VLT
®
MICRO
Pr.29 DC Braking Time During Start-up
Factory Setting d0.0 Sec
Units 0.1 Sec
Parameter value d0.0 - d5.0 Sec
This parameter determines the time duration that DC braking current will be applied to
the motor during the AC drive start-up.
Pr.30 DC Braking Time During Stopping
Factory Setting d0.0 Sec
Units 0.1 Sec
Parameter value d0.0 - d25.0 Sec
This parameter determines the time duration that DC braking current will be applied to
the motor when the Motor Stop Method (Pr.02) is set to "Ramp Stop".
Pr.31 DC Braking Start-up Frequency
Factory Setting d0.00 Hz
Units 0.1 Hz
Parameter value d0.0 - d60.0 Hz
This parameter determines the Start-up Frequency for DC braking when the AC drive
starts to decelerate. The frequency may be set in 0.1 Hz increments. When the value is
less than that specified by Pr.08, Minimum Output Frequency, the start-up frequency for
DC braking will be the value specified by this parameter.
Pr.32, Pr.33, Pr.34, Pr.35 – Momentary Power Loss Protection
Pr.32 Momentary Power Loss Operation Mode Selection
Factory Setting d00
Units None
Settings
d00 Operation stops after momentary power loss.
d01 Operation continues after momentary power loss. Speed search
starts with the Frequency Reference Value.
Minimum output
frequency
DC brake starting frequency
DC braking current %
Pr.08
Pr.29
Pr.28
Pr.31
Pr.30
30