10
RS8GM222 © Danfoss 10-2014
AK-CC 750 - 080Z0130 & 080Z0139
Common data for modules
Supply voltage
24 V d.c. / a.c. +/- 20%
Power consumption
AK-__ (controller)
8 VA
AK-XM 101, 102, 103
2 VA
AK-XM 204, 205
5 VA
Analog inputs
Pt 1000 ohm /0°C
Resolution: 0.1°C
Accuracy: +/- 0.5°C (between -58°F and +122°F)
PTC 1000 ohm /0°C
Pressure transmitter type AKS 32R / AKS
2050 / AKS 32 (1-5 V)
Resolution:1 mV
Ac/- 10 mV
Max. connection of 5 pressure transmitters on one module
Voltage signal 0-10 V
Contact function (On/Off)
On at R < 20 ohm
Off at R > 2K ohm
(Gold -plated contacts not necessary)
On/off supply voltage inputs
Low voltage
0 / 80 V a.c./d.c.
Off: U < 2 V
On: U > 10 V
High voltage
0 / 260 V a.c.
Off: U < 24 V
On: U > 80 V
Relay outputs
SPDT
AC-1 (ohmic)
4 A
AC-15 (inductive)
3 A
U
Min. 24 V
Max. 230 V
Low and high voltage must not be connected to the same
output group
Solid state outputs
Can be used for loads that are cut in and
out frequently, e.g. :
rail heat, fans and AKV valve
Max. 240 V a.c. , Min. 48 V a.c.
Max. 0.5 A,
Leak < 1 mA
Max. 1 AKV
Ambient temperature
During transport
-40 to 158°F
During operation
-4 to 131°F ,
0 to 95% RH (non condensing)
No shock influences / vibrations
Enclosure
Material
PC / ABS
Density
IP10 , VBG 4
Mounting
For mounting on panel wall or DIN rail
Weight with screw terminals
modules in100- / 200- / controller-series
Ca. 7 oz / 17 oz / 21 oz
Approvals
EU low voltage directive and EMC require-
ments are complied with
LVD tested according to EN 60730
EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
UL 873,
UL file number: E166834
The mentioned data applies to all modules.
If data is specific, this is mentioned together with the module in question.