46
Heat pump controller RS8GF202 © Danfoss 2015-08
AK-HP 780
Configuration - continued
Authorization
1. Go to Configuration menu
Press the orange setup button with the spanner at the bottom
of the display.
2. Select Authorization
3. Change setting for the user ‘SUPV‘
4. Select username and access code
5. Carry out a new login with the user name and the
new access code
You will use this button again and again whenever you want to get to
this display.
On the left-hand side are all the functions not shown yet. There will be
more here the further into the setup we go.
Press the line Authorization to get to the user setup display.
Mark the line with the user name SUPV.
Press the button Change
When the controller is supplied it has been set with standard authoriza-
tion for different user interfaces. This setting should be changed and
adapted to the plant. The changes can be made now or later.
To activate the new settings you must carry out a new login to the con-
troller with the new user name and the relevant access code.
You will access the login display by pressing the padlock at the top left
corner of the display.
This is where you can select the supervisor for the specific system and a
corresponding access code for this person.
The controller will utilize the same language that is selected in the
service tool but only if the controller contains this language. If the
language is not contained in the controller, the settings and readings
will be shown in English.