VI.GC.W3.8N 

AVT

ENGLISH

Safety Notes

Prior to assembly and commissioning to 

avoid injury of persons and damages of 

the devices, it is absolutely necessary to 

carefully read and observe these instructions.
Necessary assembly, start-up, and maintenance 

work must be performed only by qualified, 

trained and authorized personnel. 
Prior to assembly and maintenance work on the 

controller, the system must be:

- depressurized, 

-  cooled down,

-  emptied and 

- cleaned.
Please comply with the instructions of the 

system manufacturer or system operator.

Disposal instruction

This product should be dismantled and its 
components sorted, if possible, in various 

groups before recycling or disposal. 
Always follow the local disposal regulations.

Definition of Application

The temperature actuator AVT is, in 

combination with Danfoss valves and Danfoss 

controller combinations, used for temperature 

control of water and water glycol mixtures for 

heating, district heating and cooling systems. 
The temperature controllers (temperature 
actuators with valves) with the temperature 
actuator AVT are type-tested acc. to EN 14597 
and comply with the safety requirements for 
temperature control and temperature limiting 
units in heat systems.
The technical parameters on the product labels 
determine the use.

Application examples 

Temperature actuator AVT can be combined 

with:

  VG(F), VGU(F) and VGS valves.

  Combination pieces K2, K3 and valves 

mentioned above.

  Flow and temperature controller AVQT 

and Flow and temperature controller with 

integrated control valve AVQMT.

  Differential pressure and temperature 

controller with flow limitation (and fixed 

setting) AVPBT(-F).

  Differential pressure, flow and temperature 

controller AVPQT.

Assembly

Admissible Installation Positions 

Temperature actuator with valves

-  In combination with VG(F) or VGU(F) valves:

•  Can be installed in any position 

.

-  In combination with VGS valves:

•  Medium temperatures up to 160 °C:
  Can be installed in any position 

.

•  Medium temperatures > 160 °C:

  Can be installed horizontal and in 

horizontal pipelines with the actuator 
oriented downwards 

.

Admissible installation positions in 
combination with AVQT, AVQMT, 

AVPBT(-F) and AVPQT - see relevant instructions.

Temperature sensor

-  The capillary tube may not be twisted or 

buckled. The minimum bending radius is 
50 mm 

.

-  The place of installation must be chosen in 

a way that the temperature of the medium 

is directly taken without any delay. Avoid 

overheating of temperature sensor 

-  The temperature sensor must be immersed 

into the medium in its full length.

Temperature sensors 170 mm R½” and 

210 mm R¾”:

-  The temperature sensor may be installed in 

any position 

.

Temperature sensor 255 mm R¾”:

-  The temperature sensor must be installed as 

shown on the picture 

.

Installation Location and Installation 

Scheme 

• AVT/valve 

, AVT/AVT/valve 

 return 

mounting

• AVT/valve 

, AVT/AVT/valve 

 flow 

mounting

Valve Installation 

1.   Clean pipeline system prior to assembly.

2.  The installation of a strainer in front of the 

controller is strongly recommended 

.

3.  Install temperature indicators in the system 

part to be controlled.

4.   Install valve

•  The flow direction indicated on the 

product label 

 or on the valve 

 must be 

observed.

•  The valve with mounted weld-on 

tailpieces may only be spot welded to the 
pipeline 

.

  The weld-on tailpieces may be welded only 

without the valve and seals! 

⑤⑥

  If these instructions are not observed, high 

welding temperatures may destroy the 

seals.

• Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces must 

be clean and without any damage. 

Tighten screws in flanges crosswise in 3 

steps up to the maximum torque (50 Nm).

5. 

Caution

:

 

Mechanical loads of the valve body by the 
pipelines are not permitted

 

.

Mounting of temperature actuator 

Before mounting the actuator, carry out Filling 

the system, First start-up and Leak and pressure 
tests, see 

.

Place temperature actuator AVT at the valve 

 

or combination piece 

 and tighten union nut 

with wrench SW 50. Torque 35 Nm.

Insulation 

Do not insulate the temperature actuator and 

the valve as well.

Start-up 

Valves VG, VGF and VGS 

 are normally 

opened (NO) valves.

Filling the system and Leak and pressure test 
should be done without mounted temperature 
actuator 

 - valve has to be open.

Valves VGU and VGUF 

 are normally 

closed (NC) valves.

Filling the system and Leak and pressure test 
should be done with open valve. Temperature 
actuator 

 could be mounted and set in a way 

that the valve is open.

Filling the system, first start-up 

1.  Slowly open shut-off devices in the flow 

pipeline 

.

2.  Slowly open shut-off devices 

 in the return 

pipeline.

Leak and Pressure Tests

Pressure must be gradually increased at 
the +/- side of the valve . Do not test with 

closed valve.

Non-compliance may cause damages at the 
actuator or the valve.
A pressure test of the entire system must be 
carried out in accordance with manufacturer’s 
instructions.
The maximum test pressure for the valves is: 

1.5 × PN

PN - see product label!

Putting out of operation

1.  Slowly close shut-off devices 

 in the flow 

pipeline.

2.  Slowly close shut-off devices 

 in the return 

pipeline.

Settings 

Temperature Setting

The temperature setting range is indicated on 
product label 

.

Pre-conditions:

The system must be opened and the flow of the 
medium guaranteed.

Procedure:

•   Set desired setpoint by turning the setting 

adjuster 

.

-  Turning to the left (counter-clockwise) 

increases the setpoint.

-  Turning to the right (clockwise) reduces the 

setpoint.

•   The position of the setpoint adjuster on a 

scale value 

 means:

 

1 minimum setpoint

 

5 maximum setpoint

•  Observe temperature indicator 

.

•   Wait for about 3 to 5 min. until the 

temperature indicator shows the final value.

•  If the device is used as a temperature 

monitor, the setting adjuster 

 must be 

sealed by a sealing wire 

.

Adjustment diagram 

Temperature setting

Relation between scale numbers 1-5 and closing 
temperature.

The values given are approximate

Dimensions, Weights 

1)

  Conical ext. thread acc. to EN 10226-1

2)

  Flanges PN 25, acc. to EN 1092-2

Содержание AVT/VG

Страница 1: ...w danfoss es Page 8 NEDERLANDS Temperatuurregelaar AVT www danfoss nl Blz 9 SLOVEN INA Pogon regulatorja temperature AVT www danfoss si Stran 10 ESKY Pohon p mo inn ho regul toru teploty AVT www danfo...

Страница 2: ...2 Danfoss 2017 08 VI GC W3 8N AVT...

Страница 3: ...Danfoss 2017 08 3 VI GC W3 8N AVT DN L mm 15 69 20 74 25 79 32 104 40 114 50 134...

Страница 4: ...A 70 G 2A 82 G 2 A d 21 26 33 42 47 60 R 1 1 2 3 4 1 11 4 L1 2 130 150 160 L2 131 144 160 177 L3 139 154 159 184 204 234 k 65 75 85 100 110 125 d2 14 14 14 18 18 18 n 4 4 4 4 4 4 AVT VG VGU AVT VGS AV...

Страница 5: ...ation 1 Clean pipeline system prior to assembly 2 The installation of a strainer in front of the controller is strongly recommended 3 Install temperature indicators in the system part to be controlled...

Страница 6: ...VT ventilmontering i flowledning Ventilinstallation 1 Reng r r rledningssystemet f r montering 2 Det anbefales st rkt at installere et filter foran regulatoren 3 Monter temperaturm lere f r og efter d...

Страница 7: ...einen Schmutzf nger vor dem Regler einzubauen 3 Temperaturanzeiger vor und hinter den entsprechenden Anlageteilen einbauen 4 Ventil einbauen Durchflussrichtung auf dem Typenschild oder Ventil beachten...

Страница 8: ...la v lvula 1 Limpie el sistema de tuber as antes del montaje 2 Se recomientda la instalaci n de un filtro delante del controlador 3 Instale indicadores de temperatura en la parte del sistema a control...

Страница 9: ...sluiter Montage in de retour AVT regelafsluiter AVT AVT regelafsluiter Montage in de aanvoer Installatie van de regelafsluiter 1 Zorg dat de installatie schoon is 2 Het toepassen van een filter voor d...

Страница 10: ...hema vgradnje AVT ventil AVT AVT ventil vgradnja v povratek AVT ventil AVT AVT ventil ventil vgradnja v dovod Vgradnja ventila 1 Pred monta o o istite cevovod 2 Mo no priporo amo vgradnjo filtra pred...

Страница 11: ...poloh ch vyzna en ch na obr zku Um st n a sch ma instalace AVT ventil AVT AVT ventil Mont na p vodn v tev AVT ventil AVT AVT ventil Mont na p vodn v tev Instalace ventilu 1 P ed mont vy ist te potrubn...

Страница 12: ...talacj 2 Przed regulatorem zamontowa filtr 3 Zamontowa wska niki temperatury termometry w tej cz ci uk adu kt ra b dzie regulowana 4 Zamontowa zaw r Nale y zachowa kierunek przep ywu zaznaczony na tab...

Страница 13: ...montuojami tiekimo vamzdyne Vo tuvo montavimas 1 I valykite vamzdyn prie prad dami montavim 2 Labai rekomenduojame sumontuoti filtr prie ais reguliatori 3 Sumontuokite temperat ros indikatorius toje s...

Страница 14: ...VT Danfoss AVT EN 14597 AVT VG F VGU F VGS 2 3 AVQT AVQMT AVPBT F AVPQT VG F VGU F VGS 160 C 160 C AVQT AVQMT AVPBT F 50 170 R 210 R 255 R AVT AVT AVT AVT AVT AVT 1 2 3 4 50 Nm 5 AVT SW 50 35 VG VGF V...

Страница 15: ...Danfoss 2017 08 15 VI GC W3 8N AVT 1 5 3 5 1 5 mm 1 EN 10226 1 2 P 25 EN 1092 2...

Страница 16: ...s reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady a...

Отзывы: