Danfoss District Energy
VI.GP.V2.02
DKDHR
Instructions
Akva Lux II VX
Problem
Possible cause
Solution
Declining temperature during tapping
Defective or wrongly set differential
pressure controller (set too low).
(Akva Lux II VX3-E)
Check the functions of the differential
pressure controller - clean valve seat and
capillary tubes if required, - air and rinse
capillary tubes.
Automatic controls wrongly set.
Check that the controller has been cor-
rectly set - see separate instructions.
Calified plate heat exchanger.
Clean plate heat exchanger with acid
solution or replace plate heat exchanger.
Poor cooling
Calified plate heat exchanger.
Clean plate heat exchanger with acid
solution or replace plate heat exchanger.
Discoloured water (for a longer period)
Short-circuiting of plate heat exchanger
Replace plate heat exchanger