Safety functions

Min./max. suction pressure Po

The suction pressure is recorded continuously. 

If the measured value falls below the set minimum limit,  the 

compressors will immediately cut out.

If it exceeds the max. value, an alarm will be generated once  

the time delay has elapsed.

Max. condensing pressure Pc

If the condensing pressure reaches the upper permissible value 

(3 K below limit), the controller will connect all condenser fans 

to keep the pressure down. At the same time, a portion of 

the compressor capacity will be disconnected. If the pressure 

remains near the threshold value, even more compressors will be 

disconnected.

All compressors will be disconnected immediately if the threshold 

value is exceeded.

LP switch

On/off signal on a DI input

If a signal is received, all compressors will immediately be stopped.

HP switch

On/off signal on a DI input

If a signal is received, all compressors will immediately be stopped. 

Fan capacity will increase depending on how much the  

Pc measurement exceeds the reference.

Min./max superheating via Ss measurement

Temperature sensor on an AI input.

If superheating is higher or lower than the set limits, an alarm will 

be generated once the time delay has elapsed.

Max. discharge gas temperature Sd

Temperature sensor on an AI input.

A signal can be received from a Pt 1000 Ohm sensor on the 

pressure pipe.

• Common Sd for the whole compressor group

If the temperature nears the set max. temperature, the capacity 

of the compressor will be reduced

• Compressor Sd

if it is an Sd from a Copeland digital scroll, a Copeland stream or 

Bitzer CRII the capacity will be increased so that the compressor 

can cool down itself).

The compressors will be stopped if the temperature reaches the 

set max. temperature value. 

Sensor failure

If lack of signal from one of the connected temperature sensors or

pressure transmitters is registered an alarm will be given. 

• In the event of a Po error, regulation will continue with a set 

capacity in daytime operation (e.g. 50%), and a set capacity in 

night operation (e.g. 25%), but with a minimum of one step. 

• In the event of a Pc error, the condenser capacity that  

corresponds to how much compressor capacity is connected 

will cut in. Compressor regulation will remain normal.

• When there is an error on the Sd sensor the safety monitoring of 

the discharge gas temperature will be discontinued.

• When there is an error on the Ss sensor the monitoring of the 

superheat on the suction line will be discontinued.

• In the event of an error on the outdoor temperature sensor,  

Sc3, the permanent setting value will be used as a reference.

• In the event of an error on the S4 sensor, regulation will continue 

with the Po signal, but the reference will be lowered by 5 K.

• In the event of an error on the Saux sensor, the thermostat  

output will go to the rest position. 

NB: A faulty sensor must be OK within 10 minutes before a sensor 

alarm is cancelled.

A sensor alarm can be reset manually by pushing  the 

"X-button" for 2 seconds when the alarm is shown in the display 

"Active alarms".

General DI alarms

On/off signal on a DI input

The regulator contains three general alarm inputs, to which alarm 

text and delay times can be connected. 

Alarm and text will appear when the delay time has elapsed. 

General thermostat

It is possible to install one general thermostat if there is a relay 

output and an analogue input available.

Содержание ADAP-KOOL AK-PC 651

Страница 1: ...Capacity controller AK PC 651 User Guide ADAP KOOL Refrigeration Control System...

Страница 2: ...matic safety control day night signal etc Relay outputs max 13 pcs Connection of compressors condenser fans Solid state outputs max 2 pcs Control of capacity valve on a Copeland digital scroll Control...

Страница 3: ...one the control ler will cut out or cut in the next compressor in the sequence When further capacity is either cut out or cut in the capacity from the regulating compressor will be modified accordingl...

Страница 4: ...of the following functions Fixed reference Variable reference which follows the outdoor temperature When the outdoor temperature drops the reference will drop by a corresponding amount This variable...

Страница 5: ...scroll a Copeland stream or Bitzer CRII the capacity will be increased so that the compressor can cool down itself The compressors will be stopped if the temperature reaches the set max temperature va...

Страница 6: ...n groups and 1 condenser group Each of the 3 rows above is continued with three additional displays The arrow in the top corner of the display shows the way to the next display in the same area of ope...

Страница 7: ...y None Main Menu The first setting is the Plant type When the Plant type has been selected it will al low several settings to be made For example Continue to the next menus All settings are explained...

Страница 8: ...s Device for configuration of compressor and condenser Select pressure or saturation temperature Can be set during initial set up and must not be subsequently changed Temp press Fac Saturated Night si...

Страница 9: ...suction gas temperature can be read here Superheat The measured superheat can be read here Day Night status The status of the day night function can be read here Load shed The status of the load shed...

Страница 10: ...0 s Fac 120 s Configuration Configuration Control sensor Select the regulating sensor for the suction circuit Pressure transmitter Po Media temperature sensor S4 brine regulation Po is used for safety...

Страница 11: ...ed AI demand Yes No Fac No Ss suction superheat Monitoring of superheat Define whether a signal from a common Ss sensor on the suction line should be received AI demand Yes No Fac No Injection ON fct...

Страница 12: ...Compressor service Compressor service Comp 1 out of service The compressor can be taken out of operation so that the controller regulates without this compressor No Normal regulation Yes Regulating i...

Страница 13: ...uency converter Step on off control of fans will be via relays Variable step The signals are parallel so external wiring can switch over to step e g if the frequency converter fails AO demand Step Spe...

Страница 14: ...is measured in the suction line by Po and Ss Min 0 K Max 20 K Fac 0 K Superheat Max lim Alarm limit for excess superheating Min 20 K Max 80 K Fac 80 K Superheat delay Delay time before alarm is gener...

Страница 15: ...t Set the output to thermostat AI demand Yes No Fac No Thermostat cut in Here set the temperature value at which the thermostat will cut in Min 50 C Max 150 C Fac 5 C Thermostat cut out Here set the t...

Страница 16: ...ation value 10 C Pressure sensors Signal type 0 20mA 4 20mA AKS32 1 5V or AKS32R 10 90 ratiometric of 5 V supply voltage Important Current types must be connected to inputs Al 1 6 Current types must b...

Страница 17: ...ction is on or off Digital inputs 1 18 Status of on off inputs Here you can see the status of the function alarm Analoge outputs 1 4 Status of analogue outputs Here you can see the size of the output...

Страница 18: ...on the next page App no Display Suction group Condenser Speed Digital Scroll Stream CRII 1 step with unloa der Step Speed 17 3C2U FS 3 x 16 2C2U 6F 2 6 15 4C1U FS 4 x 14 3C1U 6F 3 6 13 2C1U 4F 2 4 12...

Страница 19: ...gle 8C FS 8 speed C1 C2 C3 C4 C5 C6 C7 C8 Fan VSD Alarm F speed 3 Single 6C FS 6 speed C1 C2 C3 C4 C5 C6 Fan VSD Alarm F speed 2 Single 6C 6F 6 6 C1 C2 C3 C4 C5 C6 Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan 6...

Страница 20: ...6 Compressor start and unloaders Fans Injection ON Alarm on DO15 Digital inputs DI1 DI18 Compressor safety inputs Fan safety input External main switch start stop HP safety switch LP safety switch Nig...

Страница 21: ...condensing pressure Pc has been violated 3K below safety limit High pressure Pc Critical HP safety switch cutout High safety limit for external high pressure switch has been violated DI input HP switc...

Страница 22: ...oid earth fault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals N and AO1 respectively N and AO2 PAY ATTENTION TO THE POLARITY of N Mod...

Страница 23: ...riod times as PWM per 100 capacity is delivered when cooling takes place for the whole period An off time is required by the bypass valve within the period and an on time is also permitted There is no...

Страница 24: ...remaining 50 100 for the unloader The unloader is connected to DO5 or DO6 Stream 6 The compressor capacity is distributed by up to 33 for one relay and the remaining 33 100 for the unloader The unload...

Страница 25: ...ed Display output For type MMIGRS2 Data communication Modbus for AK SM 800 Environments 20 60 C During operations 40 70 C During transport 20 80 Rh not condensed No shock influence vibrations Enclosur...

Страница 26: ...amage poor installation or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to pr...

Отзывы: