Manual 

Superheat Controller EIM 336

System configuration

The EIM 336 controller is designed to be operated via modbus and 

to rely on a constant connection to the master controller of the 

system it is located within. 

In this configuration the master controller reads the readout 

registers from the EIM 336 and uses the parameters to change the 

control behaviour of the EIM 336 (see parameter list). 

The following control modes are available:

 

ƒ

Minimum Stable Superheat search (MSS) is the default control 

mode

 

ƒ

Manual control

 

ƒ

Defrost 

 

ƒ

Maximum Operating Pressure control (MOP)

 

ƒ

Te control (De-humidifying) 

 

 

 

 

 

Standalone configuration (no modbus communication)

The EIM 336 can be set in a standalone configuration by setting 

the “HWMainSwitch” to 1. This will setup the S4 input to be used as 

a hardware main switch. 

Note that the only external control of the EIM 336 in this 

configuration is through the hardware main switch. 

The following control modes are available:

 

ƒ

Minimum Stable Superheat search (MSS) is the default control 

mode

 

ƒ

Maximum Operating Pressure control (MOP), but the Diff MOP 

option is not available 

The following control modes are not available:

 

ƒ

Manual control

 

ƒ

Defrost 

 

ƒ

T

e

 control (De-humidifying) 

Configuration

Controlling manually via modbus

When setting the manual control register “o18 Manual ctrl.” to 1, 

the controller will be in manual control. During this mode the 

opening degree is controlled by setting the “Manual OD%”. The 

manual control mode does not depend on the “r12 Main Switch”, 

and will set the opening degree regardless of its setting.

Setting “o18 Manual ctrl.” to 0 again, the controller will assume 

normal control, and will open or close from the current opening 

degree.

Related parameters:

Symbolic name

PNU

Description 

o18 Manual ctrl.

2075

0 = Superheat control, 

1 = Manual control

o45 Manual OD%

2064

Manual opening degree in percent. 

0 = fully closed, 

100 = fully open. 

Used when the o18 Manual Control is 

set to 1.

 

  Note: 

On using system configuration , it is necessary to read the 

"Ctrl Stats" register 3100 continuosly, failure to do so will start the 

MSS regulation automatically irrespective to the different status of 

the  External main switch. Refer Appendix 1 for detail.

 

 

Using stand alone configuration

The EIM 336 is designed to operate in conjunction with a system 

master controller, which will control the settings and mode of 

the EIM 336 via modbus. It is however possible to use it as a 

standalone controller by setting the “HWMainSwitch” to 1. This will 

setup the S4 input to be used as a digital input main switch. When 

the main switch is OFF, the valve opening degree will be 0%, when 

it is ON the opening degree is controlled with the settings in the 

registers, and the sensor inputs. 

 

  Note:

That the only external control of the EIM 336 in this configuration 

is through the hardware main switch. It is not possible to manually 

control the opening degree or change settings, and the defrost 

and Te control modes are not available.

Related parameters:

Symbolic name

PNU

Description 

--- HWMainSwitch

64100

0 = no external main switch, 

1 = S4 input is main switch

ETS 6

S4

EIM 336

Modbus

Danf

oss

80G41.11

EIM 336

S4 = 1

Danf

oss

80G40.11

ETS 6

Содержание EIM 336

Страница 1: ...ess noise The EIM 336 is the superheat controller that can be used to control the opening degree of a valve based on the superheat of the evaporator This is applicable in applications such as air cond...

Страница 2: ...allation sensors 17 Warnings 17 Acronyms and abbreviations used in this manual LOC Loss of charge indication SH Superheat MOP Maximum operating pressure MSS Minimum stable superheat Te Saturated sucti...

Страница 3: ...densed Superheat close When the superheat is below a set minimum value the valve will close faster in order to protect the compressor from the risk of getting liquid in the suction line Manual control...

Страница 4: ...S2 PT1000 S4 PT1000 or digital input from external contact EEV driver Max current 150 mA EEV Uni or bipolar coil Data communication RS485 Modbus RTU Environment Storage 34 C to 71 C 30 F to 160 F Ope...

Страница 5: ...odbus address stored in PNU no 40041 default 165 Jumper not mounted Outdoor unit condenser Modbus address stored in PNU no 40042 default 164 Com KM5 1 Drain D 2 RS485 TxD RxD 3 RS485 TxD RxD 4 Not Use...

Страница 6: ...trol mode does not depend on the r12 Main Switch and will set the opening degree regardless of its setting Setting o18 Manual ctrl to 0 again the controller will assume normal control and will open or...

Страница 7: ...secondary address is 164 Note Changes to these parameters will become active immediately This means that a modbus tool or controller that changes these settings will loose connection to the EIM 336 an...

Страница 8: ...e controller is powered the valve will first be closed fully so that the controller starts from a known opening degree 0 In order to make sure that it is fully closed the valve will be closed 100 plus...

Страница 9: ...sensor value will be used 5 Configuring the superheat control The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat sett...

Страница 10: ...um operation pressure If Pe goes above this value the controller will control on Pe and not on superheat Kp MOP 3113 Kp proportional gain while in MOP control mode Tn MOP 3114 Tn integration time whil...

Страница 11: ...05 Timer to trigger LOC alarm LOC Alarm 50006 Loss of charge alarm flag 0 no alarm 1 LOC alarm LOC SH Trig 50007 SH error trigger level for LOC alarm LOC Tmr 3102 Loss Of Charge time readout displays...

Страница 12: ...t regulation response Very low value give the risk of unstable regulation For Danfoss only 3105 SHL SH Low 3 20 6 K Superheat low setting for non linear control 3106 SHH SH High 8 40 16 K Superheat hi...

Страница 13: ...ext S2 temp 200 200 0 C External S2 This value can be used instead of a sensor This register must be written at least every 5 seconds otherwise the sensor value will be used 2646 TS4 ext S4 Air temp 2...

Страница 14: ...ain Switch 64309 Manual OD as steps 0 1 0 Enable the manual OD in o45 to be entered as halfsteps Readouts are still in percent Service Alarm 2046 RAL Reset alarm 0 1 0 1 clear alarm 20001 EKC Error 0...

Страница 15: ...troller will go to either the low or high boundary de pending on the error The highest value will be shown if the signal is above the maximum value The lowest value will be shown if the signal is belo...

Страница 16: ...it 3 Bit 2 Bit 1 Bit 0 Unused MOP Active Close Timer active Sensor Errors Control state Variables parameters CTRLstatus bit 0 3 Controlstate 0 closed 1 Error 2 Inject 3 De humidify 4 Force OD 5 Defros...

Страница 17: ...ght after the evaporator If the measured value is 1 2 K lower than the actual value of Pe right after the evaporator it may cause the evaporator to flood This is the case when the pressure transmitter...

Отзывы: