Danfoss ADAP-KOOL AK-PC 651 Скачать руководство пользователя страница 9

User Guide 

|

 Capacity Controller, AK-PC 651

RS8HA102 | 9

© Danfoss | ADAP-KOOL® | 2015.10  

Control status

Read the status of the control circuit here e.g.:

• No comp. - No compressor capacity available

• Normal ctrl - Normal control

• Alarm Comp. - Cannot start compressor due to alarm condition

• ON timer - Cannot stop compressor due to ON timer restriction

• Start timer - Cannot start compressor due to Start timer restriction

• Inj. On Delay - Waiting for injection on delay to expire

• 1st comp del - First compressor run timer

• Pump down - Last compressor running to pump down limit

• Sensor error - Emergency control due to sensor error

• Load shed - Load shedding function active

• Sd High - Capacity control in High Sd safety prevention mode

• Pc High - Capacity control in High Pc safety prevention mode

• Manual ctrl - Capacity control in manual mode

• Main switch OFF - OFF

Actuel zone

You will be able to see how the regulation is in relation to the reference here:

 P0 error: No regulation

- Zone: The desired pressure is below the reference value

NZ: The pressure is in place in relation to the reference value

+ Zone: The desired pressure is above the reference value

Control temp.

The current value of the regulation sensor can be read here

Reference

The total regulation reference can be read here

Running capacity

Here the connected capacity can be read as a % of total capacity

Requested capacity

Here the preferred connected capacity can be read as a % of total capacity

No. of running comp.

The number of compressors in operation can be read here

Po Pressure

The measured pressure for the Po pressure transmitter can be read here 

To Saturated temp.

The measured Po pressure converted to temperature can be read here 

S4 media temp

The measured media temperature  can be read here (only if S4 is set as regulation sensor)

MC Po offset

The size of a reference displacement on Po required from the system unit  

(suction pressure optimisation function) can be read here

Pc Pressure

The measured pressure for pressure transmitter Pc can be read here

Tc Saturated temp.

The measured Pc pressure converted to temperature can be read here

Sd disch temp.

The measured discharge temperature can be read here

Ss suction temp

The measured suction gas temperature can be read here

Superheat

The measured superheat can be read here

Day / Night status

The status of the day/night function can be read here

Load shed

The status of the load shed function can be read here

LP pressostat

The measured signal from the safety circuit can be read here

HP pressostat

The measured signal from the safety circuit can be read here

Injection ON A

The status of the injection ON signal sent to the evaporator controllers can be read here

MC Load Shedding

The status of the load shed signal received from the system device can be read here

MC Night Setback

The status of the night increase signal received from the system device can be read here

Control settings

Regulation settings

Control mode

Regulation type

The regulation is normally set to “Auto”, but it can be changed to “Off” or “Manual”. 

When setting to “Manual”, a forced capacity setting can subsequently be entered in %. 

MAN / OFF / AUTO

Fac: AUTO

Min: 0 %

Max: 100%

Setpoint

Enter the set point for the regulation (regulation reference = set point + different offsets) here

An offset can originate from a night increase signal or from an override function on the 

system device.

Min: -80°C (-1.0 bar)

Max: 30°C (50 bar)

Fac: -15°C (3.5 bar)

Neutral zone

Set the neutral zone around the reference here. Also see the illustration on page 3. 

Min: 0,1 K (0.1 bar)

Max: 20 K (5.0 bar)

Fac: 6 K (0.4 bar)

Night offset

If necessary, set the value by which the reference will be raised at night. 

Keep the setting at 0 if regulating with Po optimisation from a system device.

Min: -25 K (-5.0 bar)

Max: 25 K (5.0 bar)

Fac: 0 K (0.0 bar)

Max Reference

Set the highest permissible regulation reference here

Min: -50°C (-1.0 bar)

Max: 80°C (50.0 bar)

Fac: 80°C (40.0 bar)

Min Reference

Set the lowest permissible regulation reference here

Min: -80°C (-1.0 bar)

Max: 25°C (40.0 bar)

Fac: -80°C (-1.0 bar)

PI control selection

Set how quickly the PI regulation must react here: 1 = slowly, 10 = very quickly.

(For “Custom” setting 0, the special settings options will open, i.e. Kp, Tn and time settings 

around the neutral zone. These options are only for trained staff.)

Min: 0 (custom)

Max: 10

Fac: 5

Gain factor Kp

The amplification factor, Kp (can only be seen and set when the previous menu is set to “0”)

Integration time Tn

Integration time Tn (see above)

+ Zone rate of change Change coefficient for + zone (see above)
- Zone rate of change Change coefficient for - zone (see above)

Содержание ADAP-KOOL AK-PC 651

Страница 1: ...Capacity controller AK PC 651 User Guide ADAP KOOL Refrigeration Control System...

