4
|
Compressor assembly
4.1 Setting up
4.2 Maximum permissible inclination
A
max. 30°,
max. 2 minutes
a
max. 15°,
continuous
operation
Fig. 4
Transport and suspension unit on both eyebolts (Fig. 4).
A
A
a
a
A
A
a
a
Fig. 5
INFO
New compressors are factory-filled with inert gas. Leave this ser
-
vice charge in the compressor for as long as possible and prevent
the ingress of air.
Check the compressor for transport damage before starting any
work.
ATTENTION
Poor lubrication can damage the compressor. Respect the stated
values.
WARNING
Move compressors only with hoists that have adequate load-bear
-
ing capacity.
Storage at (-40°C) - (+100°C), maximum permissible relative humidity 10% - 95%, no
condensation.
Fittings (e.g. pipe holders, additional units etc.) on the compressor are permissible only
following consultation with Bock.
Setup on an even surface or frame with sufficient load-bearing capacity. Use all 4 fastening
points.
Correct setup of the compressor and mounting of the belt drive are decisive for running comfort,
operating safety and the service life of the compressor.