AK-PC 781
Separate thermostats
1. Select thermostats
2. Select actual thermostat
3. Define the required thermostat
functions
Configuration - continued
In our example we select
one thermostat function for
monitoring the plant room
temperature.
We have subsequently entered a
name for the function.
In our example, separate
pressostat functions are not used.
3 - Thermostats
The general thermostats can be used to monitor the tem-
perature sensors that are used, as well as 4 extra temperature
sensors. Each thermostat has a separate outlet to control
external automation.
For each thermostat adjust
• Name
• Which of the sensors is used
Actual temp
.
Temperature measurement on the sensor that is attached to
the thermostat
Actual state
Actual status on the thermostat outlet
Cut out temp.
Cut-out value for the thermostat
Cut in temp.
Cut-in value for the thermostat
High alarm limit
High alarm limit
Alarm delay high
Time delay for high alarm
Alarm text high
Indicate alarm text for the high alarm
Low alarm limit
Low alarm limit
Alarm delay low
Time delay for low alarm
Alarm text low
Indicate alarm text for low alarm
3 - Pressostats
Settings as the thermostats
Separate pressostats
1. Select pressostats
2. Select actual pressostat
3. Define the required pressostat
functions
Содержание ADAP-KOOL AK-PC 781