
"
End
"
Min. 0 min
Max. 360 min
Default 60 min
Energy Mode Delay
This is the delay in minutes between the heater and the compressor
operation. The heater is not allowed to start until this number of minutes
has expired after the compressor has cut out and vice versa.
"
AHS
"
Min. -100.0 °C
Max. 200.0 °C
Default 2.0°C
Auto Heat set point
Set point of auto heating.
"
AHd
"
Min. 0.0 K
Max. 20.0 K
Default 2.0 K
Auto heat differential
Thermostat differential for auto heatting.
ECS
ECO strategy
NOTE: some of these parameters require the installation of the Danfoss Ambient Light Sensor. The Danfoss USB Gateway in
combination with "
KoolProg Software
" allows for real time measurement of the current light intensity. Danfoss recommends test-
ing and adjusting "
SLd
" and "
SLn
" values according to customers’ specific needs.
"
ECo
"
Min. no
Max. yes
Default Yes
ECO ON/OFF
ECO active or not. If no all other settings are not active.
"
EdA
"
Min. 1
Max. 10
Default 1
Door Actions
Times of door action to trigger exiting ECO
"
EPA
"
Min. 1
Max. 10
Default 1
Pir Actions
Times of "
PIR
" action to trigger exiting ECO
"
ECt
"
Min. 0 min
Max. 180 min
Default 30 min
Action counter time
It is the duration of time for which the controller will check for number of times of Door action or activity through PIR sensor
(mentioned in "EDA" and "EPA" parameters) to exit the ECO mode.
"
Edd
"
Min. 0 min
Max. 180 min
Default 180 min
Door delay
Door delay after door close to trigger entering ECO
"
EPd
"
Min. 0 min
Max. 180 min
Default 120 min
Pir delay
"
PIR
" delay to trigger entering ECO
"
SLd
"
Min. 0
Max. 80
Default 5
Shop Light Day/SLd
Shop Light Night/SLn
These parameters are set as the percentage of the maximum light and determine when the device moves into or out of ECO
mode for power-saving purposes. Requires Light Sensor.
"
SLd
" is the amount of ambient light which will cause the device to
move to normal/serving mode from ECO mode
(normally occurs in the morning).
"
SLn
" is the amount of ambient light which will cause the device to
move to ECO mode from normal/serving mode
(normally occurs in the evening).
"
SLn
"
Min. 0
Max. 80
Default 3
"
tto
"
Min. 0 hour
Max. 168 hour
Default 0 hour
Time to pull down
Time that ERC must stay in ECO to go into Pulldown upon exiting ECO. E.g: If tto = 2, if the ERC stays in ECO for 2 or more hours, it
will go into Pulldown after exiting ECO. If it stays in ECO for less than 2 hours, it will go to Serving Mode upon exiting ECO.
"
LSd
"
Min. 0 min
Max. 180 min
Default 0 min
Light Source delay on ECO
Time delay for light source to change from serving mode source to ECO mode source.
User Guide | ERC 112 Refrigeration Controller
© Danfoss | DCS (vt) | 2019.07
BC200686422115en-000802 | 19