AME 438 SU

ENGLISH

Safety Note

To avoid injury of persons and 
damages to the device, it is absolutely 
necessary to read and observe these 

instructions carefully.

Necessary assembly, start-up, and maintenance 
work must be performed by qualified and 
authorized personnel only.

Please comply with the instructions of the 
system manufacturer or system operator.

Do not remove the cover before the 
power supply is fully switched off.

Disposal instruction

This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal. 

Always follow the local disposal regulations.

Mounting actuator

Fix the actuator on the valve. 

Admissible Installation Positions. 

Wiring 

Do not touch anything on the PCB!
Switch off the power line before 
wiring the actuator! Lethal voltage!

Wire the actuator according to the wiring 
diagram.

Control signal

Control signal from the controller must be 
connected to terminals Y (input signal) and SN 
(common) on the AME printed board.

Output signal

Output signal from the terminal X can be used 
for indication of the current position. Range 
depends on the DIP switch settings.

Supply voltage

Supply voltage (24 V~ −15 to +10 %, 50/60 Hz) 
must be connected to the terminals SN and SP.

DIP switch settings 

U

I

2 V_---V

0 V_---V

Direct

Inverse

---

Sequential

0(2) V_5(6) V

5(6) V_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % Kvs

Red. Kvs

Reset

Reset

  Factory settings: 

ALL switches are on OFF position! 

 

Note:

 All combinations of DIP switches are 

allowed. All functions that are selected are 
added consecutively. There is only one logic 
override of functionalities i.e. the switch No.6 
Proportional / 3 point, which sets actuator to 
ignore control signal and works as a “simple” 
3-point actuator.

SW1: U/I 

  Factory setting: 

voltage control signal (0-10 V).

SW2: 2-10 V / 0-10 V 

  Factory setting is: 

2-10V.

SW3: Direct/Inverse 

  Factory setting is: 

DIRECT

SW4:---/Sequential 

Two actuators can be set to work parallel with 
one control signal. If the SEQUENTIAL is set then 
an actuator responds to split control signal (see 
0(2)-5(6)V/5(6)-10V).

 

Note:

 This combination works in combination 

with switch No.5: 0(2)-5(6)V/5(6)-10V

SW5: 0(2)-5(6)V/5(6)-10V 

 

Note:

  This function is available if switch No.4: 

--- / Sequential is set. 

SW6: Proportional/3 point 

Actuator needs to perform Self 
stroking prior changing DIP 6 to ON.
Output signal depends on DIP 2, 3&5 
setting.

Actuator can operate in modulating (DIP 6 to 
OFF) or in “simple” 3-point mode, if the 3-point 
function is selected (DIP 6 to ON). 

Connect power supply on terminals SN and SP 
terminals.

Factory set DIP 6 to OFF for operating actuator 
in Modulating mode.

Actuator’s stem will run to its totally extended 
or retracted position by bridging SN signal to 
terminals 1 or 3 and will remain in this positron 
as long as potential is present. 

Set DIP 6 to ON for operating actuator in 3 point 
mode.

Look carefully wiring diagram as wiring is 
different for controllers with triac output (ECL) 
in comparison to controllers with relay output.

Return signal X indicates the correct position.

  

Note:

 If 

3 point

 function is selected actuator 

does not respond to any control signal on 
port Y. It only rises and lowers spindle if power 
is supplied on port 1 or 3.

SW7: LOG. flow/LIN. flow 

  Factory setting is: 

LOG. Flow (characteristic of valve is 
unchanged)

 

Note:

 If this function is used in combination 

with non-logarithmic valves the characteristic 
of motorised valve will be anti-logarithm of 
valve’s characteristic (e.g. valve with linear 
characteristic will be transformed to quick 
open characteristic). 

SW8: 100% K

VS

/RED. K

VS

 

 

Note: 

This function works properly only with 

logarithmic (equal percentage) valves.

SW9: Reset 

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and will 
normally last a few minutes. The stroke length 
of the valve is stored in the memory after self 
adjustment has been completed. To restart 
self adjustment, change the position of RESET 
switch (switch No.9). If the supply voltage is 
switched off or falls below 80% in more then 
0.1 s, the current valve position will be stored 
in the memory and all data remain saved in the 
memory also after a power supply cut-out.

Function test

The indicator light shows whether the 
positioner is in operation or not. Moreover, the 
indicator shows the control status and faults.
Constant light

-  normal operation

No light 

-  no operation or no power supply

Intermittent light (1 Hz)  

-  self adjusting-mode

Intermittent light (3 Hz): 

-  power supply too low
-  insufficient valve stroke (<20 s)
-  end-position cannot be reached.

Dimensions 

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Bush

X

O

O

O

O

O

Electromagnet

X

O

O

O

O

O

Housings

X

O

O

O

O

O

Adapter neck

X

O

O

O

O

O

Brake Weights

X

O

O

O

O

O

Clamp

X

O

O

O

O

O

Yoke

X

O

O

O

O

O

O:  Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X:  Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;

Содержание AME 438 SU

Страница 1: ...a 9 SUOMI AME 438 SU www danfoss fi Sivu 10 LIETUVI K AME 438 SU www sildymas danfoss lt Puslapis 11 POLSKI AME 438 SU www danfoss pl Strona 12 AME 438 SU www danfoss ru 13 MAGYAR AME 438 SU www danfo...

Страница 2: ...2 Danfoss 2016 11 VI LE F3 3O AME 438 SU 5 95 RH no condensing MAINTENANCE FREE 4 6mm 1mm T 10 6 13mm 2 4 5 mm 5 7 Nm 1 6mm 1 13mm 1 30sec 4 2 mm 5 mm 4 mm 2 4 mm 4...

Страница 3: ...ller with triacs output Proportional 3 point RL SN 0 V Neutral SP 24 VAC Power supply 1 24 VAC Input 3 X 0 2 10 VDC Output Proportional 3 point RL SN 0 V Neutral SP 24 VAC Power supply Y 0 2 10 V Inpu...

Страница 4: ...Danfoss 2016 11 4 VI LE F3 3O AME 438 SU...

Страница 5: ...29 222 32 11 4 2 112 35 226 40 11 2 21 4 132 43 237 50 2 2 160 47 242 VRB 3 VRG 3 15 1 80 40 216 20 11 4 80 45 218 25 1 11 2 95 50 222 32 11 4 2 112 58 226 40 11 2 21 4 132 75 255 50 2 2 160 83 268 H...

Страница 6: ...6 to OFF for operating actuator in Modulating mode Actuator s stem will run to its totally extended or retracted position by bridging SN signal to terminals 1 or 3 and will remain in this positron as...

Страница 7: ...6 V 5 6 10V SW5 0 2 5 6 V 5 6 10V Bem rk Denne funktion er tilg ngelig hvis kontakt Nr 4 Sekvens er indstillet SW6 Proportional 3 punkt N rDIP6erp Aktuatorskaludf re automatiskekalibreringforudat DIP...

Страница 8: ...HINWEIS Diese Funktion steht zur Verf gung wenn Schalter Nr 4 Sequentiell eingestellt ist SW6 Proportion l 3 Punkt CandDIP6esteONservomotorul trebuiesa sifacacapeteledecursa inaintedeschimbareaDIP6pe...

Страница 9: ...sDIP6esde actuadordeberealizarajuste autom ticodelalongituddecarrera antesdelconmutadorDIP6enlaposici nON Se aldesalidadependedelosinterruptoresDIP 2 3 5Ajuste Actuador puede funcionar en modulante DI...

Страница 10: ...hdistelm toimii yhdess kytkimen nro 5 kanssa 0 2 5 6 V 5 6 10V SW5 0 2 5 6 V 5 6 10V Huom T m toiminto on k ytett viss jos kytkin nro 4 Vaiheittainen on m ritetty SW6 Verrannoll 3 pisteinen JosDIP6onO...

Страница 11: ...galima nustatyti kad jos pagal vien valdymo signal veikt lygiagre iai Jei nustatomas nuoseklusis veikimas SEQUENTIAL pavara reaguoja padalyt valdymo signal 0 2 5 6 V 5 6 10V Pastaba is derinys veikia...

Страница 12: ...dy ustawiony jest prze cznik nr 4 Sequential SW6 Proporcjonalny 3 punktowy Gdyprze cznikDIP6jestNA Si ownikmusiwykonywa samodostrajaniaprzedzmian ustawie prze cznikaDIP6naON W Sygna wyj ciowyzale yodD...

Страница 13: ...V 0 2 V_5 6 V 5 6 V_10 V 3 RL 100 Kvs Red Kvs OFF DIP 6 SW1 U I 0 10 B SW2 2 10B 0 10B 2 10 B SW3 SW4 0 2 5 6 5 6 10 5 0 2 5 6 5 6 10 SW5 0 2 5 6 5 6 10 4 SW6 DIP 6 DIP 2 35 DIP6 6 OFF 3 3 6 SN SP DIP...

Страница 14: ...zgat p rhuzamos m k d sre ll that egy vez rl jellel m k dtetve SZEKVENCI LISRA ll tott helyzetben a szelepmozgat gy reag l hogy felosztja a vez rl jelet l sd a 0 2 5 6 V 5 6 10V V 5 6 6 6 V 10V Megjeg...

Страница 15: ...4mA 0V 0mA 2 10V SW3 SW4 0 2 V 5 6V 5 6 V 10V 5 0 2 V 5 6V 5 6 V 10V SW5 0 2 5 6 V 5 6 10 V 4 SW6 DIP6 DIP6 ON DIP2 3 5 DIP 6 DIP 6 ON SP SN DIP 6 OFF SN 1 3 DIP 6 On 3 ECL caparison Y SW7 SW8 100 KVS...

Страница 16: ...eserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agre...

Отзывы: