Mains supply 3 x 525-600 V AC Normal overload 110% for 1 minute
Size:
P1K1
P1K5
P2K2
P3K0
P3K7
P4K0
P5K5
P7K5
P11K
Typical Shaft Output [kW]
1.1
1.5
2.2
3
3.7
4
5.5
7.5
11
IP20/Chassis
A3
A3
A3
A3
A2
A3
A3
A3
B3
IP21/NEMA 1
A3
A3
A3
A3
A2
A3
A3
A3
B1
IP55/Type 12
A5
A5
A5
A5
A5
A5
A5
A5
B1
IP66/NEMA 4X
A5
A5
A5
A5
A5
A5
A5
A5
B1
Output current
Continuous (3 x 525-550 V) [A]
2.6
2.9
4.1
5.2
-
6.4
9.5
11.5
19
Intermittent (3 x 525-550 V) [A]
2.9
3.2
4.5
5.7
-
7.0
10.5
12.7
21
Continuous (3 x 525-600 V) [A]
2.4
2.7
3.9
4.9
-
6.1
9.0
11.0
18
Intermittent (3 x 525-600 V) [A]
2.6
3.0
4.3
5.4
-
6.7
9.9
12.1
20
Continuous kVA (525V AC) [kVA]
2.5
2.8
3.9
5.0
-
6.1
9.0
11.0
18.1
Continuous kVA (575V AC) [kVA]
2.4
2.7
3.9
4.9
-
6.1
9.0
11.0
17.9
Max. input current
Continuous (3 x 525-600 V) [A]
2.4
2.7
4.1
5.2
-
5.8
8.6
10.4
17.2
Intermittent (3 x 525-600 V) [A]
2.7
3.0
4.5
5.7
-
6.4
9.5
11.5
19
Additional specifications
Estim. power loss at rated max. load [W]
4)
50
65
92
122
-
145
195
261
300
IP20 max. cable cross-section (mains, motor, brake and
load sharing) [mm
2
]/[AWG]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
IP55, IP66 max. cable cross-section (mains, motor, brake
and load sharing) [mm
2
]/[AWG]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
Max. cable cross-section with disconnect
6, 4, 4 (12, 12, 12)
Mains disconnect switch included:
4/12
Weight IP20 [kg]
6.5
6.5
6.5
6.5
-
6.5
6.6
6.6
12
Weight IP21/55 [kg]
13.5
13.5
13.5
13.5
13.5
13.5
14.2
14.2
23
Efficiency
4)
0.97
0.97
0.97
0.97
-
0.97
0.97
0.97
0.98
Table 10.7
5)
With brake and load sharing 95 / 4/0
Specifications
VLT
®
HVAC Drive Operating Instructions
72
MG11AI02 - VLT
®
is a registered Danfoss trademark
10
10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]