Instructions  RI8LN802  ©  Danfoss  2/2012 

   AK-CC 550

Fault message

In an error situation the LED’s on the front will flash and the alarm relay will be 
activated. If you push the top button in this situation you can see the alarm 
report in the display.
There are two kinds of error reports - it can either be an alarm occurring dur-
ing the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired. 
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:

Code / Alarm text via 
data communication

Description

Alarm 
relay 
groups 
(P41)

A1/---  High t.alarm

High temperature alarm

1

A2/---  Low t. alarm

Low temperature alarm

2

A4/--- Door alarm

Door alarm

8

A5/--- Max hold time

The ”o16” function is activated during a 
coordinated defrost

16

A10/--- Inject prob.

Control problem

64

A11/--- No Rfg. sel.

No refrigerant selected

64

A13/--- High temp S6

Temperature alarm. High S6

1

A14/--- Low temp S6

Temperature alarm. Low S6

2

A15/--- DI1 alarm

DI1 alarm

8

A16/--- DI2 alarm

DI2 alarm

8

A45/--- Standby mode

Standby position (stopped refrigera-
tion via r12 or DI input)

-

A59/--- Case clean

Case cleaning. Signal from DI input

-

A74/--- AD fault

Error in the adaptive defrost function

16

A75/--- AD Iced

Evaporator is iced up. Reduction of 
air flow

16

A76/--- AD not defr.

Defrost of evaporator is not 
satisfactory

16

E1/---  Ctrl. error

Faults in the controller

32

E6/--- RTC error

Check clock

32

E20/--- Pe error

Error on pressure transmitter Pe

64

E23/--- S1 error

Error on S1 sensor

4

E24/--- S2 error

Error on S2 sensor

4

E25/--- S3 error

Error on S3 sensor

4

E26/--- S4 error

Error on S4 sensor

4

E27/--- S5 error

Error on S5 sensor

4

E28/--- S6 error

Error on S6 sensor

4

E37/--- S5 error B

Error on S5B sensor

4

---/--- Max Def.Time

Defrost stopped based on time instead 
of, as wanted, on temperature

16

Settings from 
System manager

Settings from 
AKM (AKM destination)

Log

Alarm relay

Send via
Network

Non

High

Low-High

High

1

X

X

X

X

Middle

2

X

X

X

Low

3

X

X

X

Log only

X

Disabled

Additional information:
Manual RS8EN

Data communication

The importance of individual alarms can be defined with a setting. The setting 
must be carried out in the group "Alarm destinations"

*) Emergency cooling will take effect when there is lack of signal from a defined 

S3 or S4 sensor. The regulation will continue with a registered average cutin 
frequency. There are two registered values – one for day operation and one for 
night operation.

Operating status

(Measurement)

The controller goes through some regulating situa-
tions where it is just waiting for the next point of the 
regulation. To make these “why is nothing happening” 
situations visible, you can see an operating status on 
the display. Push briefly (1s) the upper button. If there is 
a status code, it will be shown on the display. The indi-
vidual status codes have the following meanings:

Ctrl. state:
(Shown in all 
menu displays)

Normal regulation

S0

0

Waiting for end of the coordinated defrost

S1

1

When the compressor is operating it must run for at least 
x minutes.

S2

2

When the compressor is stopped, it must remain stopped 
for at least x minutes.

S3

3

The evaporator drips off and waits for the time to run out S4

4

Refrigeration stopped by main switch. Either with r12 or 
a DI-input

S10

10

Refrigeration stopped by thermostat

S11

11

Defrost sequence. Defrost in progress

S14

14

Defrost sequence. Fan delay — water attaches to the 
evaporator

S15

15

Refrigeration stopped due to open ON input or stopped 
regulation

S16

16

Door is open. DI input is open

S17

17

Melt function in progress. Refrigeration is interrupted

S18

18

Modulating thermostat control

S19

19

Emergency cooling due to sensor error

S20

20

Regulation problem in the injections function

S21

21

Start-up phase 2. Evaporator being charged

S22

22

Adaptive control

S23

23

Start-up phase 1. Signal reliability from sensors is 
controlled

S24

24

Manual control of outputs

S25

25

No refrigerant selected

S26

26

Case cleaning

S29

29

Forced cooling

S30

30

Delay on outputs during start-up

S32

32

Heat function r36 is active

S33

33

Other displays:

The defrost temperature cannot be displayed. There is 
stop based on time

non

Defrost in progress / First cooling after defrost

-d-

Password required.  Set password 

PS

Regulation is stopped  via main switch

OFF

DE-DB

Содержание AK-CC 550

Страница 1: ...l overhedningsm ling Tryktransmitter eller temperaturf ler S1 Selection of signal to superheat measurement Pressure transmitter or temperature sensor S1 Wahl des Signal f r berhitzungsmessung Druckmes...

Страница 2: ...ing application 1 If you employ another use signs are provided so that you can mount the relevant one Werkseitig wird der Regler mit Schildern geliefert die Anwendung 1 angeben Wenn Sie eine andere An...

Страница 3: ...AK CC 550 Instructions RI8LN802 Danfoss 2 2012 3 5 6 7 9 10 8 9 10...

Страница 4: ...cation MODBUS and RS 485 must comply with the requirements for data communication cables See literature RC8AC Wichtig Alle Anschl sse an die Datenkommunikation MODBUS und RS 485 m ssen die Anforderung...

Страница 5: ...which EKA Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data comm...

Страница 6: ...the hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail hea...

Страница 7: ...s and with a setting you can determine whether the temperature is to be shown in C or in F Operation Get a good start With the following procedure you can start regulation very quick ly 1 Open paramet...

Страница 8: ...1 1 1 1 1 0 min 240 min 30 Delay for door alarm A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermos...

Страница 9: ...0 75 30 Injection algorithm Only for trained personnel n17 1 1 1 1 1 1 1 1 1 1 5 70 30 Injection algorithm Only for trained personnel n18 1 1 1 1 1 1 1 1 1 1 0 10 4 Injection algorithm Only for traine...

Страница 10: ...me during day operations o41 1 1 1 1 1 1 1 0 100 100 Rail heat On time during night operations o42 1 1 1 1 1 1 1 0 100 100 Rail heat period time On time Off time o43 1 1 1 1 1 1 1 6 min 60 min 10 Case...

Страница 11: ...1 1 1 1 1 1 Reference of superheat control u22 1 1 1 1 1 1 1 1 1 1 Opening degree of AKV valve u23 1 1 1 1 1 1 1 1 1 1 Evaporating pressure Po relative u25 1 1 1 1 1 1 1 1 1 1 Evaporator temperature...

Страница 12: ...Additional information Manual RS8EN Data communication The importance of individual alarms can be defined with a setting The setting must be carried out in the group Alarm destinations Emergency cooli...

Отзывы: