© Danfoss | DCS (CC) | 2016.11  | 7

FRCC.PI.050.A1.02

suction service valve may cause serious damage 

to the compressor and/or compromise safety 

device operation, thereby resulting in potential 

injury to personnel.

• Check that all safety devices are operational 

and properly set (safety pressure switch set 

point, mechanical relief valve if necessary, etc.). 

Make sure that these devices comply with both 

generally - and locally - applicable regulations 

and standards (e.g. EN 378-2:2012).

• When using high-pressure switches or relief 

valves, the setting must not exceed maximum 

service pressure of any system component. Re-

fer to the Application Guidelines for relevant 

condensing unit pressure safety limits.

• A low-pressure switch is recommended to 

prevent operation under vacuum. Use a mini-

mum setting of 1.2 bar (absolute).

• Verify that all electrical connections are proper-

ly fastened and in compliance with local safety 

regulations.

• A compressor crankcase heater is factory ins-

talled, ensure that it has been energized for a 

minimum of 12 hours before initial start-up and/

or during prolonged shutdown periods.

10 - Start up

 Never start the compressor in the absence of 

a refrigerant charge. 

• Do not bypass the LP or any other safety swit-

ches during start-up

• Check current draw and voltage levels.

• Monitor the oil sight glass to ensure proper oil 

return to the compressor.After 2 to 4 hours of 

operations under established conditions, check 

the oil level and add oil if necessary (refer to TI 

bulletin 3-025).

If oil return continues to perform poorly, further 

investigation of the piping design is required. 

• In all cases, the application limits of the compressor 

must be respected; moreover, high superheat values 

lead to high discharge temperatures and decrease 

compressor capacity. The maximum discharge tem-

perature is 130°C: operating ata higher temperature 

may result in refrigerant decomposition.

• Under steady-state operating conditions, check 

refrigerant piping or capillary tubes for abnor-

mal vibrations (refrigeration line movement in 

excess of 1.5 mm necessitates corrective actions, 

pipe brackets, etc.).

• Ensure that refrigerant flow through the liquid 

line sight glass (when mounted) is adequate and 

that operating temperatures correspond with 

system specifications.

• When needed, refrigerant may be added in the 

liquid phase, carefully throttling the refrigerant 

on the low-pressure side and as far as possible 

from the compressor.The compressor must be 

operating during this process.

 Do not overcharge the system.

11 - Troubleshooting

• 

Compressor failure to start:

 verify that the 

compressor is hooked up to the power supply; 

check the power lead connections and all sui-

table capacitors on single-phase models. If these 

verifications reveal no abnormality, control the 

motor windings with an ohmmeter. 

Note: when the internal motor protector has 

tripped out, it may take up to several hours to 

reset and restart the compressor.

• Compressor failure to build up pressure:

 

check to make sure that all bypass valves in the 

system have not been opened. Also check that 

all solenoid valves are in their proper position. 

If the internal pressure relief valve is open, the 

compressor sump will be warm and the com-

pressor will trip out on the motor protector. If 

this happens, it may take up to 2 or 3 hours to 

reset and automatically restart the compressor.

• Abnormal running noise on the system: 

  - Ensure the absence of any liquid flood-back 

to the compressor by means of measuring the 

return gas superheat and compressor sump 

temperature. The sump should be at least 10K 

above the saturated suction temperature under 

steady-state operating conditions.

  - Check that the fans are running free and wit-

hout vibration.

• The high-pressure switch trips out:

 check 

condenser operations (condenser cleanliness, 

fan operations, etc.). If above check out OK, the 

problem may be due to either refrigerant over-

charging or the presence of a non-condensable 

(e.g. air, moisture) in the circuit. 

• The low-pressure switch trips out:

 check eva-

porator operations (coil cleanliness, fan opera-

tions, water flow, water filter, etc.), liquid refrige-

rant flow and pressure drops (solenoid valve, filter 

dryer, expansion valve, etc.), refrigerant charge.

• Low refrigerant charge:

 the correct refrige-

rant charge is given by the liquid sight glass 

indication, the condenser delta T in relation to 

the refrigerant pressure tables (pressure-tempe-

rature), the superheat and the sub-cooling, etc. 

(if additional charge is deemed necessary, refer 

to the 

«Filling the system»

 section). 

• Compressor maximum short cycling: 

there 

must be a minimum delay of five minutes 

between two compressor starts. DCC recom-

mends the compressor should run at least two 

minutes after each start, and between each stop 

and start must be three minutes standstill. Only 

during pump down cycle, the compressor may 

run much shorter until the pumpdown pressure 

has been reached or when safety devices will 

prohibit compressor further operation.

12 - Maintenance

• Proper operations and maintenance of the 

condensing units serve to prevent against sys-

tem-related problems.The following preventive 

maintenance checks, to be performed at regular 

intervals, are highly recommended:

  - Control operating conditions (evaporating 

temperature, condensing temperature, com-

pressor discharge temperature, temperature 

difference on heat exchangers, superheat, 

sub-cooling). These conditions must always re-

main within compressor operation limits.

  - Verify that safety devices are operational and 

properly set.

  - Check the compressor oil level and quality; 

this step may include an acid test, humidity 

check, spectrometer analysis, etc. whenever the 

oil becomes discolored.

  - Ensure that the circuit is leak tight.

  - Verify the proper operation of heat exchan-

gers and, if necessary, clean them.

  - Check that the fans are running free (without 

vibration) and current draw on the compressor 

motor as well as proper voltage balance between 

phases.

  - Change the filter dryer when necessary.

  - Check that all electrical connections are still 

adequately fastened. 

  - Make sure the condensing unit is clean and 

in good working order; verify the absence of rust 

or corrosion on components under pressure and 

electrical connections. 

  - Make sure the refrigerant charge is suitable 

for both winter and summer operation.

• Ensure that periodic in-service inspections re-

quired by local regulations are performed. 

13 - Replacement

 Precaution must be taken when disconnec-

ting any components, cutting or drilling holes in 

the tubing to ensure that no refrigerant under 

pressure is present in the system.

 The refrigerant shall not be discharged direc-

tly into the atmosphere; rather, it must be remo-

ved using approved reclamation techniques and 

equipment and then safely stored, inaccordance 

with applicable legislation.

 The presence of refrigerant vapor can displace 

air and lead to suffocation. Proper ventilation is 

mandatory at all times when servicing the equip-

ment.

 A condensing unit component change must be 

carried out in compliance with local regulations.

• Make sure that the main power supply has 

been switched off.

• Before replacement, it is necessary to deter-

mine the cause of failure and implement reme-

dial action. If such analysis and repair are not 

performed, repetitive failure may occur. Note 

that an oil acidity test always proves helpful in-

diagnosis when undertaking compressor repla-

cement.

• Check that the replacement component has 

the same electrical and refrigeration perfor-

mance characteristics as the original one.

• Whenever piping needs to be modified, please 

refer to the 

«Safety measures prior to assem-

bly»

 section.

• For further details on replacement steps,refer 

to the previous sections of this manual.

Note:

 

In the event of compressor motor failure, 

flush and clean the entire circuit before repla-

cing the compressor in order to remove acids and 

contaminants. Systematically install a new filter 

dryer on the liquid line. Prior to this step (if ne-

cessary), run the system for at least 2 hours with 

anti-acid cartridges (in such instances, the instal-

lation of a suction filter might also be required). Af-

ter an operating period of approximately 2 weeks, 

Содержание Bluestar Series

Страница 1: ...Instructions Condensing Units Bluestar Optyma Danfoss DCS CC 2016 11 FRCC PI 050 A1 ML 1 English English p 2 Français French p 13 Deutsch German p 16 Polski Polish p 23 ...

Страница 2: ...Z51 MTZ57 MTZ65 755 700 656 MCZC121 MCZC136 MCZC171 MTZ73 MTZ81 MTZ100 900 900 759 MGZC215 MGZC242 MGZC271 MTZ125 MTZ144 MTZ160 1350 820 759 LBP application 50 Hz Compressor W D H LCQC048 NTZ048 500 620 451 LCQC068 LCQC096 LCQC108 NTZ068 NTZ096 NTZ108 630 650 605 LCQC136 NTZ136 755 700 656 LCQC215 LCQC271 NTZ215 NTZ271 900 900 759 LGQC048 NTZ048 700 500 392 LGQC068 LGQC096 LGQC108 NTZ068 NTZ096 NT...

Страница 3: ...Instructions Danfoss DCS CC 2016 11 3 FRCC PI 050 A1 02 1 x coil height Min clearance 2 x unit length Fig 2 Fig 5 Fig 3 Fig 4 ...

Страница 4: ...Instructions 4 Danfoss DCS CC 2016 11 FRCC PI 050 A1 02 ...

Страница 5: ...s never stored in an ambient temperature of below 35 C 31 F or above 50 C 122 F Ensure that the condensing unit and its packa ging are not exposed to rain and or a corrosive flammable atmosphere 3 Safety measures prior to assembly All installation and servicing is to be performed by qualified personnel in compliance with all pertinent practices and safety procedures The condensing unit must be loc...

Страница 6: ... system volume Never use the compressor as a vacuum pump It is recommended to use large diameter connec tion lines and to connect these lines to the shut off valves rather than to the Schrader connec tion This recommendation allows avoiding excessive pressure losses Moisture level At the time of commissioning system moisture content may be as high as 100 ppm During ope ration the liquid line filte...

Страница 7: ...The low pressure switch trips out check eva porator operations coil cleanliness fan opera tions water flow water filter etc liquid refrige rant flow and pressure drops solenoid valve filter dryer expansion valve etc refrigerant charge Low refrigerant charge the correct refrige rant charge is given by the liquid sight glass indication the condenser delta T in relation to the refrigerant pressure ta...

Страница 8: ...reover a compressor in operation can generate very cold surface temperatures as low as 45 C 49 F there by exposing personnel to the risk of free zing burns Pressure inside the compressor and refrige rant circuit can reach dangerously high levels e g abnormal operation fire leading to personnel injury if suddenly released therefore never drill weld or cut the compressor shell and adjacent tubing re...

Страница 9: ... MTZ125 MTZ144 MTZ160 1350 820 759 Application LBP 50 Hz Compres seur W D H LCQC048 NTZ048 500 620 451 LCQC068 LCQC096 LCQC108 NTZ068 NTZ096 NTZ108 630 650 605 LCQC136 NTZ136 755 700 656 LCQC215 LCQC271 NTZ215 NTZ271 900 900 759 LGQC048 NTZ048 700 500 392 LGQC068 LGQC096 LGQC108 NTZ068 NTZ096 NTZ108 800 600 442 LGQC136 NTZ136 1000 700 555 Temperature évaporée C Temperature ambiante C 15 5 5 15 20 ...

Страница 10: ...2016 11 FRCC PI 050 A1 04 1 x hauteur de batterie Espace minimum 2 x longueur 8 à 12 m s à capacité minimun 8 à 12 m s à capacité maximun Condensateur du ventilateur Danfoss Condensateur du ventilateur Danfoss Fig 2 Fig 5 Fig 3 Fig 4 ...

Страница 11: ...int de declenchement Di erentiel Di erentiel fixe Point de renclenchement Test manuel Point de declenchement Couple de serrage 20 Nm Fil de cuivre uniquement Point de renclenchement Reset manuel Reglage d usine Reset manuel Reset convertible Reset convertible Di erentiel fixe Point de renclenchement Point de declenchement BP man BP auto BP auto BP man HP man HP man HP auto HP auto BP auto BP auto HP...

Страница 12: ... des substances corrosives ou inflammables 3 Mesures de sécurité avant montage Toute opération de montage et d entretien doit être effectuée par un personnel qualifié confor mément à l ensemble des pratiques courantes et aux mesures de sécurité de la profession Le groupe de condensation doit être installé dans un endroit suffisamment ventilé le débit d air au condenseur ne doit subir aucune restri...

Страница 13: ... mise en service le taux d hu midité du circuit peut atteindre un niveau aussi élevé que 100 ppm Pendant le fonctionnement le filtre déshydrateur liquide doit réduire ce ni veau à 20 ppm Notes supplémentaires Pour améliorer la déshydratation du circuit la température ne doit pas être inférieure à 10 C Une procédure appropriée de tirage au vide est encore plus importante avec les HFC et les lubrifi...

