Menu selection
Meaning
Factory setting
ALARM BRINE
Gives an alarm when the outgoing brine temperature falls below the set value.
(range:
, -14°C /
10°C)
PRESS. PIPE
Sensor on the compressor’s hot gas line. The value within brackets indicates maximum
permitted temperature. If this value is exceeded, the compressor will stop and start again
as soon as the temperature has dropped. No alarm shown in the display, however, a
square is shown in the left, lower corner of the display.
140°C
OUTDOOR STOP Displayed only if AIR is selected. Lowest outdoor temperature when the outdoor sensor
stops the compressor and heating or hot water are instead produced by the auxiliary
heater.
-20°C(range: -20°C /
-1°C)
SHUNT TIME
Time in seconds. Indicates how often the shunt is to adjust its opening.
60S(range: 10S / 99S)
SHUNT COOL-
ING
The cooling shunt works towards the set temperature.
18°C(range: 0°C / 30°C)
COOLING TEMP Set point value of the supply temperature at cooling mode.
18°C(range: 5°C / 30°C)
9.3
Sub-menu AUX. HEATER
Menu selection
Meaning
Factory setting
MAX STEP
Maximum number of permitted steps for auxiliary heating.
= no auxiliary heating per-
mitted (Means that only AUTO or HEAT PUMP can be selected.)
2
(range:
, 1, 2, 3, 4,
5, +4, +5)
INTEGRAL A2
Two conditions must be fulfilled in order to start the auxiliary heater: the integral’s value
to start must be less than integral A2, and the supply temperature must be 2°C lower than
the calculated temperature. See
Service Instructions
for more information.
-600(range: -50 /
-990)
HYSTERESIS
If the difference between the actual supply temperature and the calculated supply tem-
perature is too great (see
Service Instructions
for more information), either the integral val-
ue is set to start value A2 (starts the auxiliary heater) or to 0 (stops the auxiliary heater ).
20°C(range: 5°C /
30°C)
MAX CURRENT
Refers to main fuse in the unit, in amperes
20A(range: 16A / 35A)
HOT WATER STOP Stop temperature for hot water during AUX. HEATER. The value is read off by the hot wa-
ter sensor.
60°C(range: 50°C /
65°C)
DELAY AFTER EVU Time in minutes. Indicates how many minutes after EVU are to pass before the auxiliary
heater may be activated.
30M(range: 0M /
120M)
EXT.AUX.HEATER See table below for more information
EXT.AUX.HEATER
Menu selection
Meaning
Factory setting
EXT.AUX.HEATER
Indicates whether an external auxiliary heater is installed in the system.
/ ON
INTEGRAL A3
Indicates the value of the integral when external auxiliary heater is connected.
-300(range: -990 / IN-
TEGRAL A1 - 10)
TURN OFF DELAY
Indicates how long the external auxiliary heater must continue to be active after its de-
mand is no longer needed.
0M(range: 0M / 180M)
REV.V. HOT WATER Indicates whether the exchange valve for hot water is located before or after the exter-
nal auxiliary heater. (Determines whether the external auxiliary heater may produce hot
water.)
INT / EXT
TOPH. AUX
Indicates whether the external auxiliary heater can be used for anti-legionella. The ex-
change valve must be positioned after the external auxiliary heater.
/ ON
Installation Guide
Domestic heat pumps
VMGFQ102
Danfoss Heating Solutions
44
Содержание DHP-A
Страница 42: ...Menu selection POLSKI E TINA Installation Guide Domestic heat pumps VMGFQ102 Danfoss Heating Solutions 42...
Страница 61: ...Installation Guide Domestic heat pumps Danfoss Heating Solutions VMGFQ102 61...
Страница 62: ...Installation Guide Domestic heat pumps VMGFQ102 Danfoss Heating Solutions 62...
Страница 63: ...Installation Guide Domestic heat pumps Danfoss Heating Solutions VMGFQ102 63...