 EKC 202D / EKC 302D 

Instructions  RI8KX753  ©  Danfoss  09/2016 

5

Setting:

1 Open parameter r12 and stop the 

regulation

2 Select electric connection based on 

the drawings on page 2

3 Open parameter o61 and set the elec-

tric connection number in it

4 Open parameter r12 and start the 

regulation

5 Go through the survey of factory set-

tings. Make any necessary changes in 

the respective parameters.

6 For network. Set the address in o03 

and start scanfunction in the system 

manager.

English

Parameters

EL-diagram 

number 

(page 2)

Min.-

value

Max.-

value

Factory 

setting

Actual 

setting

Function

Codes 1

2

3

Normal operation

Temperature (set point)

---

-50.0°C

50.0°C

2.0°C

Thermostat

Differential

***

r01

0.0 K

20.0K

2.0 K

Max. limitation of setpoint setting

***

r02

-49.0°C

50°C

50.0°C

Min. limitation of setpoint setting

***

r03

-50.0°C

49.0°C

-50.0°C

Adjustment of temperature indication

r04

-20.0 K

20.0 K

0.0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from S4

r09

-10.0 K +10.0 K

0.0 K

Correction of the signal from S3

r10

-10.0 K +10.0 K

0.0 K

Manual service, stop regulation, start regulation (-1, 

0, 1)

r12

-1

1

0

Displacement of reference during night operation

r13

-10.0 K

10.0 K

0.0 K

Definition and weighting, if applicable, of thermostat 

sensors - S4% (100%=S4,  0%=S3)

r15

0%

100%

100%

Activation of reference displacement  r40

r39

OFF

ON

OFF

Value of reference displacement (activate via r39 or DI)

r40

-50.0 K

50.0 K

0.0 K

Alarm

Delay for temperature alarm

A03

0 min 240 min 30 min

Delay for door alarm

***

A04

0 min 240 min 60 min

Delay for temperature alarm after defrost

A12

0 min 240 min 90 min

High alarm limit

***

A13

-50.0°C

50.0°C

8.0°C

Low alarm limit

***

A14

-50.0°C

50.0°C

-30.0°C

Alarm delay DI1

A27

0 min 240 min 30 min

Alarm delay DI2

A28

0 min 240 min 30 min

Signal for alarm thermostat. S4% (100%=S4, 0%=S3)

A36

0%

100%

100%

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Compressor relay 1 must cutin and out inversely

(NC-function)

c30

0

OFF

1

ON

0

OFF

External relays (zero-crossing control – only EKC 302D)

Must be 'ON' when connecting to external relays

c70

OFF

ON

ON

Defrost

Defrost method (none/EL/GAS/BRINE)

d01

no

bri

EL

Defrost stop temperature

d02

0.0°C

25.0°C

6.0°C

Interval between defrost starts

d03

0 hours 48 hours 8 hours

Max. defrost duration

d04

0 min 180 min 45 min

Displacement of time on cutin of defrost at start-up

d05

0 min 240 min 0 min

Drip off time

d06

0 min

60 min

0 min

Delay for fan start after defrost

d07

0 min

60 min

0 min

Fan start temperature

d08

-15.0°C

0.0°C

-5.0°C

Fan cutin during defrost

0: Stopped

1: Running

2: Running during  pump down and defrost

d09

0

2

1

Defrost sensor (0=time, 1=S5, 2=S4)

d10

0

2

0

Pump down delay

d16

0 min

60 min

0 min

Max. aggregate refrigeration time between two 

defrosts

d18

0 hours 48 hours 0 hours

Defrost on demand - S5 temperature’s permitted vari-

ation during frost build-up. On central plant choose 

20 K (=off)

d19

0.0 K

20.0 k

20.0 K

Fan

Fan stop at cutout compressor

F01

no

yes

no

Delay of fan stop

F02

0 min

30 min

0 min

Fan stop temperature (S5)

F04

-50.0°C

50.0°C

50.0°C

Real time clock

Six start times for defrost. 

Setting of hours. 

0=OFF

t01-

t06

0 hours 23 hours 0 hours

Six start times for defrost.

Setting of minutes.

0=OFF

t11-

t16

0 min

59 min

0 min

Clock - Setting of hours

***

t07

0 hours 23 hours 0 hours

Clock - Setting of minute

***

t08

0 min

59 min

0 min

Clock - Setting of date

***

t45

1

31

1

Clock - Setting of month

***

t46

1

12

1

Clock - Setting of year

***

t47

0

99

0

Miscellaneous

Delay of output signals after start-up

o01

0 s

600 s

5 s

Input signal on DI1. Function:

0=not used. 1=status on DI1. 2=door function with 

alarm when open. 3=door alarm when open. 4=defrost 

start (pulse-signal).  5=ext.main switch. 6=night 

operation 7=change reference (activate r40). 8=alarm 

function when closed. 9=alarm function when open. 

10=case cleaning (pulse signal). 11=forced cooling. 

12=not used. 13=case shut down (302D).

o02

1

13

0

Network address (0= off)

o03

0

240

0

On/Off switch (Service Pin message)

IMPORTANT! o61 

must

 be set prior to o04

o04

OFF

ON

OFF

EKC 202D: SW = 2.2x

EKC 302D: SW = 1.2x

Содержание EKC 302D

Страница 1: ...A 60 LRA 2 DO2 6 3 A 3 FLA 18 LRA 1 10 6 A 5 FLA 30 LRA 2 DO3 6 3 A 3 FLA 18 LRA 1 10 6 A 5 FLA 30 LRA 2 DO4 4 1 A Min 100 mA EKC 202D DO1 and DO2 are 16 A relays DO3 and DO4 are 8 A relays Above max...

Страница 2: ...2 Instructions RI8KX753 Danfoss 09 2016 EKC 202D EKC 302D 1 3 Danfoss 84B2428 12 Danfoss 84B2429 13 Danfoss 84B2430 13 DI1 DI2 AU Guld Gold Or Oro l max 15 m 2 EKC 202D o61 1 2 3 EKC 302D o61...

Страница 3: ...Nulgennemgangsstyring kun EKC 302D Skal v re ON ved tilslutning til eksterne rel er C70 OFF ON ON Afrimning Afrimningsmetode ingen EL GAS BRINE d01 no bri EL Afrimnings stoptemperatur d02 0 0 C 25 0 C...

Страница 4: ...ntvarme On tid under natdrift o42 0 100 100 Kantvarme periodetid On tid Off tid o43 6 min 60 min 10 min M belreng ring 0 ingen m belreng ring 1 kun ventilatorer 2 Alle udgange er OFF o46 0 2 0 Valg af...

Страница 5: ...out inversely NC function c30 0 OFF 1 ON 0 OFF External relays zero crossing control only EKC 302D Must be ON when connecting to external relays c70 OFF ON ON Defrost Defrost method none EL GAS BRINE...

Страница 6: ...us on DI2 output on 1 closed u37 Temperature shown on display u56 Measured temperature for alarm thermostat u57 Status on relay for cooling u58 Status on relay for fan u59 Status on relay for defrost...

Страница 7: ...is 1 muss entgegengesetzt schalten NC Funktion c30 0 OFF 1 ON 0 OFF Externe Relais Nulldurchgangsregelung nur EKC 302D Muss beim Anschluss an externe Relais ON EIN sein c70 OFF ON ON Abauung Abtaumeth...

Страница 8: ...am DI2 Ausgang 1 geschlossen u37 Temperaturanzeige auf dem Display u56 Gemessene Temperatur f r den Alarmthermostaten u57 Status am Relais f r K hlung u58 Status am Relais f r L fter u59 Status am Re...

Страница 9: ...ers le thermostat d alarme S4 100 S4 0 S3 A36 0 100 100 Compresseur Temps de marche min c01 0 min 30 min 0 min Intervalle entre deux d marrages c02 0 min 30 min 0 min Le relais de compresseur 1 doit a...

Страница 10: ...du r gime de nuit tout ou rien 1 enclench u13 Temp rature relev e par la sonde S4 u16 Temp rature du thermostat u17 Affichage de la r f rence de r gulation actuelle u28 Etat de la sortie DI2 On 1 encl...

Страница 11: ...cionamiento de la salida DO1 compresor c30 0 OFF 1 ON 0 OFF Rel s externos control de cruce cero solo el EKC 302D Debe configurarlo en ON cuando lo conecte a rel s externos C70 OFF ON ON Desescarche T...

Страница 12: ...stado del rel de antivaho u61 Estado del rel de alarma u62 Estado del rel de luz u63 Los botones Ajustar par metros 1 Pulsar el bot n superior hasta que aparece el par metro r01 2 Pulsar los botones a...

Отзывы: