AK-PC 781
Capacity
controller RS8GG602 © Danfoss 2015-03
57
Set plant type
1. Go to Configuration menu
2. Select plant type
Press the line
Select plant type
.
3. Set plant type
4. Set Common functions
Press the
+
-button to go on to the
next page
6. Quick basis setup
Configuration - continued
In our example we want the control-
ler to control both a compressor
group and a condenser group. We
therefore select the plant type
One
pack
.
Subsequent options are then available,
but only those options allowed by the
current selection.
Select the refrigerant type, here CO2,
further options are made available, etc.
In our example, the cooling (MT) is
regulated..
(If it was a cascade control/two step
system, the other controller would need
to be set to "LP".)
The settings for our example can be viewed
in the display.
This setting is special.
Here the user can select a pre-defined
system. We do not use this function in our
example, but perform the adjustments
individually.
Adjust only the two lines with "Smart"
(Only when the refrigerant selected is CO2)
Here you can adjust the overall pressure
values for the system
- Regulation Pgc max
- Regulation Receiver reference.
The controller will then suggest values for all
settings connected with this.
The values can be seen in this display, but
also later in the relevant setup.
Fine adjustments can be made if necessary.
3 - Plant type
Application selection
Select between "One Suction", "One condens-
er" or both "One Pack"
4- Plant type continued
Refrigerant
Select refrigerant type
Refrigerant factors K1, K2, K3
Only used if “Po refrigerant type” is set to custom
(contact Danfoss for information)
Pack type
MT = Medium temperature. LT = Low tempera-
ture
HP control
High pressure control enabled. To be adjusted
later on.
Receiver control
Receiver control enabled. To be adjusted later
on.
IT Compressor
Parallel compressor (there are special settings;
see the section on page 122).
Heat recovery
Heat recovery enabled. To be adjusted later on.
Oil management
Oil control enabled. To be adjusted later on.
Quick setup
A choice will give a number of predefined com-
binations, which at the same time determine
the connection points. The display options
depend on previous settings.
At the end of the manual there is an overview
of the options and connection points.
After configuration of this function, the
controller will shut down and restart. After the
restart, a large number of settings will have
been made. These include the connection
points. Continue with the settings and check
the values.
If you change some of the settings, the new
values will come into force.
External main switch
A switch may be connected for starting and
stopping the regulation.
Mon. Ext. Power loss
(signal from an UPS)
Monitoring of external voltage. When selecting
"yes", a digital input is allocated.
Alarm output
Here you may set whether or not it should be
an alarm relay, and which priorities will activate
it.
I'm alive relay
A relay will "release" if the regulation is stop-
ped.
Show Tc
If selecting "yes" the Pc pressure will also be
shown as temperature.
Comp. cap. out to AO
If selecting "yes" indicate the current capacity
of an output.
Comp. run signal DO
If “yes” is selected, an output is reserved that
shows if the compressors are operating.
5 – Quick relative setup
Smart = Setting the controller’s overall pressure
values. The remaining pressure values will be
set automatically.
General
If you want to know more about the different
configuration options, they are listed in the right
column.
The number refers to the number and picture in
the column on the left.
As the screen only shows the settings and readings
that are required for a given setup, all possible set-
tings have also been included in the right column.
Our example
The comments for the example are shown on the
following pages, in the middle column.
Содержание ADAP-KOOL AK-PC 781
Страница 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Страница 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Страница 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Страница 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...