Superheat Controller EIM 336

Related parameters:

Symbolic name

PNU

Description 

--- Def Activate

50011 Defrost activating, 0 = no defrost, 1 = defrost active

--- Def Hold OD

50008 Opening degree during Def Hold Ti 1

--- Def HoldTi 1

50009 Defrost hold time 1

--- Def HoldTi 2

50010 Defrost hold time 2

--- DefHold shdw

64305 Copy of 50008.  If it is required to write Def Hold OD frequently, this should be used instead.

Defrosting

A defrost sequence is initiated by setting the defrost activate 

register “Def Activate” to 1. As long as this register is kept at 1, the 

valve opening degree is 100%. When “Def Activate” returns to 0, 

the valve opening degree is kept at “Def Hold OD” for “Def Hold Ti 

1” seconds. When this time expires, the valve opening degree is set 

to a calculated average opening degree for “Def Hold Ti 2” seconds. 

When this time expires the controller resumes normal operation.

 

  Note:

That defrost is not initiated by the EIM 336, but must be initiated 

by the master controller. In a standalone configuration the defrost 

mode is not possible. 

If a more dynamic control of the opening degree during defrost is 

required, the user should disable the “Def Hold Ti 2” by setting it 

to 0, and only use the “Def Hold Ti 1”. If frequent changes are to be 

made to the “Def Hold OD”, the parameter “DefHold shdw” should 

be used instead. This parameter is an exact copy of the “Def Hold 

OD” except that it is not placed in the Eeprom. 

Related parameters:

Symbolic name

PNU

Description 

--- LOC Trig

50003 Trigger value for loss of charge

--- LOC Reset

50004 Reset value for loss of charge

--- LOC Timer

50005 Timer to trigger LOC alarm

--- LOC Alarm

50006 Loss of charge alarm flag, 0 = no alarm, 1 = LOC alarm

--- LOC SH Trig

50007 SH error trigger level for LOC alarm

--- LOC Tmr

3102

Loss Of Charge time readout displays the elapsed time since the alarm became active.

LOC detection

When a system loses refrigerant charge the controller will have 

difficulties keeping the superheat low, even when increasing the 

valve opening degree. Therefore, if both the valve opening degree 

and the superheat are high for a long period of time, this could 

indicate that refrigerant charge was lost. 

When the valve opening degree exceeds the trigger level "LOC 

Trig, and the superheat exceeds the superheat trigger level "LOC 

SH Trig", a timer is started. 

When the timer exceeds the user defined time “LOC Timer” the 

“LOC Alarm” is set. If the valve opening degree drops below the 

user defined reset level “LOC Reset”, the timer and the alarm are 

reset. 

The loss of charge alarm does not perform any actions, except 

setting the “LOC Alarm”.

Related parameters:

Symbolic name

PNU

Description 

--- Reset alarm

2046

1 = Clear alarm

--- EKC Error

20001 Common error flag. EKC Error is SET if any other Error Alarm is ON.

--- S2 Error

20002 S2 sensor error. If the sensor error occurs, the valve OD will be set to 80% of the Avg. opening (PNU 50021) - see

troubleshooting.

--- Pe inp.error

20005 Pressure transmitter out of range. If the sensor error occurs, the valve OD will be set to 80% of the Avg. opening (PNU

50021) - see troubleshooting

--- No Rfg. Sel.

20006 Refrigerant not selected 

--- LOC Alarm

50006 Loss of charge alarm. No action will be performed except setting the alarm.

--- Ctrl Status

3100

Bit mappped status register, see also appendix 2

Alarms and clearing alarms

Several alarms are registered and made available on modbus. Most 

of these are automatically cleared when the error is no longer 

present. 

Содержание EIM 336

Страница 1: ...ess noise The EIM 336 is the superheat controller that can be used to control the opening degree of a valve based on the superheat of the evaporator This is applicable in applications such as air cond...

Страница 2: ...allation sensors 17 Warnings 17 Acronyms and abbreviations used in this manual LOC Loss of charge indication SH Superheat MOP Maximum operating pressure MSS Minimum stable superheat Te Saturated sucti...

Страница 3: ...densed Superheat close When the superheat is below a set minimum value the valve will close faster in order to protect the compressor from the risk of getting liquid in the suction line Manual control...

Страница 4: ...S2 PT1000 S4 PT1000 or digital input from external contact EEV driver Max current 150 mA EEV Uni or bipolar coil Data communication RS485 Modbus RTU Environment Storage 34 C to 71 C 30 F to 160 F Ope...

Страница 5: ...odbus address stored in PNU no 40041 default 165 Jumper not mounted Outdoor unit condenser Modbus address stored in PNU no 40042 default 164 Com KM5 1 Drain D 2 RS485 TxD RxD 3 RS485 TxD RxD 4 Not Use...

Страница 6: ...trol mode does not depend on the r12 Main Switch and will set the opening degree regardless of its setting Setting o18 Manual ctrl to 0 again the controller will assume normal control and will open or...

Страница 7: ...secondary address is 164 Note Changes to these parameters will become active immediately This means that a modbus tool or controller that changes these settings will loose connection to the EIM 336 an...

Страница 8: ...e controller is powered the valve will first be closed fully so that the controller starts from a known opening degree 0 In order to make sure that it is fully closed the valve will be closed 100 plus...

Страница 9: ...sensor value will be used 5 Configuring the superheat control The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat sett...

Страница 10: ...um operation pressure If Pe goes above this value the controller will control on Pe and not on superheat Kp MOP 3113 Kp proportional gain while in MOP control mode Tn MOP 3114 Tn integration time whil...

Страница 11: ...05 Timer to trigger LOC alarm LOC Alarm 50006 Loss of charge alarm flag 0 no alarm 1 LOC alarm LOC SH Trig 50007 SH error trigger level for LOC alarm LOC Tmr 3102 Loss Of Charge time readout displays...

Страница 12: ...t regulation response Very low value give the risk of unstable regulation For Danfoss only 3105 SHL SH Low 3 20 6 K Superheat low setting for non linear control 3106 SHH SH High 8 40 16 K Superheat hi...

Страница 13: ...ext S2 temp 200 200 0 C External S2 This value can be used instead of a sensor This register must be written at least every 5 seconds otherwise the sensor value will be used 2646 TS4 ext S4 Air temp 2...

Страница 14: ...ain Switch 64309 Manual OD as steps 0 1 0 Enable the manual OD in o45 to be entered as halfsteps Readouts are still in percent Service Alarm 2046 RAL Reset alarm 0 1 0 1 clear alarm 20001 EKC Error 0...

Страница 15: ...troller will go to either the low or high boundary de pending on the error The highest value will be shown if the signal is above the maximum value The lowest value will be shown if the signal is belo...

Страница 16: ...it 3 Bit 2 Bit 1 Bit 0 Unused MOP Active Close Timer active Sensor Errors Control state Variables parameters CTRLstatus bit 0 3 Controlstate 0 closed 1 Error 2 Inject 3 De humidify 4 Force OD 5 Defros...

Страница 17: ...ght after the evaporator If the measured value is 1 2 K lower than the actual value of Pe right after the evaporator it may cause the evaporator to flood This is the case when the pressure transmitter...

Отзывы: