Instructions  RI8LN802  ©  Danfoss  2/2012 

   AK-CC 550

Menu survey

SW = 1.5x

Parameter

EL-diagram page 2 or 3

Min.-value Max.-value

Factory 

setting

Actual 

setting

Function

Code

 1

 2

3

4

 5

 6

7

8

9

10

Normal operation

Temperature (setpoint)       

- - -

1

1

1

1

1

1

1

1

1

1

-50°C

50°C

2

Thermostat

Differential

r01

1

1

1

1

1

1

1

1

1

1

0.1 K

20 K

2

Max. limitation of setpoint setting

r02 

1

1

1

1

1

1

1

1

1

1

-49°C

50°C

50

Min. limitation of setpoint setting

r03 

1

1

1

1

1

1

1

1

1

1

-50°C

49°C

-50

Adjustment of temperature indication

r04

1

1

1

1

1

1

1

1

1

1

-10

10

0

Temperature unit (°C/°F)

r05 

1

1

1

1

1

1

1

1

1

1

0/°C

1/F

0/°C

Correction of the signal from S4

r09 

1

1

1

1

1

1

1

1

1

1

-10 K

10 K

0

Correction of the signal from S3

r10 

1

1

1

1

1

1

1

1

1

1

-10 K

10 K

0

Manual service, stop regulation, start regulation (-1, 0, 1)

r12 

1

1

1

1

1

1

1

1

1

1

-1

1

0

Displacement of reference during night operation

r13

1

1

1

1

1

1

1

1

1

1

-25 K

25 K

0

Define thermostat function
1=ON/OFF, 2=Modulating 

r14

1

1

1

1

1

1

1

1

1

1

1

2

1

Definition and weighting, if applicable, of thermostat sen-
sors - S4% (100%=S4,  0%=S3)

r15

1

1

1

1

1

1

1

1

0 %

100 %

100

Time between melt periods

r16 

1

1

1

1

1

1

1

1

1

1

0 hrs

10 hrs

1

Duration of melt periods

r17

1

1

1

1

1

1

1

1

1

1

0 min.

30 min.

5

Temperature setting for thermostat band 2 

. As differential 

use r01

r21

1

1

1

1

1

1

1

1

1

1

-50°C

50°C

2

Correction of the signal from 

S6

r59

1

1

1

1

1

1

1

1

1

-10 K

10 K

0

Definition and weighting, if applicable, of thermostat sen-
sors 

 when night cover is on.  (100%=S4,  0%=S3)

r61

1

0 %

100 %

100

Heat function
Neutral zone between refrigeration and heat function

r62

1

0 K

50 K

2

Time delay at switch between refrigeration and heat 
function 

r63

1

0 min.

240 min.

0

Alarms

Delay for temperature alarm

A03

1

1

1

1

1

1

1

1

1

1

0 min.

240 min.

30

Delay for door alarm

A04

1

1

1

1

1

1

1

1

1

1

0 min.

240 min.

60

Delay for temperature alarm after defrost

A12

1

1

1

1

1

1

1

1

1

1

0 min.

240 min.

90

High alarm limit for thermostat 1

A13

1

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for thermostat 1

A14 

1

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

High alarm limit for thermostat 2

A20

1

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for thermostat 2

A21

1

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

High alarm limit for sensor S6 at thermostat 1

A22

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for sensor S6 at thermostat 1

A23

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

High alarm limit for sensor S6 at thermostat 2

A24

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for sensor S6 at thermostat 2

A25

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

S6 alarm time delay
With setting = 240 the S6 alarm will be omitted

A26

1

1

1

1

1

1

1

1

1

0 min.

240 min.

240

Alarm time delay or signal on the DI1 input

A27

1

1

1

1

1

1

1

1

1

1

0 min.

240 min.

30

Alarm time delay or signal on the DI2 input

A28

1

1

1

1

1

1

1

1

1

1

0 min.

240 min.

30

Signal for alarm thermostat. S4% (100%=S4, 0%=S3)

A36

1

1

1

1

1

1

1

1

0 %

100 %

100

Delay for S6 (product sensor alarm) after defrost

A52

1

1

1

1

1

1

1

1

1

0 min.

240 min.

90

Compressor

Min. ON-time

c01

1

1

1

1

0 min.

30 min.

0

Min. OFF-time

c02

1

1

1

1

0 min.

30 min.

0

Time delay for cutin of comp.2

c05

1

0 sec

999 sec

5

Defrost

Defrost method

: 0=none, 1= EL,  2= Gas

d01

1

1

1

1

1

1

1

1

1

1

0/No

2/GAs

1/EL

Defrost stop temperature

d02

1

1

1

1

1

1

1

1

1

1

0°C

50°C

6

Interval between defrost starts

d03

1

1

1

1

1

1

1

1

1

1

0 hrs/Off

48 hrs

8

Max. defrost duration

d04

1

1

1

1

1

1

1

1

1

1

0 min.

360 min.

45

Displacement of time on cutin of defrost at start-up

d05

1

1

1

1

1

1

1

1

1

1

0 min.

240 min.

0

Drip off time

d06

1

1

1

1

1

1

1

1

1

1

0 min.

60 min.

0

Delay for fan start after defrost

d07

1

1

1

1

1

1

1

1

1

1

0 min.

60 min.

0

Fan start temperature

d08

1

1

1

1

1

1

1

1

1

1

-50 °C

0 °C

-5

Содержание AK-CC 550

Страница 1: ...l overhedningsm ling Tryktransmitter eller temperaturf ler S1 Selection of signal to superheat measurement Pressure transmitter or temperature sensor S1 Wahl des Signal f r berhitzungsmessung Druckmes...

Страница 2: ...ing application 1 If you employ another use signs are provided so that you can mount the relevant one Werkseitig wird der Regler mit Schildern geliefert die Anwendung 1 angeben Wenn Sie eine andere An...

Страница 3: ...AK CC 550 Instructions RI8LN802 Danfoss 2 2012 3 5 6 7 9 10 8 9 10...

Страница 4: ...cation MODBUS and RS 485 must comply with the requirements for data communication cables See literature RC8AC Wichtig Alle Anschl sse an die Datenkommunikation MODBUS und RS 485 m ssen die Anforderung...

Страница 5: ...which EKA Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data comm...

Страница 6: ...the hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail hea...

Страница 7: ...s and with a setting you can determine whether the temperature is to be shown in C or in F Operation Get a good start With the following procedure you can start regulation very quick ly 1 Open paramet...

Страница 8: ...1 1 1 1 1 0 min 240 min 30 Delay for door alarm A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermos...

Страница 9: ...0 75 30 Injection algorithm Only for trained personnel n17 1 1 1 1 1 1 1 1 1 1 5 70 30 Injection algorithm Only for trained personnel n18 1 1 1 1 1 1 1 1 1 1 0 10 4 Injection algorithm Only for traine...

Страница 10: ...me during day operations o41 1 1 1 1 1 1 1 0 100 100 Rail heat On time during night operations o42 1 1 1 1 1 1 1 0 100 100 Rail heat period time On time Off time o43 1 1 1 1 1 1 1 6 min 60 min 10 Case...

Страница 11: ...1 1 1 1 1 1 Reference of superheat control u22 1 1 1 1 1 1 1 1 1 1 Opening degree of AKV valve u23 1 1 1 1 1 1 1 1 1 1 Evaporating pressure Po relative u25 1 1 1 1 1 1 1 1 1 1 Evaporator temperature...

Страница 12: ...Additional information Manual RS8EN Data communication The importance of individual alarms can be defined with a setting The setting must be carried out in the group Alarm destinations Emergency cooli...

Отзывы: