Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P30K
37
P37K
45
P45K
55
P55K
75
P75K
90
Typical Shaft Output [HP] at 575 V
40
50
60
75
100
IP21/NEMA 1
C2
C2
C2
C2
C2
IP55/NEMA 12
C2
C2
C2
C2
C2
Output current
Continuous (3 x 525-550 V) [A]
43
54
65
87
105
Intermittent (3 x 525-550 V) [A]
47.3
59.4
71.5
95.7
115.5
Continuous (3 x 551-690 V) [A]
41
52
62
83
100
Intermittent (3 x 551-690 V) [A]
45.1
57.2
68.2
91.3
110
Continuous kVA (550 V AC) [kVA]
41
51.4
61.9
82.9
100
Continuous kVA (575 V AC) [kVA]
40.8
51.8
61.7
82.7
99.6
Continuous kVA (690 V AC) [kVA]
49
62.1
74.1
99.2
119.5
Max. input current
Continuous (3 x 525-690 V) [A]
49
59
71
87
99
Intermittent (3 x 525-690 V) [A]
53.9
64.9
78.1
95.7
108.9
Max. pre-fuses
1)
[A]
100
125
160
160
160
Additional specifications
Estimated power loss at rated max. load [W]
4)
592
720
880
1200
1440
Max. cable size (mains, motor, brake) [mm
2
]/(AWG)
2)
[95]/(4/0)
Weight IP21 [kg]
65
65
65
65
65
Weight IP55 [kg]
65
65
65
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
Table 10.11 Mains Supply 3 x 525-690 V AC IP21-IP55/NEMA 1-NEMA 12
1)
For type of fuse see 10.3 Fuse Tables
2)
American Wire Gauge
3)
Measured using 5 m screened motor cables at rated load and rated
frequency
4)
The typical power loss is at normal load conditions and expected
to be within
±
15% (tolerance relates to variety in voltage and cable
conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line).
Lower efficiency motors will also add to the power loss in the
frequency converter and vice versa.
If the switching frequency is raised from nominal the power losses
may rise significantly.
LCP and typical control card power consumptions are included.
Further options and customer load may add up to 30 W to the
losses. (Though typically only 4 W extra for a fully loaded control
card or options for slot A or slot B, each).
Although measurements are made with state of the art equipment,
some measurement inaccuracy must be allowed for (
±
5%).
Specifications
VLT
®
HVAC Drive Operating Instructions
76
MG11AI02 - VLT
®
is a registered Danfoss trademark
10
10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]