AK-CC 550

Instructions

AK-CC 550

RI8LN802    02-2012

Identification

S1, S2:

Isoler følerne
Insulate sensors
Fühler isolieren
Capteurs isolés 

 

Sensores aislados

S1 placeres på første rørbøjning af det næstnederste fordamperløb
Place S1 on the first U-bend of the second-lowest evaporator passage
S1 an der ersten Rohrbiegung des zweituntersten Verdampferrohrs anbringen.
Monter S1 sur le premier coude du serpentin de la deuxiéme ligne à partir du bas
Montar S1 en la primera curva en U del serpentín correspondiente a la penúltima  
tubería del distribuidor

084B8020 / 
084B8021

Valg af signal til overhedningsmåling. Tryktransmitter eller temperaturføler S1
Selection of signal to superheat measurement. Pressure transmitter or temperature sensor S1
Wahl des Signal für Überhitzungsmessung. Druckmessumformer oder Temperaturfühler S1
Sélection de signal pour la mesure de surchauffe. Transmetteur de pression ou sonde de température S1

AKV info !!

230 V a.c. spole
230 V a.c. coil
230 V a.c. Spule
230 V c.a. Bobine
230 V c.a. Bobina
230 V c.a. Bobine

Additional information:  English Manual 

RS8EN... www.danfoss.com

Weitere Information: 

Deutsches Manual

Renseignements sup-
plémentarires: 

Manuel en français 

Yderligere information:  Dansk Manual
Información adicional:

Manual español

Informazioni ag-
giuntive!

Manuale in italiano

Ytterligare information: Svenska Handbok
Aanvullende infor-
matie:

Dutch Handleiding

Содержание AK-CC 550

Страница 1: ...l overhedningsm ling Tryktransmitter eller temperaturf ler S1 Selection of signal to superheat measurement Pressure transmitter or temperature sensor S1 Wahl des Signal f r berhitzungsmessung Druckmes...

Страница 2: ...ing application 1 If you employ another use signs are provided so that you can mount the relevant one Werkseitig wird der Regler mit Schildern geliefert die Anwendung 1 angeben Wenn Sie eine andere An...

Страница 3: ...AK CC 550 Instructions RI8LN802 Danfoss 2 2012 3 5 6 7 9 10 8 9 10...

Страница 4: ...cation MODBUS and RS 485 must comply with the requirements for data communication cables See literature RC8AC Wichtig Alle Anschl sse an die Datenkommunikation MODBUS und RS 485 m ssen die Anforderung...

Страница 5: ...which EKA Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data comm...

Страница 6: ...the hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail hea...

Страница 7: ...s and with a setting you can determine whether the temperature is to be shown in C or in F Operation Get a good start With the following procedure you can start regulation very quick ly 1 Open paramet...

Страница 8: ...1 1 1 1 1 0 min 240 min 30 Delay for door alarm A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermos...

Страница 9: ...0 75 30 Injection algorithm Only for trained personnel n17 1 1 1 1 1 1 1 1 1 1 5 70 30 Injection algorithm Only for trained personnel n18 1 1 1 1 1 1 1 1 1 1 0 10 4 Injection algorithm Only for traine...

Страница 10: ...me during day operations o41 1 1 1 1 1 1 1 0 100 100 Rail heat On time during night operations o42 1 1 1 1 1 1 1 0 100 100 Rail heat period time On time Off time o43 1 1 1 1 1 1 1 6 min 60 min 10 Case...

Страница 11: ...1 1 1 1 1 1 Reference of superheat control u22 1 1 1 1 1 1 1 1 1 1 Opening degree of AKV valve u23 1 1 1 1 1 1 1 1 1 1 Evaporating pressure Po relative u25 1 1 1 1 1 1 1 1 1 1 Evaporator temperature...

Страница 12: ...Additional information Manual RS8EN Data communication The importance of individual alarms can be defined with a setting The setting must be carried out in the group Alarm destinations Emergency cooli...