Instructions  RI8LN802  ©  Danfoss  2/2012 

   AK-CC 550

Coordinated defrost via 
data communication

Coordinated defrost via 
cable connections

The following controllers can be connected 
up in this way:
EKC 204A, AK-CC 210, AK-CC 250, 
AK-CC 450, AK-CC 550,

Refrigeration is resumed when all 
controllers have “released” the signal for 
defrost.

The setting of controllers to coordinate 
their defrosting takes place in the 
gateway/system manager.

Refrigeration is resumed when all 
controllers have “released” the signal for 
defrost.

DO1

Connection of expansion valve type AKV or AKVA. The coil must 
be a 230 V a.c. coil.

DO2

Alarm

There is a connection between terminal 7 and 8 in alarm 
situations and when the controller is without power.

Rail heat and heating element in drip tray

There is connection between terminal 7 and 9 when heating 
takes place.

Night blind

There is connection between terminal 7 and 9 when the night 
blind is up.

Suction line valve

There is connection between terminal 7 and 9 when the 
suction line must be open.

DO3

Refrigeration, Rail heat, Heat function, Defrost 2

There is connection between terminal 10 and 11 when the 
function must be active.

Heating element in drip tray

There is connection between terminal 10 and 11 when heating 
takes place.

DO4

Defrost

There is connection between terminal 12 and 14 when 
defrosting takes place.

Hot gas / drain valve

There is connection between terminal 13 and 14 during normal 
operation.  
There is connection between terminal 12 and 14 when the hot 
gas valves must open.

DO5

Fan

There is connection between terminal 15 and 16 when the fan 
is on.

DO6

Light relay

There is connection between terminal 17 and 18 when the 
light must be on.

Rail heat, Compressor 2

There is connection between terminal 17 and 19 when the 
function must be active.

DI3

Digital input signal.  
The signal must have a voltage of 0 / 230 V AC. 
The function is defined in o84. 

Data communication

If data communication is used, it is important that the installation 
of the data communication cable is performed correctly.
See separate literature No. RC8AC…

Electric noise

Cables for sensors, DI inputs and data communication 

must

 be 

kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided

Installation considerations

Accidental damage, poor installation, or site conditions, can give 
rise to malfunctions of the control system, and ultimately lead to a 
plant breakdown.
Every possible safeguard is incorporated into our products to 
prevent this. However, a wrong installation, for example, could still 
present problems. Electronic controls are no substitute for normal, 
good engineering practice.
Danfoss will not be responsible for any goods, or plant compo-
nents, damaged as a result of the above defects. It is the installer's 
responsibility to check the installation thoroughly, and to fit the 
necessary safety devices.
Special reference is made to the necessity of signals to the 
controller when the compressor is stopped and to the need of 
liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further 
advice, etc.
 

Max. 10

Содержание AK-CC 550

Страница 1: ...l overhedningsm ling Tryktransmitter eller temperaturf ler S1 Selection of signal to superheat measurement Pressure transmitter or temperature sensor S1 Wahl des Signal f r berhitzungsmessung Druckmes...

Страница 2: ...ing application 1 If you employ another use signs are provided so that you can mount the relevant one Werkseitig wird der Regler mit Schildern geliefert die Anwendung 1 angeben Wenn Sie eine andere An...

Страница 3: ...AK CC 550 Instructions RI8LN802 Danfoss 2 2012 3 5 6 7 9 10 8 9 10...

Страница 4: ...cation MODBUS and RS 485 must comply with the requirements for data communication cables See literature RC8AC Wichtig Alle Anschl sse an die Datenkommunikation MODBUS und RS 485 m ssen die Anforderung...

Страница 5: ...which EKA Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data comm...

Страница 6: ...the hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail hea...

Страница 7: ...s and with a setting you can determine whether the temperature is to be shown in C or in F Operation Get a good start With the following procedure you can start regulation very quick ly 1 Open paramet...

Страница 8: ...1 1 1 1 1 0 min 240 min 30 Delay for door alarm A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermos...

Страница 9: ...0 75 30 Injection algorithm Only for trained personnel n17 1 1 1 1 1 1 1 1 1 1 5 70 30 Injection algorithm Only for trained personnel n18 1 1 1 1 1 1 1 1 1 1 0 10 4 Injection algorithm Only for traine...

Страница 10: ...me during day operations o41 1 1 1 1 1 1 1 0 100 100 Rail heat On time during night operations o42 1 1 1 1 1 1 1 0 100 100 Rail heat period time On time Off time o43 1 1 1 1 1 1 1 6 min 60 min 10 Case...

Страница 11: ...1 1 1 1 1 1 Reference of superheat control u22 1 1 1 1 1 1 1 1 1 1 Opening degree of AKV valve u23 1 1 1 1 1 1 1 1 1 1 Evaporating pressure Po relative u25 1 1 1 1 1 1 1 1 1 1 Evaporator temperature...

Страница 12: ...Additional information Manual RS8EN Data communication The importance of individual alarms can be defined with a setting The setting must be carried out in the group Alarm destinations Emergency cooli...

Отзывы: