Service parameters (10-199)
31c
Circuit II (DHW)
Lines Setting ranges
Factory settings Your settings
24
Gear motor / thermo actuator
ON / OFF
ON
30
Return temperature limitation
10 ... 110 °C
60 °C
°C
35
Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9
-2.0
36
Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9
0.0
37
Time constant for return temperature
limitation
OFF / 1 ... 50
25
40
DHW pump post-run
0 ... 9 min.
0 min.
min.
41
DHW charging pump post-run (P3)
0 ... 9 min.
1 min.
min.
44
Max. DHW charging time
OFF / 1 ... 100 min.
OFF
min.
45
DHW charging deactivation time
0 ... 250 min.
0 min.
min.
52
Compensation of heat loss in
circulation circuit
ON / OFF
ON
55
Activation / deactivation of DHW
circulation during DHW charging
ON / OFF
OFF
78
Desired temperature for anti-bacteria
function
OFF / 1 ... 100 °C
OFF
°C
80
Anti-bacteria function period
5 ... 250 min.
120 min.
min.
83
Internal relationship between circuits
I and II
0 ... 4
0
84
Pump P2 in DHW circuit, primary side
ON / OFF
OFF
85
Pump P2 in DHW circuit, primary side
ON / OFF
OFF
140
Function of temperature sensor S5
ON / OFF
OFF
141
Override input selection
OFF / 1 ... 6
OFF
147
Acceptable temperature deviation
below desired flow temperature
(ΔT1
ALARM
)
OFF / 1 ... 30 K
OFF
K
148
Acceptable temperature deviation
above the desired flow temperature
(ΔT2
ALARM
)
1 ... 30 K
5 K
K
149
Time interval Δt
ALARM
before
activation of alarm function
1 ... 99 min.
10 min.
min.
174
Motor protection
OFF / 10 ... 59 min.
OFF
min.