Service parameters (10-199)
Circuit I (Heating)
Lines Setting ranges
Factory settings Your settings
147
Acceptable temperature deviation
below desired flow temperature
(ΔT1
ALARM
)
OFF / 1 ... 30 K
OFF
K
148
Acceptable temperature deviation
above the desired flow temperature
(ΔT2
ALARM
)
1 ... 30 K
5 K
K
149
Time interval Δt
ALARM
before
activation of alarm function
1 ... 99 min.
10 min.
min.
174
Motor protection
OFF / 10 ... 59 min.
OFF
min.
196
Service pin LON
ON / OFF
OFF
197
LON reset
ON / OFF
ON
198
Daylight saving time changeover
ON / OFF
ON
199
Slave address
0 ... 9, 15
15