Reglermanual - VMGFF102

5.3 - Heat exchanger water pump control

The unit can control one or two heat exchanger water pumps. 
The pump is turned on when this option is confi gured (see 
PUMPCONFIG) and when the unit is in one of the on modes 
described above or in delay mode. Since the minimum value for 
the delay at start-up is 1 minute (confi gurable between 1 and 
15 minutes), the pump will run for at least one minute before 
the fi rst compressor starts.

The pump is kept running for 20 seconds after the unit goes to 
stop mode. The pump keeps working when the unit switches 
from heating to cooling mode or vice-versa. It is turned off  if 
the unit is shut down due to an alarm unless the fault is a frost 
protection error. The pump can be started in particular 
operating conditions when the heat exchanger heater is 
active (see chapter 5.5). See chapter 5.14 for the particular 
heat exchanger pump control for the follower unit (master/
slave assembly).

If two pumps are controlled and the reversing function has 
been selected (see PUMPCONF confi guration), the control tries 
to limit the pump run time delta to the confi gured pump 
change-over delay. If this delay has elapsed, the pump 
reversing function is activated, when the unit is running. 
During the reversing function both pumps run together for 
two seconds. If the pumps are of the variable fl ow rate type 
pump reversal will take place at the next machine start-up.

If a pump has failed and a secondary pump is available, the 
unit is stopped and started again with this pump.

The control provides a means to automatically start the 
pump each day at 14.00 hours for 2 seconds when the unit is 
off . If the unit is fi tted with two pumps, the fi rst pump is 
started on odd days and the second pump is started on even 
days. Starting the pump periodically for  few seconds 
increases the life-time of the pump bearings and the 
tightness of the pump seal.

5.4 - Control interlock contact

This contact checks the status of a loop (water fl ow switch 
and customer safety loop, see chapter 3.6). It prevents the 
unit from starting if it is open when the delay at start-up has 
expired. This open contact leads to an alarm shut-down, if 
the unit is running.

5.5 - Heat exchanger frost protection

The heater for the heat exchanger and the water pump (for 
units with a pump) can be energised to protect the heat 
exchanger, if it may be damaged by frost, when the unit is 
shut down for a long time at low outdoor temperature.

NOTE: Heat exchanger heater control parameters can be 
modifi ed, using the Service confi guration.

5.2.2 - Heating/cooling/auto selection

The table below summarises the unit heating/cooling opera-
tion, based on the following parameters:
• 

Control type: indicates whether the unit operates in 
local, remote or CCN mode. See section 5.1.

• Unit 

on/off  status: indicates whether the unit is shut 

down (not authorised to start) or in operation (or 
authorised to start).

• 

Heating/cooling/auto selection in local mode: operating 
mode selected via the user interface. See GENUNIT 
menu.

• 

Remote heating/cooling contacts: these contacts are 
only active if the unit is under remote control.

• 

HC_SEL: this network command permits heating/
cooling/auto control, if the unit is in CCN operating 
mode.

• 

Outside temperature: determines the operation, if the 
unit is in automatic heating/cooling/standby changeover 
mode.

PARAMETER STATUS

ON/OFF STATUS

CONTROL TYPE

HEATING/COOLING 
SELECTION IN LOCAL 
MODE

REMOTE HEATING/
COOLING CONTACTS

HC_SEL

OUTDOOR TEMPERATURE

OPERATING MODE

Off -

-

-

-

-

Cooling

On

Local

Cooling

-

-

-

Cooling

On

Local

Heating

-

-

-

Heating

On

Local

Auto

-

-

> Cooling threshold

Cooling

On

Local

Auto

-

-

< Heating threshold

Heating*

On

Local

Auto

-

-

Between cooling and heating thresholds

Standby

On

Remote

-

Cooling mode

-

-

Cooling

On

Remote

-

Heating mode

-

-

Heating

On

Remote

-

Auto mode

-

> Cooling threshold

Cooling

On

Remote

-

Auto mode

-

< Heating threshold

Heating*

On

Remote

-

Auto mode

-

Between cooling and heating thresholds

Standby

On

CCN

-

-

Cooling

-

Cooling

On

CCN

-

-

Heating

-

Heating

On

CCN

-

-

Auto

> Cooling threshold

Cooling

On

CCN

-

-

Auto

< Heating threshold

Heating*

On

CCN

-

-

Auto

Between cooling and heating thresholds

Standby

*  

Does not apply to cooling only units that do not control a boiler.

Содержание AR05

Страница 1: ...AR05 Control Operation instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP...

Страница 2: ...ics 6 4 3 Password screens 6 4 4 Menu screen characteristics 7 4 5 Data screen or con gurable parameter characteristics 7 4 6 Parameter modi cation 7 4 7 Operating mode screen 8 4 8 Menu tree structur...

Страница 3: ...egulate the AR05 units These units have one or two refrigerant circuits Controls compressor start up to control the water loop the fans to optimise operation of each refrigerant circuit the defrost cy...

Страница 4: ...sure the suction and discharge pressure in each circuit Thermistors The heat exchanger water sensors are installed in the enter ing and leaving side The outdoor temperature sensor is mounted under a m...

Страница 5: ...pump 1 J2B CH 22 NRCP2 BASE Command water pump 2 J2B CH 23 NRCP2 BASE The change over between the two pumps is con gurable Alarm relay output J3 CH 24 30A 31A NRCP2 BASE Unit operation relay output J3...

Страница 6: ...ction screen Password entry screen Parameter modi cation screen NOTE If the interface is not used for a long period it will go black The control is always active the operating mode remains unchanged T...

Страница 7: ...arameters such as the water temperature setpoints MAINMENU TEMP Current path in the menu structure EWT 12 0 C List of items LWT 7 0 C Cursor position OAT 35 0 C CHWSTEMP 17 8 C SCT_A 57 0 C Leaving Wa...

Страница 8: ...Select Machine Mode Description of the screen Local On List of the machine operating modes Local Schedule Cursor CCN Remote The Up and Down keys position the cursor on the selected operating mode Fou...

Страница 9: ...DAY BRODCAST DATETIME CTRL_ID HOLIDY01S HOLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs O...

Страница 10: ...LWT nnn n C Heat exchanger leaving water temperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n...

Страница 11: ...tput B1 exv_a 0 100 EXV position circuit B HD_POS_B 0 100 Position variable fan speed controller B RV_B On O Four way refrigerant valve C_HEATER On O Heat exchanger and lower coil heater BOILER On O B...

Страница 12: ...of start ups fan B1 hr_cpum1 nnnnn hours Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles c...

Страница 13: ...rent alarm 1 alarm_2c nnnnn Current alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus a...

Страница 14: ...me Summer time startmon 1 to 12 3 Month startdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday s...

Страница 15: ...0 to 13 9 0 C Delta T for maximum reset cr_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature...

Страница 16: ...Monday P2 period 2 7h00 18h00 Monday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not us...

Страница 17: ...l be in occupied or unoccupied mode depending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTEN...

Страница 18: ...ange over to heating mode Heating cooling control can be automatic or manual In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold valu...

Страница 19: ...customer safety loop see chapter 3 6 It prevents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 He...

Страница 20: ...Heating sp 1 open Heating setpoint 1 Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modi ed so that less machine capacity is required in cooling mode the se...

Страница 21: ...rotection and in all cases cannot satisfy the heating load The outdoor temperature is below a con gured threshold see HCCONFIG con guration The unit demand limit is not active The user may con gure th...

Страница 22: ...eturn to an autonomous operating mode until the fault is cleared If the master unit is halted due to an alarm the slave unit is authorised to start without prior conditions ATTENTION For heat pumps op...

Страница 23: ...hen communication is re established Installation bus fault or defective slave board Depending on the con guration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with...

Страница 24: ...ve 45 P 43 Heat exchanger temperature too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor p...

Страница 25: ...VMGFF102...

Отзывы: