Superheat Controller EIM 336

Troubleshooting    

Symptom

Possible Cause

Remedy

Suction pressure too low

Pressure drop across the evaporator too high

Lack of subcooling ahead of expansion valve

Check refrigerant ahead of expansion valve.

If the valve is placed much higher than condenser outlet, 

check pressure difference.

Evaporator superheat too high

1.  Check superheat performance, the settings  

 

       SH min and SH max.

2.  Check valve capacity.

3.  Check that the maximum number of steps of  

 

       valve is same as parameter n37.

Pressure drop across the expansion valve less than valve is 

sized for

Check pressure drop across expansion valve. Replace with 

larger valve.

Expansion valve too small

Check refrigeration system capacity and compare with 

expansion valve capacity. Replace with larger valve if neces-

sary.

Expansion valve block with foreign material 

Remove valve and examine the orifice.

Evaporator wholly or partly iced up

De-ice evaporator

Liquid hammer 

in compressor

Superheat of expansion valve too low

Increase the values of SH close and SH min.

Superheat reference set too low

Increase the value  of  SH min

The S2 sensor not in good contact with the suction line

Ensure that S2 sensor is secured on suction line. Insulate 

sensor.

S2 sensor error: PNU 20002 Bad connection or damaged S2 sensor

The controller will go to either the low or high boundary 

depending on the error. The lowest value will be shown at a 

short circuit. The highest value will be shown for a missing 

connection. Check the temperature sensors.

AKS32R out of range: PNU 

20005

The suction pressure is above the maximum limit or below 

the minimum limit

The controller will go to either the low or high boundary de-

pending on the error. The highest value will be shown if the 

signal is above the maximum value. The lowest value will 

be shown if the signal is below the minimum value or for a 

missing connection. Check the pressure range.

Finding the optimum settings

Details on the controller algorithm and settings

Problems with startup

Sometimes in one-to-one applications, the valve does not open

sufficiently on startup, and troublesome low pressure trips may

occur. 

The force opening of valve function has been implemented in

the EIM 336 controller. After startup, this function will provide a

constant, set minimum opening degree during a set time period,

regardless of the superheat value. The setting parameters are

called Start OD% (n17) and StartUp time (n15).

Low Pressure Issue due to compressor cut in and cut out

One of the features of TEX valves is the external pressure 

equalization making a direct and fast responding pressure 

connection between the compressor suction line and underside of 

the diaphragm in the valve. This enables the valve to open-/ close 

momentarily with compressor capacity cut in and out . 

The same function has been implemented into EIM 336, which is 

controlled by the parameter  n20,  KpTo. In this function.  kp factor 

related directly to the suction pressure (To) with direct effect on the 

requested signal to the ETS6 valve .

The default value of KpTo is set to automatic (i.e  -1). If the 

automatic tuning is not fulfilling the desired order,  Increasing the 

n20 setting to the fixed value  will contribute to an improvement. 

Too high n20 will produce high fluctuation in superheat regulation.

Service (continued)

Group

PNU

Parameter

Symbolic name

Min.

Max.

Default Units

e2

W

*10

Description

Control

status

3099

-

Control  State

0

5

0

Current state of internal control state

machine.

3100

-

Ctrl Status 

0

20000

0

Bit mappped status register. See also

appendix 2.

Содержание EIM 336

Страница 1: ...ess noise The EIM 336 is the superheat controller that can be used to control the opening degree of a valve based on the superheat of the evaporator This is applicable in applications such as air cond...

Страница 2: ...allation sensors 17 Warnings 17 Acronyms and abbreviations used in this manual LOC Loss of charge indication SH Superheat MOP Maximum operating pressure MSS Minimum stable superheat Te Saturated sucti...

Страница 3: ...densed Superheat close When the superheat is below a set minimum value the valve will close faster in order to protect the compressor from the risk of getting liquid in the suction line Manual control...

Страница 4: ...S2 PT1000 S4 PT1000 or digital input from external contact EEV driver Max current 150 mA EEV Uni or bipolar coil Data communication RS485 Modbus RTU Environment Storage 34 C to 71 C 30 F to 160 F Ope...

Страница 5: ...odbus address stored in PNU no 40041 default 165 Jumper not mounted Outdoor unit condenser Modbus address stored in PNU no 40042 default 164 Com KM5 1 Drain D 2 RS485 TxD RxD 3 RS485 TxD RxD 4 Not Use...

Страница 6: ...trol mode does not depend on the r12 Main Switch and will set the opening degree regardless of its setting Setting o18 Manual ctrl to 0 again the controller will assume normal control and will open or...

Страница 7: ...secondary address is 164 Note Changes to these parameters will become active immediately This means that a modbus tool or controller that changes these settings will loose connection to the EIM 336 an...

Страница 8: ...e controller is powered the valve will first be closed fully so that the controller starts from a known opening degree 0 In order to make sure that it is fully closed the valve will be closed 100 plus...

Страница 9: ...sensor value will be used 5 Configuring the superheat control The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat sett...

Страница 10: ...um operation pressure If Pe goes above this value the controller will control on Pe and not on superheat Kp MOP 3113 Kp proportional gain while in MOP control mode Tn MOP 3114 Tn integration time whil...

Страница 11: ...05 Timer to trigger LOC alarm LOC Alarm 50006 Loss of charge alarm flag 0 no alarm 1 LOC alarm LOC SH Trig 50007 SH error trigger level for LOC alarm LOC Tmr 3102 Loss Of Charge time readout displays...

Страница 12: ...t regulation response Very low value give the risk of unstable regulation For Danfoss only 3105 SHL SH Low 3 20 6 K Superheat low setting for non linear control 3106 SHH SH High 8 40 16 K Superheat hi...

Страница 13: ...ext S2 temp 200 200 0 C External S2 This value can be used instead of a sensor This register must be written at least every 5 seconds otherwise the sensor value will be used 2646 TS4 ext S4 Air temp 2...

Страница 14: ...ain Switch 64309 Manual OD as steps 0 1 0 Enable the manual OD in o45 to be entered as halfsteps Readouts are still in percent Service Alarm 2046 RAL Reset alarm 0 1 0 1 clear alarm 20001 EKC Error 0...

Страница 15: ...troller will go to either the low or high boundary de pending on the error The highest value will be shown if the signal is above the maximum value The lowest value will be shown if the signal is belo...

Страница 16: ...it 3 Bit 2 Bit 1 Bit 0 Unused MOP Active Close Timer active Sensor Errors Control state Variables parameters CTRLstatus bit 0 3 Controlstate 0 closed 1 Error 2 Inject 3 De humidify 4 Force OD 5 Defros...

Страница 17: ...ght after the evaporator If the measured value is 1 2 K lower than the actual value of Pe right after the evaporator it may cause the evaporator to flood This is the case when the pressure transmitter...

Отзывы: