 EKC 316A 

Instructions  RI8HA852  ©  Danfoss  04/2009 

7

Start of controller

When the electric wires have been connected to the controller, 
the following points have to be attended to before the regulation 
starts:
1. Switch off the external ON/OFF switch that starts and stops the 

regulation.

2. Follow the menu survey and set the various parameters to the 

required values.

3. Switch on the external switch, and regulation will start.
4. Follow the actual room temperature or superheat on the 

display. 

If the superheating fluctuates

When the refrigerating system has been made to work steadily, 
the controller’s factory-set control parameters should in most 
cases provide a stable and relatively fast regulating system.
If the system however fluctuates this may be due to the fact that 
too low superheat parameters have been selected:

If adaptive superheat has been selected:

Adjust: n09, n10 and n18.

If load-defined superheat has been selected:

Adjust: n09, n10 and n22.

Alternatively it may be due to the fact that the set regulation 
parameters are not optimal.

If the time of oscillation is longer than the integration time:

(T

p

 > T

n

 , (T

n

 is, say, 240 seconds))

1. Increase T

n

 to 1.2 times T

p

2. Wait until the system is in balance again
3. If there is still oscillation, reduce K

p

 by, say, 20%

4. Wait until the system is in balance
5. If it continues to oscillate, repeat 3 and 4

If the time of oscillation is shorter than the integration time:

(T

p

 < T

n

 , (T

n

 is, say, 240 seconds))

1. Reduce K

p

 by, say, 20% of the scale reading

2. Wait until the system is in balance
3. If it continues to oscillate, repeat 1 and 2.

Check that the ETS valve closes when the 
supply voltage to the controller is interrupted

This control is performed if the controller is connected to battery 
backup.
The battery will make the step motor move to the end stop and 
thus close the valve.

The control may be omitted if a solenoid valve is mounted and 
connected via terminals 9-10.

The controller can give the following messages:

E1

Error message

Fault in controller

E15

Cut-out S2 sensor

E16

Shortcircuited S2 sensor

E17

Cut-out  S3 sensor

E18

Shortcircuited S3 sensor

E19

The input signal on terminals 16-17 is outside 
the range.

E20

The input signal on terminals 14-15 is outside 
the range (P0 signal)

A1

Alarm message

High-temperature alarm

A2

Low-temperature alarm

A11

No refrigerant has been selected

A43

Check the supply voltage to the step motor

A44

Battery alarm (no voltage or too low voltage)

Miscellaneous

Controller’s address

o03*** 0

119

0

ON/OFF switch (service-pin message)

o04*** -

-

-

Define input signal on the analoge input AIA:
0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3:  Displacement of superheat reference. 0-20 mA
4:  Displacement of superheat reference. 4-20 mA
5: Forced control of valve's max. opening degree. 
0-20 mA
6: Forced control of valve´s max. opening degree 
4-20 mA

o10

0

6

0

Set supply voltage frequency

o12

50 Hz

60 Hz

50

Select display for ”normal picture”
1:  Superheat
2:  Valve’s opening degree
3:  Air temperature

o17

1

3

1

Manual control of outputs:
OFF: no manual control 
1:  Relay for solenoid valve: select ON
2: Relay for solenoid valve: select OFF
3: Alarm relay activated (cut out)
4: Forced control of valve's opening degree. 0-20 
mA
5: Forced control of valve´s opening degree 4-20 
mA
At settings 1-3, ”o45” will be active

o18

off

5

0

Working range for pressure transmitter – min. 
value

o20

-1 bar

60 bar

-1.0

Working range for pressure transmitter – max. 
value

o21

-1 bar

60 bar

12.0

Refrigerant setting
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  
6=R13.  7=R13b1.  8=R23.  9=R500.  10=R503.  
11=R114.  12=R142b. 13=User defined. 14=R32. 
15=R227.  16=R401A.  17=R507. 18=R402A.  
19=R404A. 20=R407C.  21=R407A.  22=R407B.  
23=R410A.  24=R170.  25=R290.  26=R600.  
27=R600a.  28=R744.  29=R1270.

o30

0

29

0

Manual control of the valve’s opening degree. 
The function can only be operated if ”o18” has 
been set.

o45

0 %

100 %

0

Selection of control mode:
1=Normal  
2 = With inner loop (T0)
3 = With inner loop (S media temperature less T0)

o56

1

3

1

Service

Analog input AIA (16-17)

u06

mA

Read status of input DI

u10

on/off

Thermostat cut-in time

u18

min.

Temperature at S2 sensor

u20

°C

Superheat

u21

K

Superheat reference

u22

K

Read AKV valve’s opening degree

u24

%

Read evaporating pressure

u25

bar

Read evaporating temperature

u26

°C

Temperature at S3 sensor

u27

°C

Temperature reference

u28

°C

Read signal at pressure transmitter input

u29

mA

***) This setting will only be possible if a data communication module has been 
installed in the controller.
Configuration settings available only when regulation is stopped.

Содержание EKC 316A

Страница 1: ...Princip Principle Montageprinzip Principe M l Dimensions Ma e Dimensions Instructions EKC 316A RI8HA852 04 2009 Identifikation Identification 084B7088...

Страница 2: ...arat litteratur nr RC8AC Necessary connections Terminals 25 26 Supply voltage 24 V a c 21 24 Supply to step motor 18 19 Pt 1000 sensor at evaporator outlet S2 14 15 Pressure transmitter type AKS 33 1...

Страница 3: ...beachten dass die Installation des Daten kommunikationskabels korrekt vorgenommen wird Siehe separate Literatur Nr RC8AC Raccordements n cessaires Bornes 25 26 Tension d alimentation 24 V c a 21 24 Te...

Страница 4: ...ineres i o17 K Hvis du vil se ekspansionsventilens aktuelle b ningsgrad skal du trykke kortvarigt 1s p den nederste knap Visningen defineres i o17 Reference Indstil det nskede setpunkt for termostaten...

Страница 5: ...et A1 Alarmmeddelelse H jtemperaturalarm A2 Lavtemperaturalarm A11 Der er ikke valgt k lemiddel A43 Kontroll r forsyningssp ndingen til stepmo toren A44 Batterialarm ingen eller for lav sp nding Defin...

Страница 6: ...display Shows the actual superheat valve s opening degree temperature Define view in o17 K If you wish to see the expansion valve s actual opening degree give the lower button a brief push 1s Define...

Страница 7: ...e range E20 The input signal on terminals 14 15 is outside the range P0 signal A1 Alarm message High temperature alarm A2 Low temperature alarm A11 No refrigerant has been selected A43 Check the suppl...

Страница 8: ...p Die Anzeige wird in o17 definiert K Zur Anzeige des aktuellen ffnungsgrads des Expansionsventils kurzzeitig 1 Sek die unterste Taste bet tigen Die Anzeige wird in o17 definiert Referenz Einstellung...

Страница 9: ...rmmitteilung Hoch Temperaturalarm A2 Tief Temperaturalarm A11 Kein K ltemittel gew hlt A43 Leistungsspannung zum Schrittmotor kont rollieren A44 Batterie alarm keine oder niedrige Spannung Regleradres...

Страница 10: ...glage de la consigne du thermostat 60 C 50 C 3 0 Diff rentiel r01 0 1 K 20 0 K 2 0 Unit s 0 C bar 1 F psig r05 0 1 0 Suppl ment externe de la r f rence r06 50 K 50 K 0 0 Correction du signal en proven...

Страница 11: ...d placer jusqu la fin de course et de fermer le d tendeur Si une lectrovanne est install e et raccord e aux bornes 9 10 ce contr le peut tre omis Adresse du r gulateur o03 0 119 0 Commutateur ON OFF m...

Страница 12: ...12 Instructions RI8HA852 Danfoss 04 2009 EKC 316A DE BD...

Отзывы: