40
Capacity
controller RS8GG602 © Danfoss 2015-03
AK-PC 781
11
Signal
Module
Point
Terminal
Active at
Compressor 1 Gen. Safety
4
1
(DI 1)
1 - 2
Open
Compressor 2 Gen. Safety
2
(DI 2)
3 - 4
Open
Compressor 3 Gen. Safety
3
(DI 3)
5 - 6
Open
Compressor 4 Gen. Safety
4
(DI 4)
7 - 8
Open
Start/stop heat recovery hr
5
(DI 5)
9 - 10
Closed
All compressors common safety
6
(DI 6)
11 - 12
Open
Flow switch FStw
7
(DI 7)
13 - 14
Open
Flow switch FShr
8
(DI 8)
15 - 16
Open
Signal
Module
Point
Terminal
Signal type
Temp. gas cooler outlet Sgc
5
1
(AI 1)
1 - 2
Pt 1000
Temp. by-pased gas Shp
2
(AI 2)
3 - 4
Pt 1000
Start/stop heat recovery tw
3
(AI 3)
5 - 6
Closed
Gas cooler pressure Pgc
4
(AI 4)
7 - 8
AKS 2050-159
Speed control, compressor
5
(AO 1)
9 - 10
0 - 10 V
Speed control, gas cooler fan
6
(AO 2)
11 - 12
0 - 10 V
Speed control, pump - tw
7
(AO 3)
13 - 14
0 - 10 V
Speed control, pump - hr
8
(AO 4)
15 - 16
0 - 10 V
Connection diagram
Drawings of the individual modules may be
ordered from Danfoss.
Format = dwg and dxf.
You may then yourself write the module
number in the circle and draw the individual
connections.
The supply voltage for the pressure
transmitter should be taken from
the same module that receives the
pressure signal.
Содержание ADAP-KOOL AK-PC 781
Страница 31: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 31 ...
Страница 41: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 41 Example continued ...
Страница 44: ...44 Capacity controller RS8GG602 Danfoss 2015 03 AK PC 781 ...
Страница 135: ...AK PC 781 Capacity controller RS8GG602 Danfoss 2015 03 135 ...