Страница 14: ...gaz d aspiration et la température de refoulement du compres seur La température du carter d huile doit se situer au moins 10K au dessus de la température d aspiration saturée en régime de fonctionne ment permanent Vérifiez que les ventilateurs tournent librement et sans vibration Le pressostat de sécurité haute pression se déclenche contrôlez le condenseur propreté fonctionnement du ventilateur d...

Страница 15: ...r le groupe et ses tuyauteries D autre part lorsque le compres seur est en fonctionnement la température de ces surfaces peut également être extrêmement froide jusqu à 45 C 49 F exposant ainsi le personnel à un risque de brûlures par le froid La pression interne du compresseur peut atteindre des niveaux dangereusement élevés par exemple dysfonctionnement incendie pouvant occasionner des blessures ...

Страница 16: ...dung 50 Hz Verdichter W D H LCQC048 NTZ048 500 620 451 LCQC068 LCQC096 LCQC108 NTZ068 NTZ096 NTZ108 630 650 605 LCQC136 NTZ136 755 700 656 LCQC215 LCQC271 NTZ215 NTZ271 900 900 759 LGQC048 NTZ048 700 500 392 LGQC068 LGQC096 LGQC108 NTZ068 NTZ096 NTZ108 800 600 442 LGQC136 NTZ136 1000 700 555 Verdampfungstemperatur C Umgebungstemperatur C 15 5 5 15 20 50 45 35 25 15 HGZ R134a 30 20 10 0 10 50 45 35...

Страница 17: ...r Höhe Min Abstand 2 x Länge des Aggregats Ein oder zwei Lüfter für Danfoss Verflüssigungssätze Ein oder zwei Lüfter für Danfoss Verflüssigungssätze Lüfterkondensator Lüfterkondensator Hubvolumen Ein oder zwei Lüfter für Danfoss Verflüssigungssätze Abb 2 Abb 5 Abb 3 Abb 4 ...

Страница 18: ...ei UL konformem Einsatz 1 bar Pe 30in Hg KP 15 15A 17W 17B KP17W B 060 539366 060 539466 ND auto ND auto HD man HD auto Einschalten ND HD ND HD Di erenz Feste Di erenz Ausschalten Manueller Test Einschalten Anzugsmoment 2 5 Nm Nur Kupferleitungen verwenden Ausschalten Manueller Reset SPDT ND Signal ND ND HD HD ND HD Signal Werkseinstellung Manueller Reset Umschaltbarer Reset W B Umschaltbarer Rese...

Страница 19: ...bar sind müssen beim Transport unternehmen schriftlich als Reklamation an gezeigt werden Die gleiche Empfehlung gilt für die Fälle in denen die Transportanweisungen nicht eingehalten wurden Bitte hinsichtlich der Lagerung die auf dem Verpackungskarton aufgedruckten Sicherheit sanweisungen beachten Es ist dafür zu sorgen dass der Verflüssig ungssatz nicht bei Umgebungstemperaturen unter 35 C oder ü...

Страница 20: ... evakuieren zu können Empfohlene Vorgehensweise 1 Nach Abschluss der Lecksuche 2 ist der Druck in der Anlage auf ein Vakuum von 500 mHg 0 67 mbar abzusenken 3 Sobald das Vakuum 500 mHg erreicht die Pumpe von der Anlage trennen 4 Das Vakuum von 500 mHg 0 67 mbar 4 Stunden lang halten Dieser Druck soll an der Kälteanlage und nicht mit dem Manometer an der Vakuumpumpe gemessen werden Steigt der Druck...

Страница 21: ... Ver dichter erneut starten lässt Verdichter baut keinen Druck auf Bitte kontrollieren ob etwaige in der Anlage befind lichen Bypassventile geschlossen sind Befinden sich sämtliche Magnetventile tatsächlich in der gewünschten Stellung offen oder geschlossen Ist das interne Überströmventil offen steigt die Temperatur im Kurbelgehäuse desVerdichters an was zu einem Auslösen des Motorschutzschalters ...

