VLT
®
MICRO
Wiring
There are two wiring systems in an AFD: Main Circuit and Control Circuit. The Main
Circuit terminals are located at the top of the drive. Control Circuit terminals are located
bottom of drive, Both terminal blocks are covered by the plastic housing. Lift the
hinged portion of the housing to gain access to the terminals. Make sure power is
removed before making any connections. Connect wires to the terminals according to
the diagram below. When no connections are made to the control terminals, the drive is
operated by the Digital Keypad/Display.
9
Braking Resistor (Option)
Select 80 ohm 120V
/200 ohm 120V
R
S
T
VAC Input
(Select two
terminals as
input for 230V
single phase
models)
Factory set as
multi-function input terminals
Forward/Stop
Reverse/Stop
Reset
Multi-Step 1
Multi-Step 2
Multi-Step 3
Signal Common
M0
M1
M2
M3
M4
M5
GND
M
Grounding
Trim (1K ohm)
Analog +
output
DC 0-10V –
Factory set as,
Indication of output frequency
Multi-function indication output
contacts 120VAC/28VDC 5A
240VAC 2.5A
Factory set as,
Indication of fault
RA
RB
RC
Multi-function PHC output
48V 50mA below
Factory set as,
Indication of "At work"
MO1
MCM
Power for
speed setting
+10V 10mA (max)
AV1
GND
Output Freq. determined
Analog voltage
0-10VDC
VR: 3K-5K ohm
Analog current
4-20mA
Factory set as, output frequency
determined by the potentiometer on
the control panel
R
S
T
E
U
V
W
F
AFm
GND
Ground
Control Circuit Terminals
Main Circuit (power) Terminals
RJ-11 communication port with
RS-485 serial interface
2: GND
3: SG–
4: SG+
5: +5V
6
* NOTE: Do not plug a modem or telephone in to the RS485 port. Do not use terminals
2 or 5 when using the port.
Содержание 176F7300
Страница 2: ...VLT MICRO ...