Страница 2: ...matic safety control day night signal etc Relay outputs max 13 pcs Connection of compressors condenser fans Solid state outputs max 2 pcs Control of capacity valve on a Copeland digital scroll Control...

Страница 3: ...one the control ler will cut out or cut in the next compressor in the sequence When further capacity is either cut out or cut in the capacity from the regulating compressor will be modified accordingl...

Страница 4: ...of the following functions Fixed reference Variable reference which follows the outdoor temperature When the outdoor temperature drops the reference will drop by a corresponding amount This variable...

Страница 5: ...scroll a Copeland stream or Bitzer CRII the capacity will be increased so that the compressor can cool down itself The compressors will be stopped if the temperature reaches the set max temperature va...

Страница 6: ...n groups and 1 condenser group Each of the 3 rows above is continued with three additional displays The arrow in the top corner of the display shows the way to the next display in the same area of ope...

Страница 7: ...y None Main Menu The first setting is the Plant type When the Plant type has been selected it will al low several settings to be made For example Continue to the next menus All settings are explained...

Страница 8: ...s Device for configuration of compressor and condenser Select pressure or saturation temperature Can be set during initial set up and must not be subsequently changed Temp press Fac Saturated Night si...

Страница 9: ...suction gas temperature can be read here Superheat The measured superheat can be read here Day Night status The status of the day night function can be read here Load shed The status of the load shed...

Страница 10: ...0 s Fac 120 s Configuration Configuration Control sensor Select the regulating sensor for the suction circuit Pressure transmitter Po Media temperature sensor S4 brine regulation Po is used for safety...

Страница 11: ...ed AI demand Yes No Fac No Ss suction superheat Monitoring of superheat Define whether a signal from a common Ss sensor on the suction line should be received AI demand Yes No Fac No Injection ON fct...

Страница 12: ...Compressor service Compressor service Comp 1 out of service The compressor can be taken out of operation so that the controller regulates without this compressor No Normal regulation Yes Regulating i...

Страница 13: ...uency converter Step on off control of fans will be via relays Variable step The signals are parallel so external wiring can switch over to step e g if the frequency converter fails AO demand Step Spe...

Страница 14: ...is measured in the suction line by Po and Ss Min 0 K Max 20 K Fac 0 K Superheat Max lim Alarm limit for excess superheating Min 20 K Max 80 K Fac 80 K Superheat delay Delay time before alarm is gener...

Страница 15: ...t Set the output to thermostat AI demand Yes No Fac No Thermostat cut in Here set the temperature value at which the thermostat will cut in Min 50 C Max 150 C Fac 5 C Thermostat cut out Here set the t...

Страница 16: ...ation value 10 C Pressure sensors Signal type 0 20mA 4 20mA AKS32 1 5V or AKS32R 10 90 ratiometric of 5 V supply voltage Important Current types must be connected to inputs Al 1 6 Current types must b...

Страница 17: ...ction is on or off Digital inputs 1 18 Status of on off inputs Here you can see the status of the function alarm Analoge outputs 1 4 Status of analogue outputs Here you can see the size of the output...

Страница 18: ...on the next page App no Display Suction group Condenser Speed Digital Scroll Stream CRII 1 step with unloa der Step Speed 17 3C2U FS 3 x 16 2C2U 6F 2 6 15 4C1U FS 4 x 14 3C1U 6F 3 6 13 2C1U 4F 2 4 12...

Страница 19: ...gle 8C FS 8 speed C1 C2 C3 C4 C5 C6 C7 C8 Fan VSD Alarm F speed 3 Single 6C FS 6 speed C1 C2 C3 C4 C5 C6 Fan VSD Alarm F speed 2 Single 6C 6F 6 6 C1 C2 C3 C4 C5 C6 Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan 6...

Страница 20: ...6 Compressor start and unloaders Fans Injection ON Alarm on DO15 Digital inputs DI1 DI18 Compressor safety inputs Fan safety input External main switch start stop HP safety switch LP safety switch Nig...

Страница 21: ...condensing pressure Pc has been violated 3K below safety limit High pressure Pc Critical HP safety switch cutout High safety limit for external high pressure switch has been violated DI input HP switc...

Страница 22: ...oid earth fault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals N and AO1 respectively N and AO2 PAY ATTENTION TO THE POLARITY of N Mod...

Страница 23: ...riod times as PWM per 100 capacity is delivered when cooling takes place for the whole period An off time is required by the bypass valve within the period and an on time is also permitted There is no...

Страница 24: ...remaining 50 100 for the unloader The unloader is connected to DO5 or DO6 Stream 6 The compressor capacity is distributed by up to 33 for one relay and the remaining 33 100 for the unloader The unload...

Страница 25: ...ed Display output For type MMIGRS2 Data communication Modbus for AK SM 800 Environments 20 60 C During operations 40 70 C During transport 20 80 Rh not condensed No shock influence vibrations Enclosur...

Страница 26: ...amage poor installation or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to pr...

Отзывы: