Cause
Troubleshooting
Remedy
10. Closed or partially closed thermo-
stats/valves in the heating system.
Check that the thermostats/valves in the
heating system are open.
Open closed thermostats/valves.
11. The total output of the heat pump
and auxiliary heater is too low in relation
to the building’s power demand.
What is the building’s power demand?
What is the output of the heat pump?
What is the output of the auxiliary
heater, what is it set to?
Ensure that available power is at least as
great as the building’s power demand.
12. Under dimensioned heating system. Check existing heating system.
What output is it dimensioned for to
produce at what supply temperature?
What output is required to keep the
room warm?
If the heating system is dimensioned for
greater supply temperatures than the
heat pump can provide, it must be
adjusted by increasing the heat emitting
surface for example.
If the room requires a higher output
than the heating system can provide,
extend the heating system.
13. Changed conditions
Have you increased your heating and/or
hot water demand?
•
If the heat pump has been dimen-
sioned for a certain demand and
this demand is increased, the heat
pump might not be able to main-
tain the desired room temperature.
•
If hot water consumption increases,
a larger proportion of time is used
to produce hot water, which means
less time for heat production (only
applies to system solution 1).
If the heat pump cannot cope with the
demand, replace it with one with a
higher output or supplement it with a
higher output auxiliary heater.
Table 21.
Problem – Too hot
Cause
Troubleshooting
Remedy
1. The heat pump’s control computer is
not set/adjusted to the customer’s
requirements/wishes.
Check the ROOM and CURVE and MIN set-
tings.
Adjust incorrect values in the heat
pump’s control computer.
ROOM = Desired indoor temperature.
CURVE = Should be set so that the
desired indoor temperature (ROOM) is
maintained regardless of the outdoor
temperature.
MIN = Lowest set-point value on the
supply line regardless of the outdoor
temperature.
2. Sensor fault, OUTDOOR/ROOM/SUP-
PLY LINE.
Check what the relevant sensor shows. Is
it a plausible/actual value?
Measure the resistance of the sensor,
check against the ohm table in Measure-
ment points, Page 11.
If the sensor is defective, replace it.
26 – Service instructions VMGFJ102
Содержание DHP-AQ Mini
Страница 1: ...Service instructions DHP AQ VMGFJ102...
Страница 4: ......
Страница 37: ...VMGFJ102...