Service parameter(s) 52(II)-55
32n
52 Compensation of heat loss in circulation circuit
Circuit
Setting range
Factory setting
II
ON / OFF
ON
In primarily connected storage charging systems (system types 2,
2a, 6 and 6a, section 10), you can choose to compensate for the
heat loss of the circulation circuit.
ON:
No compensation (system types 2 and 6):
The circulation circuit (P3) is kept warm by
the storage tank.
The motorized control valve (M2) is closed.
OFF:
Compensation
(system types 2a and 6a)
:
The circulation circuit (P3) is kept warm by
the heat exchanger.
The motorized control valve (M2) is active
to keep the charging temperature at S4
constant.
55 Activation / deactivation of DHW circulation pump
during DHW charging
Circuit
Setting range
Factory setting
II
ON / OFF
OFF
At DHW charging, the pump can be deactivated independently of
the schedule.
ON:
The pump always operates according to
schedule.
OFF:
The pump is deactivated at DHW charging,
independently of the schedule.