VLT
®
MICRO
Chapter 5
Summary of Parameters
This chapter summarizes all 10 of the parameter groups. For complete descriptions of
individual parameters refer to Chapter 4.
No.
Parameter
Function
Parameter
Factory
Name
Explanation
Value
Setting
00
Master Speed
Master frequency
d00:Master frequency input
d00
Frequency
source select
determined by the digital
Setting
control panel
d01:Master frequency input
determined by the analog
signal (DC 0 to +10 V)
d02:Master frequency input
determined by the analog
signal (DC 4 to 20 mA)
01
Operation
Operation
d00:Operating instructions
d00
Command
command
determined by the digital
Source
source select
control panel
d01:Operating instructions
determined by the external
terminal connections,
keypad STOP key effective
d02:Operating instructions
determined by the external
terminal connections, keypad
STOP key not effective
02
Motor stop
Motor stop
d00:RAMP stop
d00
method
method select
d01:Coasting to stop
03
V/F Curve
Max output freq.
d50.0 - d400. Hz
d60.0
04
Setting
Max voltage freq.
d10.0 - d400. Hz
d60.0
05
(13 & 14)
Max output volt
d2.0 - d255.0 V
d220.
06
Mid-point freq.
d0.1 - d400. Hz
d1.50
07
Mid-point volt
d002.0 - d255. V
d12.0
08
Min output freq.
d0.1 - d20.0 Hz
d1.50
09
Min output volt
d2.0 - d50.0 V
d12.0
10
Accel/Decel
Acceleration time 1 d0.1 - d600. sec
d10.0
11
Time Setting
Deceleration time 1 d0.1 - d600. sec
d10.0
12
Acceleration time 2 d0.1 - d600. sec
d10.0
62
Содержание 176F7300
Страница 2: ...VLT MICRO ...