Danfoss ADAP-KOOL AK-PC 651 Скачать руководство пользователя страница 25

User Guide 

|

 Capacity Controller, AK-PC 651

RS8HA102 | 25

© Danfoss | ADAP-KOOL® | 2015.10  

An external display is only for front assembly (IP 20)

Connection only via cable with plug. See ordering.

Supply voltage

230 a.c.  (85-265 V) 50/60 Hz, 26 VA

10 analog Input

Pressure meauring:

Ratiometric pressure transmitter type AKS 32R

1-5 volt  pressure transmitter type AKS 32

0-20 (4-20) mA pressure transmitter type AKS 33
Temperature measurement

Pt 1000 ohm/0°C

NTC - 86K from digital scroll / stream

18 digital input

(14 for low v 

4 for high voltage or 

low voltage)

From contact function

E.g. to:

Start/stop of regulation

Monitoring of safety circuits

General alarm function

15 Relay output to 

capacity control

7 pcs. SPST (8A)

AC-1: 6 A (ohmic)

AC-15: 4 A (inductive)

4 pcs. SPDT (8A)

AC-1: 6 A (ohmic)

AC-15: 4 (inductive)

2 pcs. SPDT (16A)

AC-1: 7 A (ohmic)

AC-15: 3.5 (inductiv)

2 pcs. Solid State.

PWM for unloader 

valves

Imax. = 0.5A

Imin. = 50 mA. 

Leak<1.5 mA

4 Voltage output

0-10 V d.c.  Ri = 1kohm

Separate 24 V supply required

Display output

For  type MMIGRS2

Data communication Modbus

for AK-SM 800

Environments

-20 - 60°C, During operations

-40 - 70°C, During transport
20 - 80% Rh, not condensed
No shock influence / vibrations

Enclosure

IP 20

Weight

0.8 kg

Mounting

DIN-rail

Connection terminals max. 2.5 mm

2

 multi core

Approvals

EU Low Voltage Directive and EMC demands re 

CE-marking complied with

LVD tested acc. EN 60730-1 and EN 60730-2-9

EMC-tested acc. EN 61000-6-2 and 3

Data

External display

Pressure transmitter / temperature sensor

Kindly refer to catalogue RK0YG...

Termination

When an external display is connected, two ter-

minals must short-circuited: “R120” and “CAN H”. 

Ordering

Type

Function

Operation

Supply voltage

Code no.

 AK-PC 651

Capacity controller

With buttons and display

230 V

080G0312

MMIGRS2

Display unit

With buttons and display

-

080G0294

Wire for display unit, L = 1.5 m, 1 pcs.

080G0075

Wire for display unit, L = 3 m, 1 pcs.

080G0076

Termination

Connect H-R

Important!

Capacitive load

The relays cannot be used for the direct connection of capacitive loads such 

as LEDs and on/off control of EC motors.

All loads with a switch mode power supply must be connected with a suit-

able contactor or similar. 

Содержание ADAP-KOOL AK-PC 651

Страница 1: ...Capacity controller AK PC 651 User Guide ADAP KOOL Refrigeration Control System...

Страница 2: ...matic safety control day night signal etc Relay outputs max 13 pcs Connection of compressors condenser fans Solid state outputs max 2 pcs Control of capacity valve on a Copeland digital scroll Control...

Страница 3: ...one the control ler will cut out or cut in the next compressor in the sequence When further capacity is either cut out or cut in the capacity from the regulating compressor will be modified accordingl...

Страница 4: ...of the following functions Fixed reference Variable reference which follows the outdoor temperature When the outdoor temperature drops the reference will drop by a corresponding amount This variable...

Страница 5: ...scroll a Copeland stream or Bitzer CRII the capacity will be increased so that the compressor can cool down itself The compressors will be stopped if the temperature reaches the set max temperature va...

Страница 6: ...n groups and 1 condenser group Each of the 3 rows above is continued with three additional displays The arrow in the top corner of the display shows the way to the next display in the same area of ope...

Страница 7: ...y None Main Menu The first setting is the Plant type When the Plant type has been selected it will al low several settings to be made For example Continue to the next menus All settings are explained...

Страница 8: ...s Device for configuration of compressor and condenser Select pressure or saturation temperature Can be set during initial set up and must not be subsequently changed Temp press Fac Saturated Night si...

Страница 9: ...suction gas temperature can be read here Superheat The measured superheat can be read here Day Night status The status of the day night function can be read here Load shed The status of the load shed...

Страница 10: ...0 s Fac 120 s Configuration Configuration Control sensor Select the regulating sensor for the suction circuit Pressure transmitter Po Media temperature sensor S4 brine regulation Po is used for safety...

Страница 11: ...ed AI demand Yes No Fac No Ss suction superheat Monitoring of superheat Define whether a signal from a common Ss sensor on the suction line should be received AI demand Yes No Fac No Injection ON fct...

Страница 12: ...Compressor service Compressor service Comp 1 out of service The compressor can be taken out of operation so that the controller regulates without this compressor No Normal regulation Yes Regulating i...

Страница 13: ...uency converter Step on off control of fans will be via relays Variable step The signals are parallel so external wiring can switch over to step e g if the frequency converter fails AO demand Step Spe...

Страница 14: ...is measured in the suction line by Po and Ss Min 0 K Max 20 K Fac 0 K Superheat Max lim Alarm limit for excess superheating Min 20 K Max 80 K Fac 80 K Superheat delay Delay time before alarm is gener...

Страница 15: ...t Set the output to thermostat AI demand Yes No Fac No Thermostat cut in Here set the temperature value at which the thermostat will cut in Min 50 C Max 150 C Fac 5 C Thermostat cut out Here set the t...

Страница 16: ...ation value 10 C Pressure sensors Signal type 0 20mA 4 20mA AKS32 1 5V or AKS32R 10 90 ratiometric of 5 V supply voltage Important Current types must be connected to inputs Al 1 6 Current types must b...

Страница 17: ...ction is on or off Digital inputs 1 18 Status of on off inputs Here you can see the status of the function alarm Analoge outputs 1 4 Status of analogue outputs Here you can see the size of the output...

Страница 18: ...on the next page App no Display Suction group Condenser Speed Digital Scroll Stream CRII 1 step with unloa der Step Speed 17 3C2U FS 3 x 16 2C2U 6F 2 6 15 4C1U FS 4 x 14 3C1U 6F 3 6 13 2C1U 4F 2 4 12...

Страница 19: ...gle 8C FS 8 speed C1 C2 C3 C4 C5 C6 C7 C8 Fan VSD Alarm F speed 3 Single 6C FS 6 speed C1 C2 C3 C4 C5 C6 Fan VSD Alarm F speed 2 Single 6C 6F 6 6 C1 C2 C3 C4 C5 C6 Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan 6...

Страница 20: ...6 Compressor start and unloaders Fans Injection ON Alarm on DO15 Digital inputs DI1 DI18 Compressor safety inputs Fan safety input External main switch start stop HP safety switch LP safety switch Nig...

Страница 21: ...condensing pressure Pc has been violated 3K below safety limit High pressure Pc Critical HP safety switch cutout High safety limit for external high pressure switch has been violated DI input HP switc...

Страница 22: ...oid earth fault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals N and AO1 respectively N and AO2 PAY ATTENTION TO THE POLARITY of N Mod...

Страница 23: ...riod times as PWM per 100 capacity is delivered when cooling takes place for the whole period An off time is required by the bypass valve within the period and an on time is also permitted There is no...

Страница 24: ...remaining 50 100 for the unloader The unloader is connected to DO5 or DO6 Stream 6 The compressor capacity is distributed by up to 33 for one relay and the remaining 33 100 for the unloader The unload...

Страница 25: ...ed Display output For type MMIGRS2 Data communication Modbus for AK SM 800 Environments 20 60 C During operations 40 70 C During transport 20 80 Rh not condensed No shock influence vibrations Enclosur...

Страница 26: ...amage poor installation or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to pr...

Отзывы: