Instructions  RI8KX753   ©  Danfoss  09/2016 

   EKC 202D / EKC 302D

*) Can only be set when regulation is stopped (r12=0)

**) Can be controlled manually, but only when r12=-1

***)  With access code 2 the access to these menus will be limited

Access code 1 (all settings)

o05

0

100

0

Used sensor type (Pt /PTC/NTC)

o06

Pt

ntc

Pt

Only EKC 302D: Readout of software version

o08

Display step = 0.5 (normal 0.1 at Pt sensor)

o15

no

yes

no

Max hold time after coordinated defrost

o16

0 min

60 min

20

Select signal for display view.  S4% (100%=S4, 0%=S3)

o17

0%

100%

100%

Input signal on DI2. Function: 

0=not used. 1=status on DI2. 2=door function with 

alarm when open. 3=door alarm when open. 4=defrost 

start (pulse-signal).  5=ext. main switch 6=night 

operation 7=change reference (activate r40). 8=alarm 

function when closed. 9=alarm function when open. 

10=case cleaning (pulse signal). 11=forced cooling. 

12=coordinated defrost. 13=case shut down (302D).

o37

0

13

0

Configuration of light function (relay 4)

1=ON during day operation. 2=ON / OFF via data com-

munication. 3=ON follows the DI-function, when DI is 

selected to door function or to door alarm

o38

1

3

1

Activation of light relay (only if o38=2)

o39

OFF

ON

OFF

Rail heat On time during day operations

o41

0%

100%

100

Rail heat On time during night operations

o42

0%

100%

100

Rail heat period time (On time + Off time)

o43

6 min

60 min 10 min

Case cleaning. 0=no case cleaning. 1=Fans only. 2=All 

output Off.

***

o46

0

2

0

Selection of  EL diagram. See overview page 2

*

o61

1

2

3

1

3

1

Access code 2 (partly access)

***

o64

0

100

0

EKC 202D only: Save the controllers present settings to 

the programming key. Select your own number. 

o65

0

25

0

EKC 202D only: Load a set of settings from the pro-

gramming key (previously saved via o65 function)

o66

0

25

0

Replace the controllers factory settings with the 

present settings

o67

OFF

On

OFF

Service

Status codes

S0-S33

Temperature measured with S5 sensor

***

u09

Status on DI1 input. on/1=closed

u10

Temperature measured with S3 sensor

***

u12

Status on night operation (on or off) 1=closed

***

u13

Temperature measured with S4 sensor

***

u16

Thermostat temperature

u17

Read the present regulation reference

u28

Status on DI2 output. on/1=closed

u37

Temperature shown on display

u56

Measured temperature for alarm thermostat

u57

Status on relay for cooling

**

u58

Status on relay for fan

**

u59

Status on relay for defrost

**

u60

Status on relay for railheat

**

u61

Status on relay for alarm

**

u62

Status on relay for light

**

u63

The buttons

Set menu

1. Push the upper button until a parameter 

r01 is shown

2. Push the upper or the lower button and 

find that parameter you want to change

3. Push the middle button until the 

parameter value is shown

4. Push the upper or the lower button and 

select the new value

5. Push the middle button again to enter 

the value.

Cutout alarm relay / receipt alarm/see alarm 

code 

• Push short the upper button

Set temperature

1. Push the middle button until the 

temperature value is shown

2. Push the upper or the lower button and 

select the new value

3. Push the middle button to select the 

setting.

Reading the temperature at defrost sensor

• Push briefly the lower button

Manuel start or stop of a defrost

• Push the lower button for four seconds.

 

LED

  Light emitting diode

 

 = refrigeration

 

 = defrost

 

 = fan running

Flashes fast at alarm

Fault code display

E 1

Fault in controller

E 6

EKC 202D: Change b check 

clock

EKC 302D: Reset the clock

E 25

S3 sensor error

E 26

S4 sensor error

E 27

S5 sensor error

Alarm code display

A 1

High temperature alarm

A 2

Low  temperature alarm

A 4

Door alarm

A 5

Max. Hold time

A 15

DI 1 alarm

A 16

DI 2 alarm

A 45

Standby mode

A 59

Case cleaning

Status code display

S0

Regulating

S 1

Waiting for end of the coordinated 

defrost

S 2

ON-time Compressor

S 3

OFF-time Compressor

S 4

Drip-off time

S 10

Refrigeration stopped by main 

switch

S 11

Refrigeration stopped by thermostat

S 14

Defrost sequence. Defrosting

S 15

Defrost sequence. Fan delay

S 17

Door open (open DI input)

S 20

Emergency cooling

S 25

Manual control of outputs

S 29

Case cleaning

S 30

Forced cooling

S 32

Delay of output at start-up

S 45

Case shut down. Only EKC 302D

non

The defrost temperature cannot 

be displayed. There is stop based 

on time

-d-

Defrost in progress

PS

Password required

Factory setting

If you need to return to the factory-set values, it can be done in this way:

- Cut out the supply voltage to the controller

- Keep upper and lower button depressed at the same time as you recon nect the supply voltage

Содержание EKC 302D

Страница 1: ...A 60 LRA 2 DO2 6 3 A 3 FLA 18 LRA 1 10 6 A 5 FLA 30 LRA 2 DO3 6 3 A 3 FLA 18 LRA 1 10 6 A 5 FLA 30 LRA 2 DO4 4 1 A Min 100 mA EKC 202D DO1 and DO2 are 16 A relays DO3 and DO4 are 8 A relays Above max...

Страница 2: ...2 Instructions RI8KX753 Danfoss 09 2016 EKC 202D EKC 302D 1 3 Danfoss 84B2428 12 Danfoss 84B2429 13 Danfoss 84B2430 13 DI1 DI2 AU Guld Gold Or Oro l max 15 m 2 EKC 202D o61 1 2 3 EKC 302D o61...

Страница 3: ...Nulgennemgangsstyring kun EKC 302D Skal v re ON ved tilslutning til eksterne rel er C70 OFF ON ON Afrimning Afrimningsmetode ingen EL GAS BRINE d01 no bri EL Afrimnings stoptemperatur d02 0 0 C 25 0 C...

Страница 4: ...ntvarme On tid under natdrift o42 0 100 100 Kantvarme periodetid On tid Off tid o43 6 min 60 min 10 min M belreng ring 0 ingen m belreng ring 1 kun ventilatorer 2 Alle udgange er OFF o46 0 2 0 Valg af...

Страница 5: ...out inversely NC function c30 0 OFF 1 ON 0 OFF External relays zero crossing control only EKC 302D Must be ON when connecting to external relays c70 OFF ON ON Defrost Defrost method none EL GAS BRINE...

Страница 6: ...us on DI2 output on 1 closed u37 Temperature shown on display u56 Measured temperature for alarm thermostat u57 Status on relay for cooling u58 Status on relay for fan u59 Status on relay for defrost...

Страница 7: ...is 1 muss entgegengesetzt schalten NC Funktion c30 0 OFF 1 ON 0 OFF Externe Relais Nulldurchgangsregelung nur EKC 302D Muss beim Anschluss an externe Relais ON EIN sein c70 OFF ON ON Abauung Abtaumeth...

Страница 8: ...am DI2 Ausgang 1 geschlossen u37 Temperaturanzeige auf dem Display u56 Gemessene Temperatur f r den Alarmthermostaten u57 Status am Relais f r K hlung u58 Status am Relais f r L fter u59 Status am Re...

Страница 9: ...ers le thermostat d alarme S4 100 S4 0 S3 A36 0 100 100 Compresseur Temps de marche min c01 0 min 30 min 0 min Intervalle entre deux d marrages c02 0 min 30 min 0 min Le relais de compresseur 1 doit a...

Страница 10: ...du r gime de nuit tout ou rien 1 enclench u13 Temp rature relev e par la sonde S4 u16 Temp rature du thermostat u17 Affichage de la r f rence de r gulation actuelle u28 Etat de la sortie DI2 On 1 encl...

Страница 11: ...cionamiento de la salida DO1 compresor c30 0 OFF 1 ON 0 OFF Rel s externos control de cruce cero solo el EKC 302D Debe configurarlo en ON cuando lo conecte a rel s externos C70 OFF ON ON Desescarche T...

Страница 12: ...stado del rel de antivaho u61 Estado del rel de alarma u62 Estado del rel de luz u63 Los botones Ajustar par metros 1 Pulsar el bot n superior hasta que aparece el par metro r01 2 Pulsar los botones a...

Отзывы: