Table 26.

Problem – The heat pump consumes too much energy

Cause

Troubleshooting

Remedy

1. Blocked strainer in the heating sys-

tem.

Check that the strainer is not blocked.

Clean the strainer if necessary.

2. The compressor cannot run due to

an alarm.

Check the alarm that is indicated in the dis-

play.

Rectify the problem and rest the alarm.

See section Alarm, Page 15.

3. Incorrect flow over hot side of the

heat pump.

Measurement check what the difference

between the supply and return line is using

a thermometer (∆t). The difference should

be about 8°C (can vary depending on

refrigerant). A lower ∆t results in reduced

efficiency in the heat pump.

Adjust the system to obtain the correct

∆t.

4. The heat pump’s control computer

is not set/adjusted to the customer’s

requirements/wishes.

Check the ROOM and CURVE and MIN set-

tings.

Adjust incorrect values in the heat

pump’s control computer. ROOM =

Desired indoor temperature CURVE =

Should be set so that the desired indoor

temperature (ROOM) is maintained

regardless of the outdoor temperature.

MIN = Lowest set-point value on the

supply line regardless of the outdoor

temperature.

5. The interval for peak heat opera-

tion has changed to a lower value

than the factory set value. This results

in the heat pump going into peak

heat operation more often than cal-

culated.

Check the specified interval for peak heat

operation in the control computer.

If there is a shorter interval between the

peak heat productions, this explains why

the unit consumes more current than

calculated, but this does not mean for

sure that it should be increased, there

might be a reason why the interval has

been changed.

6. The heat pump has stopped on

HIGH RETURN.

Check what the MAX RETURN value is

set at in the heat pump’s control com-

puter. It must be adjusted to the unit’s

maximum supply temperature and the

system’s delta temperature so that it

does not cut at too high a return tem-

perature when the highest supply

temperature is transmitted.

Check what the return line sensor

shows. Is it a plausible/actual value? If

not, take a resistance reading from the

sensors and check against the ohm

table in Measurement points, Page 11.

If the MAX RETURN value is not adjusted

for the system according to the trouble-

shooting window, adjust it. If the sensor

is defective, replace it.

7. The compressor runs backwards.

The incoming phases have the incor-

rect sequence (only applies to 3-

phase heat pumps). If the compressor

runs backwards, it will not cope with

compressing the refrigerant and

therefore does not produce the cor-

rect power, which leads to the control

computer requesting auxiliary heat-

ing.

If the text ERR PHASE SEQ. appears in

the display when the heat pump is

powered, (only appears in the first 10

minutes) this means that the phases

have the incorrect sequence.

When the compressor is running,

check the pressure pipe temperature

by feeling the pressure pipe. If the

phases are correctly sequenced it

should be hot (not just warm) even a

distance from the compressor.

When the compressor runs with the

phases incorrectly sequenced a

strange noise may be heard (loud, rat-

tling) when the compressor runs back-

wards.

If the phases are in the incorrect order,

switch two incoming phases at the main

terminal block and recheck according to

the troubleshooting window.

 

 

Service instructions VMGFJ102 – 31

Содержание DHP-AQ Mini

Страница 1: ...Service instructions DHP AQ VMGFJ102...

Страница 2: ...the applicable warranty is not binding Danfoss A S retains the right to make changes to components and specifications without prior notice 2011 Copyright Danfoss A S The Swedish language is used for t...

Страница 3: ...3 1 4 Terminology 5 2 Important information 6 2 1 General safety precautions 6 2 2 Refrigerant 6 2 3 Electrical connection 7 2 4 Important information 7 2 5 Commissioning 8 3 Troubleshooting 9 3 1 Ala...

Страница 4: ......

Страница 5: ...uctions and Electrical instructions are available for download here www documentation heatpump danfoss com 1 2 Symbols in documents The instructions contain different warning symbols which together wi...

Страница 6: ...rushing injury Electrical components Component normal Component accessory 3 Outdoor unit 362 Shunt valve 50 Outdoor sensor 363 Exchange valve hot water 54 Hot water sensor 365 Supply line sensor 55 Se...

Страница 7: ...ter Supply line The heating system s supply line with flow direction from the heat pump to radiators under floor heating or water heater Return line The heating system s return line with flow directio...

Страница 8: ...efrigerant has low toxicity However although the toxicity of the refrig erant is low it can cause injury or be highly dangerous in abnormal circumstances or where deliberately abused Warning Risk of p...

Страница 9: ...l and national regulations Warning The electrical installation must be carried out using permanently routed cables It must be possible to isolate the power supply using a multi pole circuit breaker wi...

Страница 10: ...he circulation pump can be damaged Caution If the installation is only to operate using an auxiliary heater during the installation ensure that the heating system is filled and bled and that the compr...

Страница 11: ...sensor SYSTEM SUPPLY LINE SENSOR Sensor fault alternatively cable fault System supply line sensor RETURN LINE SENSOR Sensor fault alternatively cable fault Return line sensor HIGH RETURN LINE TEMP Re...

Страница 12: ...m the heat pump will if possible supply heating to the house primarily with the compressor secondarily with the auxiliary heater Hot water will stop to indicate that something noteworthy has occurred...

Страница 13: ...e 18 Solenoid 9 Discharge pipe 19 Non return valve 10 Air heat exchanger 3 2 2 Indoor unit 1 DHP AQ Mini 1 2 4 3 5 DHP AQ Maxi 1 2 3 4 DHP AQ Midi Position Description 1 Control module transparent in...

Страница 14: ...66 3 5 52 4 10 41 8 15 33 5 20 27 1 25 22 0 30 18 0 35 14 8 40 12 2 45 10 1 50 8 5 55 7 1 60 6 0 65 5 0 70 4 2 75 3 7 80 3 1 85 2 7 3 3 1 Measurement checking sensors during fault tracing 1 Disconnect...

Страница 15: ...REFR 1 SENSOR 4 REFR 2 SENSOR 5 DEFROST SENSOR located to rear beside air intake 6 OUTDOOR SENSOR positioned on wall to north 7 SUPPLY LINE SENSOR 8 HOT WATER TOP 9 HOT WATER SENSOR RETURN LINE SENSO...

Страница 16: ...operation the heat pump operates with superheating of 5 5 C 7 C the expansion valve s degree of opening will vary depending on operating situation At outdoor temperatures of 5 C or lower the opening...

Страница 17: ...Using manometer apparatus and ther mometer check that the unit s overheat ing is correct for the specific refrigerant If the evaporator is thought to be blocked by oil for example try blowing nitroge...

Страница 18: ...h always open If the high pressure switch opens too soon or is always open replace it 9 External system shunt that closes on time setting Check for shunts or valves in the system which are timer contr...

Страница 19: ...nd ing on type of refrigerant to add the cor rect amount of refrigerant If there appears to be a leak in the refrig erant circuit carry out leak tracing and any necessary corrective action Table 8 Pro...

Страница 20: ...t take a reading from the sensor including cable and check against the ohm table in Symbols on decals If the read off value does not corre spond with the table only measure the sensor and check the oh...

Страница 21: ...sor is defective replace it 5 No or insufficient circulation in the heating system Check That the circulation pump spins That the shut off valves are open That the strainer is not blocked That there i...

Страница 22: ...maximum temperature of the discharge pipe 140 C 4 Lack of refrigerant not enough refrigerant in the system Using manometer apparatus and ther mometer check that the unit s overheat ing is correct for...

Страница 23: ...ing to the instructions Install flexible hoses according to the instructions 3 Installing suspending pipes Check if vibrations are transmitted via one of the pipe mountings in the installation Remove...

Страница 24: ...and output phases for the soft starter as well as the control signals from the heat pump card see wiring diagram If the soft starter is defective replace it 2 The compressor s safety valve opens The...

Страница 25: ...it a plausible actual value Measure the resistance of the sensor check against the ohm table in Measure ment points Page 11 If the sensor is defective replace it 6 Large drain flow 12 l min Check how...

Страница 26: ...duce the hot water When done read off the temperature on the top sensor and on the start sensor The top sensor should show a tempera ture of around 50 55 C and the start sensor around 45 48 C If after...

Страница 27: ...y HYSTERE SIS before INTEGRAL reaches 0 there may be heating deficit in the house Check if heat production stops because the hysteresis value is set too low See the installation instructions for facto...

Страница 28: ...water demand If the heat pump has been dimen sioned for a certain demand and this demand is increased the heat pump might not be able to main tain the desired room temperature If hot water consumption...

Страница 29: ...es Check the ROOM and CURVE MIN MAX CURVE5 CURVE0 CURVE 5 and HEAT STOP settings Adjust incorrect values in the heat pump s control computer ROOM Desired indoor temperature CURVE Should be set so that...

Страница 30: ...ted leak and look for bub bles Also check for oil as this can come out from the refrigerant circuit Table 24 Problem Runs on electric heating element Cause Troubleshooting Remedy 1 Operating mode AUX...

Страница 31: ...sor runs back wards If the phases are in the incorrect order switch two incoming phases at the main terminal block and recheck according to the troubleshooting window 7 Changed conditions Have you inc...

Страница 32: ...n sor is defective replace it If the delivery line temperature gets so hot that the compressor stops start by leak tracing the unit Rectify the leak if a leak is found If no leak is found try draining...

Страница 33: ...d be increased there might be a reason why the interval has been changed 6 The heat pump has stopped on HIGH RETURN Check what the MAX RETURN value is set at in the heat pump s control com puter It mu...

Страница 34: ...delivery line temperature is If the prob lem persists replace the compressor 9 Expansion valve defective or incor rectly set Using manometer apparatus and ther mometer check what the overheating read...

Страница 35: ...racing and any necessary corrective action If leak tracer is not available brush soap water on the suspected leak and look for bub bles Also check for oil as this can come out from the refrigerant cir...

Страница 36: ...instructions and that it is correctly calibrated Calibrate if necessary Table 32 Problem Build up of ice under and around the outdoor unit Cause Troubleshooting Remedy Insufficient drainage Does a lo...

Страница 37: ...VMGFJ102...

Отзывы: