zer 27 080G3212 ERC 112D Red LED with buzzer 27 080G3213 ERC 112C Blue LED with buzzer 27 080G3216 ERC 112D Blue LED with buzzer 27 080G3217 ERC 112C Blue LED with buzzer 27 080G3233 ERC 112D Blue LED...

Страница 9: ...Press variable direct function e g ECO Night mode Sub function back 1 Press variable direct function e g light Sub function OK 1 Press temperature set point Sub function up 1 Press temperature set po...

Страница 10: ...K Max 25 K Default 0 Seasonal offset temperature This parameter is only available from Product version PV03 onwards Please check product label for Product version of your controller Offset value for s...

Страница 11: ...an be set to one of these alternatives to control the light in the cabinet on always ON oFF always OFF dor door sensor only Lod Min 0 s Max 300 s Default 0 s Light OFF delay Number of seconds the ligh...

Страница 12: ...rator sensor or by the cabinet temperature sensor if no evaporator sensor is used drt Min 0 0 C Max 200 0 C Default 5 0 C Defrost reset temperature The defrost counter is saved and restored at power u...

Страница 13: ...t Times based on elapsed time doC Min 0 hour Max 24 hour Default 0 hour Defrost by Comp running time Continuous compressor running can cause defrost 0 deactived dEt Min 50 0 C Max 0 0 C Default 50 0 C...

Страница 14: ...n Default 1 min Error Stop Time The parameter only become active in the unlikely event of a broken temperature sensor It is used to run the application in safety mode At the same time the sensor error...

Страница 15: ...denser at which an alarm will be generated CbL Min 0 C Max 200 C Default 85 C Condenser Block Limit CbL This parameter sets the temperature which if reached will cause the compressor to switch OFF CoL...

Страница 16: ...e a realistic temperature appearance for an application a display delay can be set The parameter sets the time constant tau of the moving average filter for the display Physically one time constant re...

Страница 17: ...10 readings Controller will display Error Err if the probe value is more than Signaling threshold value and the trend of the probe is increasing based on the past 10 readings Controller will display i...

Страница 18: ...have an alarm If set to 999 the alarm will continue to sound until the reason for the alarm is cleared for example the temperature has dropped enough or the door closed In some cases it may be necess...

Страница 19: ...of Door action or activity through PIR sensor mentioned in EDA and EPA parameters to exit the ECO mode Edd Min 0 min Max 180 min Default 180 min Door delay Door delay after door close to trigger ente...

Страница 20: ...respect to normal mode during holiday mode diE Min 0 0 K Max 10 0 K Default 2 0 K ECO Differential Thermostat differential for ECO FoE Min 0 s Max 960 s Default 0 s ECO Fan on cycle On time for fan du...

Страница 21: ...perature sensor input S1C Default Stn S1 Config S1C S2 Config S2C S3 Config S3C S4 Config S4C Available options are Stn for a standard temperature sensor NTC 5 K 25 C and TPE precision Htn for a high...

Страница 22: ...Default noP Button 5 Config short press b5C Button 5 Config long press b5L Button 5 is an external button option which can be connected and configured through S4 sensor b5L Default noP Short press fu...

Страница 23: ...product code ACt Accumulated Comp run time AFt Accumulated Fan run time ALt Accumulated Light run time AEt Accumulated ERC up time Sdi DI physcial DI pin state ON OFF uAC Voltage value Current main p...

Страница 24: ...nsor Et1 Evaporator1 Temp Temperature of the evaporator sensor1 Et2 Evaporator2 Temp Temperature of the evaporator sensor2 AuS AUX Temp Temperature of the AUX sensor invisible LLu Light level value Ac...

Страница 25: ...ighest temperature If configured cut in alarm relay beep the buzzer High temperature alarm Lo Air temperature is lower than LAt for Ltd User configured Blink Lo with the lowest temperature If configur...

Страница 26: ...0 mm 077F8766 3000 mm 080G3392 3000 mm 080G3342 3000 mm 080G3324 2000 mm 077F8765 3000 mm 077F8798 3000 mm 077F8768 4000 mm 080G3393 4000 mm 080G3343 2200 mm 077F8767 6000 mm 080G2029 6000 mm 080G2039...

Страница 27: ...0 mm 077F8798 3000 mm 077F8768 4000 mm 080G3343 2200 mm 077F8767 6000 mm 080G2029 6000 mm 080G2039 3000 mm 077F8769 3500 mm 077F8723 6000 mm 080G2019 Temperature Sensor for Cabinet Temperature Control...

Страница 28: ...l Evaporator Condenser or Ambient Light or Motion detection Door or Motion detection CFF refrigerator ERC 112C Comp Fan Lamp Control Defrost Condenser Door CFF freezer ERC 112D Comp Heater Fan Lamp Co...

Страница 29: ...peratures sensor placement in the evaporator outlet air can be considered Vertical freezers with fan Placement in the return air or in the freezer compartment Coolers without fan The best results are...

Страница 30: ...liquid side of the condenser Use a metal bracket or metal tape to ensure good thermal conductivity Be sure that the cable does not pass hot spots at the compressor or condenser that exceeds 80 C Plac...

Страница 31: ...User Guide ERC 112 Refrigeration Controller Danfoss DCS vt 2019 07 BC200686422115en 000802 31...

Страница 32: ...Danfoss DCS vt 2019 07 BC200686422115en 000802 32 ADAP KOOL...

Отзывы: