Service Guide 

|

 Troubleshooting Guidelines, AK-CC 550A

© Danfoss | ADAP-KOOL® | 2018.08  

2  |    AX278927426184en-000101 

The following troubleshooting guidelines detail the process of 
verifying proper setup of an AK-CC 550A when encountering 
communication/offline issues with an AK-SM 800 series controller.

System Manager Programming

• 

Complete Rescan

- On Network Nodes screen, select ‘Press for complete rescan’

*Also complete rescan if any of the items below required 
adjustment

• 

Ensure proper channel enabled on Network Nodes screen of 
system manager

- ‘Channel LONWORKS’ for LON RS485 comm loop
- ‘Channel MODBUS-RS485’ for Modbus comm loop

• 

Verify no Duplicates in System Manager

- Check under Network Nodes->Duplicates
- If duplicates exist, identify case controller with mistaken 

address, and update

• 

Verify address has been assigned to case controller in 
program

- Verify under Configuration->Control->Refrigeration-
>Addresses

AK-CC 550A Hardware

• 

Verify part # of AK-CC 550A. This will be printed on front of 
controller below display

- For 084B8030, verify 230Vac to terminals 1&2
- For 084B8036, verify 115Vac to terminals 1&2

AK-CC 550A Programming

• 

Ensure address is set correctly, via parameter o03. 

• 

Ensure application is set correctly, via parameter o61.

Comm Loop Wiring

• 

Verify intended form of communication to be used (Modbus 
or LON RS485)

- For Modbus communication:

- Ensure comm wires are landed on terminals 57&58.
- Modbus loop is polarity sensitive, ensure polarity is 

consistent throughout loop

- Ensure any other Modbus devices on the loop use 38400 

baud rate

- For LON RS485 communication:

- Ensure comm wires are landed on terminals 52&53
- Ensure EKA 175 comm card is installed in port below 

display.

- EOL resistor

- For 1 loop from system manager, ensure 120 ohm resistor 

at end of loop and switch above comm plug in ‘On’ 
position

- For 2 loops from system manager, ensure 120 ohm resistor 

at end of each loop and switch above comm plug in ‘Off’ 
position

• 

For either comm type, max distance is 4000’. Beyond this 
distance, a repeater is needed

• 

For either comm type, max # of case controllers is 120 per 
system manager

• 

For either comm type, an EIA 485 rated cable should be used