AK-CC 750 - 080Z0130 & 080Z0139
Fan control
To obtain energy savings it is possible to pulse control the power
supply to the fans at the evaporators.
Pulse control can be accomplished in one of the following ways:
- during the thermostat’s cutout period (cold room)
- during night operation and during the thermostat’s cutout pe-
riod (appliance with Night blind)
Pulse control only takes place when
all sections/evaporators are cut out.
A period of time is set as well as the percentage of this period of
time where the fans have to be operating.
Stop of fans if cooling is missing
If the refrigeration in a breakdown situation stops, the temperature
in the cold room may rise quickly as a result of the power supply
from large fans. In order to prevent this situation the controller can
stop the fans if the temperature at S5 exceeds a set limit value.
The function can also be used as a sort of MOP function during
start-up with a hot evaporator. The fans will not start until the S5
temperature has been reached below the set limit value. In other
words, the evaporator and hence the compressor wll not be so
heavily loaded during the startup phase.
The function uses the S5 sensor from section A.
The function is not active when refrigeration has stopped.
Anti sweat heat control
It is possible to pulse-control the power to the ASH in order to save
energy. Pulse control can either be controlled according to day/
night load or dew point.
Pulse control according to day and night
Various ON periods can be set for day and night operation.
A period time is set as well as the percentage part of the period in
which the ASH is ON.
Pulse control according to dew point
In order to use this function a system manager of the type AK-SC
255 is required which can measure dew point and distribute the
current dew point to the appliance controllers. For this the ASH ON
period is controlled from the current dew point.
Two dew point values are set in the appliance control:
• One where the effect must be max. i.e.100%.
• One where the effect must be min.
At a dew point which is equal to or lower than the value, the effect
will be the value indicated in "ASH min ON%".
In the area between the two dew point values the controller will
manage the power to be supplied to the rail heat.
The current dew point and duty cycle for ASH can be read off as
status values.
If the dew point signal cannot be distributed to a controller, the
ASH will revert to day/night control.
During defrost the ASH will always be 100% ON.
If ASH ON is selected, it will run at 100% during d the time
after defrost if the thermostat temperature is above the cut-in
limit (but max. 15 minutes).
Compressor control
The controller has a function that can be used for compressor
control. When the function is selected ON a relay will automati-
cally follow the status of the thermostat functions. The relay is ON
when the thermostat demands refrigeration. If the thermostat
function is selected OFF the compressor output will constantly be
ON.
A minimum ON time and a minimum restart time for the relay
belong to the function.
The relay will be OFF during defrost.
There is display of:
- operating hours during the past 24 hours
- total number of operating hours
- number of couplings during the past 24 hours
- total number of couplings
Appliance cleaning
This function makes it easy for the shop’s staff to carry out a
cleaning of the appliance according to a standard procedure.
Function
Appliance cleaning is activated via a pulse signal of minimum
three seconds’ duration – as a rule via a key switch placed on the
appliance. It can however also be activated via data communica-
tion. Appliance cleaning is carried out via three phases:
1 - at the first activation the refrigeration is stopped, but the fans
keep on operating in order to defrost the evaporators. ”Fan” is
shown on the display.
2 - at the second activation the fans are also stopped and the
appliance can now be cleaned. ”OFF” is shown on the display.
3 - At the third activation refrigeration is recommenced. The
display will show the actual appliance temperature.
Common functions
ASH.
Min. ON%
Effect
Dew point