Mechanical vibrations
A compressor generates some vibrations that propagate into the surrounding parts and structure. The vibration
level of a DSF compressor alone does not exceed 120 µm peak to peak for DSF090 to DSF200, and 154um peak to
peak for DSF270 to DSF530.. However, when system structure natural frequencies are close to running frequency,
vibrations are amplified due to resonance phenomenon.
A high vibration level is damageable for piping reliability and generates high sound levels.
© Danfoss | Climate Solutions | 2023.06
AB309735209512en-000603 | 15
Scroll compressors, DSF090 to DSF530 | Sound and vibration data