
21
Reglermanual - VMGFF102
5.9 - Capacity control
This function adjusts the number of active compressors to
keep the heat exchanger water temperature at its setpoint.
The precision with which this is achieved depends on the
capacity of the water loop, the fl ow rate, the load, and the
number of stages available on the unit. The control system
continuously takes account of the temperature error with
respect to the setpoint, as well as the rate of change in this
error and the diff erence between entering and leaving water
temperatures, in order to determine the optimum moment at
which to add or withdraw a capacity stage.
If the same compressor undergoes too many starts (per hour)
or runs below one minute each time it is started this
automatically brings about reduction of compressor starts,
which makes leaving water temperature control less precise.
The high pressure, low pressure or defrost unloading functions
can also aff ect temperature control accuracy. Compres-sors are
started and stopped in a sequence designed to equalise the
number of start-ups (value weighted by their operating time).
5.10 - Head pressure control
The head pressure is independently controlled for each
circuit, based on the saturated condensing temperature value.
5.11 - Defrost function
This function only applies to heat pumps. Defrost is activated,
when the unit is in heating mode to reduce frost build-up on
the air heat exchanger. The defrost cycle can only be applied to
one circuit at a time. During the defrost cycle the fans of that
circuit are stopped, and the four-way refrigerant valve is
reversed, forcing the circuit to cooling mode. The fan can
temporarily be restarted during the defrost cycle. The defrost
cycle is fully automatic and does not require any setting.
5.12 - Desuperheater option
In units with desuperheater it is possible to reclaim the hot
water. To optimise this option, the condensing setpoint
should be increased (chapter 4.9.4 setpoint menu, sct_min)
while the desuperheater heat exchanger is used. Optimis-
ing desuperheater condensation is activated via dry contact
DSHTR_SW (see chapter 3.6.1).
5.13 - Additional electric heater stage control
The heat pump units can control up to four additional
electric heating stages (accessory).
The electric heating stages are activated to complement the
heating capacity when the following conditions are satisfi ed:
•
The unit uses 100% of the available heating capacity, or
the unit is limited in its operation by a protection mode
(low suction temperature, hot gas or defrost sequence in
progress protection), and in all cases cannot satisfy the
heating load.
•
The outdoor temperature is below a confi gured
threshold (see HCCONFIG confi guration).
•
The unit demand limit is not active.
The user may confi gure the last available electric heating
stages as a safety stage. In this case, the safety stage is only
activated in addition to the other stages if there is a machine
fault, preventing the use of the heating capacity. The other
electric heating stages will continue to operate as described
above.
5.14 - Control of a boiler
NOTE: The control of the electric heating stages or of a
boiler is not authorised for slave units.
The unit can control the start-up of a boiler, if it is in heating
mode. When the boiler is operating, the unit water pump is
stopped.
A heat pump unit and a boiler cannot operate together. In
this case the boiler output is activated in the following
conditions:
•
The unit is in heating mode, but a fault prevents the use
of the heat pump capacity.
•
The unit is in heating mode, but works at a very low
outdoor temperature, making the heat pump capacity
insuffi
cient. The outdoor air temperature threshold for
use of the boiler is fi xed at -10°C, but this value can be
adjusted in the HCCONFIG menu.
5.15 - Master/slave assembly
Two control units can be linked to produce a master/slave
assembly. The two machines are interconnected over the CCN
bus. All parameters required for the master/slave function
must be confi gured through the Service confi gura-tion
menu.
Master/slave operation requires the connection of a tempe-
rature probe at the common manifold on each machine, if the
heat exchanger leaving water temperature is controlled. It is
not required, if the entering water temperature is controlled.
The master/slave assembly can operate with constant or
variable fl ow. In the case of variable fl ow each machine must
control its own water pump and automatically shut down the
pump, if the cooling capacity is zero.
For constant fl ow operation the pumps for each unit are
continuously operating, if the system is operating. The master
unit can control a common pump that will be activated,
when the system is started. In this case the slave unit pump is
not used.
All control commands to the master/slave assembly (start/
stop, setpoint, heating/cooling operation, load shedding, etc.)
are handled by the unit which is confi gured as the master,
and must therefore only be applied to the master unit. They
will be transmitted automatically to the slave unit.
The master unit can be controlled locally, remotely or by CCN
commands. Therefore to start up the assembly, simply
validate the Master operating type (Master) on the master
unit. If the Master has been confi gured for remote control
then use the remote volt-free contacts for unit start/stop.
Содержание AR05
Страница 25: ...VMGFF102...