CB
CC
CCH
DGT
F1
HP
KM
LPS
M
MPM
S
SS
SSH
Figure 58: Compressor model DSF485 - 530
CC
SS
LPS
KM
F1
F1
HP
L1 L3 L2
KM
DGT
MPM
CB
UC
M
S
CCH
T2
T1
T3
CC-000020
Thermal magnetic motor circuit breaker
Control circuit
Crankcase heater
Discharge gas thermistor (embedded in com-
pressor)
Fuses
High pressure safety switch
Compressor contactor
Safety pressure switch
Compressor motor
Motor Protection Module
Thermistor chain (motor and discharge tem-
perature)
Seprate supply
Surface sump heater
Soft starts
Soft starters are designed to reduce the starting current of 3-phase AC motors. Soft starter must be set so
compressor start-up time is always less than 0.5 seconds to ensure proper lubrication of compressor parts.
Ramp-down must be set to minimum to ensure proper discharge valve closing.
Make sure that the soft starter selected is compatible with R32 refrigerant.
© Danfoss | Climate Solutions | 2023.06
AB309735209512en-000603 | 51
Scroll compressors, DSF090 to DSF530 | Application