Страница 22: ...ertem Personal vorgenommen werden Die Oberflächentemperatur an den Rohrlei tungen desVerflüssigungssatzes und amVerdich terkann100 C übersteigenundschwereVerbren nungen verursachen Bei Arbeiten im Bereich des Verdichters und der Kältemittel rohrleitung ist besondere Vorsicht walten zu lassen Darüber hinaus kann ein in Betrieb befindlicher Verdich ter sehr kalte Oberflächen temperaturen bis zu 45 C...

Страница 23: ...271 MTZ125 MTZ144 MTZ160 1350 820 759 Zastosowania niskotemperaturowe LBP 50 Hz Sprężarka W D H LCQC048 NTZ048 500 620 451 LCQC068 LCQC096 LCQC108 NTZ068 NTZ096 NTZ108 630 650 605 LCQC136 NTZ136 755 700 656 LCQC215 LCQC271 NTZ215 NTZ271 900 900 759 LGQC048 NTZ048 700 500 392 LGQC068 LGQC096 LGQC108 NTZ068 NTZ096 NTZ108 800 600 442 LGQC136 NTZ136 1000 700 555 Temperatura parowania C Temperatura oto...

Страница 24: ...sokoÊç wymiennika Minimalny odst p 2 x szerokoÊç agregatu 8 do 12 m s przy minimalnej wydajnosci 8 do 12 m s przy maksymalnej wydajnosci Tlumik wibracji Danfoss Kondensator wentylatora Kondensator wentylatora Pojemność skokowa cm3 Danfoss Fig 2 Fig 5 Fig 3 Fig 4 ...

Страница 25: ... 30in Hg KP 15 15A 17W 17B KP 17B 060 539366 060 539466 LP auto LP auto HP man HP auto Ciśnienie załączania Różnica Stała różnica Ciśnienie wyłączania Sprawdzian manualny Ciśnienie załączania Tightening torque 20 lb in Use copper wire only Ciśnienie wyłączania Reset manuel SPDT LP niskie ciśnienie LP LP HP Wysokie ciśnienie HP LP HP niskie i wysokie ciśnienie Ustawienia fabryczne Reset manuel Odbl...

Страница 26: ...ądzenie i jego opa kowanie nie jest narażone na bezpośrednie działanie deszczu czynników łatwopalnych oraz czynników powodujących korozję 3 Środki bezpieczeństwa podjęte przed mon tażem urządzenia Wszystkie podłączenia obsługa i serwisowa nie urządzenia muszą być wykonywane przez wykwalifikowane osoby zgodnie z przyjętymi zasadami i procedurami bezpieczeństwa Agregat skraplający musi być ulokowany...

Страница 27: ...ci 2 obniżyć ciśnienie w instalacji do 500 µm Hg 3 po osiągnięciu w w ciśnienia odizolować układ od pompy próżniowej 4 ciśnienie500µmHgpowinnobyćutrzymane przez ok 4 godziny a wartość ciśnienia powinna być mierzona w instalacji chłodniczej a nie odc zytywana ze wskażnika pompy próżniowej 5 jeżeli ciśnienie rośnie powtórzyć próbę szc zelności patrz pkt 5 Pompa próżniowa Do prób powinno się używać d...

Страница 28: ...nież czy zawory elektromagnety czne są we właściwej pozycji W przypadku gdy wewnętrzny zawór upustowy jest otwarty karter sprężarki będzie ciepły i zadziała wewnętrzne zabezpieczenie silnika W takim przypadku należy odczekać ok 2 3 godz po tym czasie sprężarka załączy się automatycznie Niewłaściwe odgłosy podczas pracy Należy sprawdzić czy sprężarka nie jest zalewana ciekłym czynnikiem mierząc prz...

Страница 29: ...rociągu cieczowym na zwykły odwadniający i w razie potrzeby usunąć wkład z filtra na stronie ssawnej 14 Wskazówki dla użytkownika Wszystkie czynności serwisowe powinny być wykonywane tylko i wyłącznie przez wykwa lifikowane osoby Temperatury powierzchni rur agregatu i powierzchni sprężarki mogą przekroczyć 100 C i w związku z tym mogą być przyczyną poważny ch poparzeń Podczas wykonywania czynnoś c...

Отзывы: