17
Reglermanual - VMGFF102
4.9.26 - HOLIDY0XS menu
This function is used to defi ne 16 public holiday periods.
Each period is defi ned with the aid of three parameters: the
month, starting day and duration of the public holiday
period. During these public holidays the controller will be in
occupied or unoccupied mode, depending on the
programmed periods validated for public holidays.
Each of these public holiday periods can be displayed and
changed with the aid of a sub-menu.
ATTENTION: The broadcast function must be activated to
utilise the holiday schedule, even if the unit is running in
stand-alone mode (not connected to CCN).
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
HOL_MON
0-12
0
-
Holiday month
HOL_DAY
0-31
0
-
Holiday day
HOL_LEN
0-99
0
-
Holiday duration