14
Reglermanual - VMGFF102
4.9.15 - SCHEDULE menu
NAME
DESCRIPTION
OCC1P01S
Unit on/off time schedule
OCC1P02S
Unit setpoint selection time schedule
4.9.16 - HOLIDAY menu
NAME
DESCRIPTION
HOLDY_01
Holiday period 1
HOLDY_02
Holiday period 2
HOLDY_03
Holiday period 3
HOLDY_04
Holiday period 4
HOLDY_05
Holiday period 5
HOLDY_06
Holiday period 6
HOLDY_07
Holiday period 7
HOLDY_08
Holiday period 8
HOLDY_09
Holiday period 9
HOLDY_10
Holiday period 10
HOLDY_11
Holiday period 11
HOLDY_12
Holiday period 12
HOLDY_13
Holiday period 13
HOLDY_14
Holiday period 14
HOLDY_15
Holiday period 15
HOLDY_16
Holiday period 16
4.9.17 - BRODCAST menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
CCNbroad
0/1/2
2
-
Activates the broadcast
0 = deactivated, 1= broadast during holidays at the network, 2 =
broadcast during holidays, machine only
oatbusnm
0 to 239
0
-
Broadcast of the outside temperature
Bus number of the machine with the outside temperature
oatlocad
0 to 239
0
-
Element number of the machine with the outside temperature
dayl_sel
Disable/Enable
Disable
-
Activation summer time, winter time
Summer time
startmon
1 to 12
3
-
Month
startdow
1 to 7
7
-
Day of the week (1 = Monday)
startwom
1 to 5
5
-
Week of the month
Winter time
stopmon
1 to 12
10
-
Month
stoptdow
1 to 7
7
-
Day of the week (1 = Monday)
stopwom
1 to 5
5
-
Week of the month
4.9.18 - GENCONF menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
lead_cir
0/1/2
0
-
Circuit loading sequence
0 = auto, 1 = A fi rst, 2 = B fi rst
seq_typ
No/Yes
No
-
Loading sequence by circuit
ramp_sel
No/Yes
No
-
Ramp loading sequence
off _on_d
1 to 15
1
min
Start-up delay
nh_limit
0 to 100
100
%
Capacity limitation in night mode
nh_start
00:00 to 24:00
00:00
-
Night mode start hour
nh_end
00:00 to 24:00
00:00
-
Night mode stop hour
bas_menu
0 to 3
0
-
Basic menu confi guration
0 = total access
1 = access to the alarm menu by password
2 = access to the setpoint menu by password
3 = combination of 1 and 2
synoptic
No/Yes
No
-
Synoptic diagram displayed
4.9.19 - PUMPCONF menu
NAME
FORMAT
DEFAULT
UNIT
DESCRIPTION
pump_seq
0/1/2/3/4
0
-
Heat exchanger pump sequence
0 = no pump
1 = one pump
2 = two pumps auto
3 = pump 1 manual
4 = pump 2 manual
pump_del
24 to 3000
48
hours
Rotation time between pumps
pump_per
No/Yes
No
-
Pump seizure protection
pump_sby
No/Yes
No
-
Pump shutdown when the unit is in standby
pump_loc
No/Yes
Yes
-
Flow rate verifi cation when the pump has shut down
Содержание AR05