To avoid injury and damage to persons and 

devices, it is absolutely necessary these 

instructions and Safety notes attached are 

carefully read and observed prior to assembly 

and commissioning.
Do not dismantle actuators with safety spring 

function! Danger of injury and life in case of 

improper handling!
Actuator is heavy. Handle with care to avoid 

injury or product damage.

Wiring

Do not touch anything on the PCB! 

Do not 

remove the cover before the power supply is 

fully switched off.

Max. allowed current output on terminals 

4 and 5 is 4 A.

NOTE:

If AME 655 is connected as 3 point version only 
DIP1 and DIP2 are active

DIP switch setting 

DIP1: FAST/SLoW – Speed selection 

 

-  FAST position; 3 (4) s/mm (see Tech. data)

-  SLOW position; 6 s/mm 

DIP2: DIr/INv – Direct or inverse acting 

selector 

 

-  DIR position; the actuator is direct acting to 

input signal

-  INV position; the actuator is inverse acting to 

input signal

DIP3: 2-10v/0-10v – Input/output 

-  2-10V position; the input signal is in the range 

from 2-10 V (voltage input) or from 4-20 mA 

(current input)

-  0-10V position; the input signal is in the range 

from 0-10 V (voltage input) or from 0-20 mA 

(current input)

Signal range selector sets Y and X signal.

DIP4: LIN/MDF – Characteristic 

modification function 

-  LIN position; Linear correlation between Y 

signal and stem position

-  MDF position; Enables modified correlation 

between Y signal and stem position. Degree 

of modification depends on setting of 

potentiometer CM.

Function enables to change MCV (valve and 

actuator) characteristic (for example linear to 

logarithmic and logarithmic to linear) and works 

with all combinations of DIP switch settings. 

DIP5: 100%/95% – Stroke limitation: 

100% position; Full stroke

95% position; Stroke limited to 95%

DIP6: C/P – output signal mode selector

⑨ 

Output signal is present on terminal 4 when 

position of the actuator is equal or  lower 

then setpoint of S4.

  Output signal is present on terminal 5 when 

position of the actuator is equal or lower then 

setpoint of S5. 

 position C; output signal is present on 

terminals 4 or 5 independent of the input 

signal

-  position P; output terminals 4 and 5 are 

bridged with input terminals 1 and 3

DIP7: Uy/Iy –Input signal type selector: 

-  position Uy; input signal Y is set to voltage (V)

-  position Iy; input signal Y is set to current 

(mA) 

DIP8: Ux/Ix –output signal type 

selector: 

-  position Ux; output signal X is set to voltage 

(V)

-  position Iy; output signal X is set to current 

(mA)

NOTE:

If DIP7 is in ON position, Y detection is disabled.

Functions accessible from cover

rESET button

Actuators AME 655/658/659  have external 

RESET button which is located on top cover of 

the actuator next to LED indicators. With this 

button you can enter or exit Stand-By mode 

(press once) or Self stroking mode (press and 

hold for 5 seconds). See next paragraph for 

mode details.

Self stroking mode 

Self stroking mode starts automatically

the first time when power supply is

applied to the actuator. To start self

stroking procedure 

press and hold

rESET button for 5 seconds

 

 until

the green light starts flashing. End positions of 

the valve are automatically set and the actuator 

goes to stationary mode 

 and starts

responding to the control signal.

Stand-By mode 

 

(versions AME 655/658/659)

Press the rESET button

 to enter

Stand-By mode. The actuator stops

in current position and stops responding

to any control signal. Red light is

constantly lit. You can now manually

operate the actuator.

Manual operation

Mechanical and electrical operation are 

not allowed to be used at the same time! 

Actuators AME 655/658  can be manually 

positioned when in Stand-By mode or when 

there is no power supply (mechanically).

Actuators AME 659 can be manually positioned 

only in Stand-By mode.

Actuator 

type

Mechanical 

operation

Electrical 

operation

AME 655

AME 658

AME 659

Mechanical manual operation 

A

 

Actuators AME 655/658 have a manual 

operation knob on the top of the housing which 

enables hand positioning of  the actuator.

Mechanical manual operation shall be used 
only when no power supply. 

Electrical manual operation 

B

Actuators AME 655/658/659 have two buttons 

on the top of the housing that are used for 

electrical manual positioning (up or down) if 

the actuator is in Stand-By mode. First press the 

RESET button  until the actuator goes to Stand-

By mode (red LED is lit). By pressing  the upper 

button 

 the stem will be extracted and by 

pressing the lower button 

 the stem will be 

retracted.

Installation Guide 

AME 655 / 658 SD / 658 SU / 659 SD

DEN-SMT/SI 

VI.LE.M2.0S 

District Energy 

LANGUAGE

ENGLISH

Содержание AME 655

Страница 1: ...SD www cz danfoss com Strana 11 DANSK AME 655 658 SD 658 SU 659 SD www varme danfoss dk Side 12 DEUTSCH AME 655 658 SD 658 SU 659 SD www danfoss com Seite 13 Fran ais AME 655 658 SD 658 SU 659 SD www...

Страница 2: ...2 AUTO 13 mm 4 mm 2 2 12 15 Nm 2 2 2 12 15 Nm 2 A B Installation Guide AME 655 658 SD 658 SU 659 SD DEN SMT SI VI LE M2 0S District Energy...

Страница 3: ...3 3 AME 655 AUTO 3 5 4 5 mm 0 7mm 4 mm T 10 AME 658 SD 659 SD AME 658 SU 1 3 5 Nm 2 1 3 5 Nm 2 3 5 Nm 2 A B C Installation Guide AME 655 658 SD 658 SU 659 SD District Energy VI LE M2 0S DEN SMT SI...

Страница 4: ...0 4 20 mA X 0 2 10 V Output 0 4 20 mA AME 655 DIP 6 OFF 1a 1b DIP 6 ON 2a 2b AME 658 659 2 Wire Ferrite M16 M20 M16 M20 SN 0 V Neutral 1 3 24 230 V AC DC Power supply 4 5 SP AC 4 5 1 3 SP output 1 SP...

Страница 5: ...VL 2 3 DN 100 VFG S 2 VFG 3 AHQM DN 125 150 VFU AFQM FAST FAST SLOW SLOW FAST 3 4 sec mm 6 sec mm T sec 3 4 S 6 S LIN MDF CM S Y 2 10 V 0 10 V 2 10 V 0 10 V 0 2 4 CM CM Installation Guide AME 655 658...

Страница 6: ...2 10V 100 C Uy Ux S4 S5 input 1 3 C P output 4 5 output 4 5 C P Ux Ix Ux Ix Uy Iy 0 2 10V Uy Iy 0 4 20mA 0 2 10V 0 4 20mA 100 95 100 95 100 stroke 95 stroke Installation Guide AME 655 658 SD 658 SU 6...

Страница 7: ...7 7 AUTO 3 5 4 5 mm 0 7mm T 10 0 7 1 1 Nm 2 Installation Guide AME 655 658 SD 658 SU 659 SD District Energy VI LE M2 0S DEN SMT SI...

Страница 8: ...r konstant Leuchtet dauerhaft Allum e en permanence Folyamatosan vil g t Dega nuolat wieci wiat em sta ym Stalno upaljeno Stationary mode Actuator has reached upper end position retracted stem Stacion...

Страница 9: ...s cycle Flashing 1 s cycle Flashing LED Yellow RESET AUTO AME 655 658 1s STAND BY ON STAND BY OFF Constantly lit LED Red AME 655 658 659 A B1 B2 Installation Guide AME 655 658 SD 658 SU 659 SD Distri...

Страница 10: ...y Input signal type selector position Uy input signal Y is set to voltage V position Iy input signal Y is set to current mA DIP8 Ux Ix Output signal type selector position Ux output signal X is set to...

Страница 11: ...l X je nastaven na proud mA POZN MKA Pokud je DIP7 v zapnut poloze ON detekce Y je vypnuta Ovl dac funkce na servopohonu Tla tko RESET Servopohony AME 655 658 659 maj vn j tla tko RESET kter se nach z...

Страница 12: ...signaltype position Uy Indgangssignal Y er indstillet til sp nding V position Iy Indgangssignal Y er indstillet til str m mA DIP8 Ux Ix Valg af udgangssignaltype position Ux Udgangssignal X er indstil...

Страница 13: ...eine Spannung in V ausgew hlt Position Iy Als Ausgangssignal X wird eine Stromst rke in mA ausgew hlt BITTE BEACHTEN Wenn sich der Schalter DIP 7 in Position ON befindet ist die Y Erkennung deaktivier...

Страница 14: ...gl sur la tension V position Iy le signal de sortie X est r gl sur le courant mA REMARQUE Si DIP7 est en position MARCHE la d tection Y est d sactiv e Fonctions accessibles depuis le capot Bouton REIN...

Страница 15: ...z X kimenti jel fesz lts gre V be ll tva Iy poz ci az X bementi jel ramra mA be ll tva FIGYELEM Ha a DIP7 ON poz ci ban van akkor az Y rz keli ki van kapcsolva A fed lr l el rhet funkci k RESET gomb A...

Страница 16: ...ustatyta kad i jimo signalas X rodo srov mA PASTABA jei 7 funkcij parinkimo jungiklis yra pad tyje JUNGTAS Y aptikimas yra i jungtas Gaubte esantys funkcij valdikliai Mygtukas RESET nustatyti i naujo...

Страница 17: ...Ix sygna wyj ciowy X jest ustawiony na pr d mA UWAGA Je li prze cznik DIP7 jest w po o eniu W wykrywanie sygna u Y jest wy czone Funkcje dost pne na pokrywie Przycisk ZEROWANIE Si owniki AME 655 658...

Страница 18: ...IP 8 Ux Ix Ux X Iy X DIP7 Y RESET AME 655 658 659 RESET 5 RESET 5 AME 655 658 659 RESET AME 655 658 AME 659 AME 655 AME 658 AME 659 A AME 655 658 B AME 655 658 659 RESET Ferrite Wire Neutral Power sup...

Страница 19: ...i signal X je postavljen na volta u V polo aj Ix izlazni signal X je postavljen na struju mA NAPOMENA Ako je DIP7 u polo aju UKLJU ENO Y otkrivanje je onemogu eno Funkcije pristupa ne sa poklopca Dugm...

Страница 20: ...Ux X V Ix X mA DIP7 ON Y RESET AME 655 658 659 RESET LED 5 RESET 5 AME 655 658 659 RESET AME 655 658 AME 659 AME 655 AME 658 AME 659 A AME 655 658 B AME 655 658 659 RESET LED Ferrite Wire Neutral Pow...

Страница 21: ...21 21 Installation Guide AME 655 658 SD 658 SU 659 SD District Energy VI LE M2 0S DEN SMT SI...

Страница 22: ...s fenntartja mag nak a jogot hogy term keit rtes t s n lk l megv ltoztassa Ez vonatkozik a m r megrendelt term kekre is felt ve hogy e v ltoztat sok v grehajthat k a m r elfogadott specifik ci l nyege...

Отзывы: