These instructions pertain to OPTYMA™ 
condensing units (R507A, R404A, R134a and 
R22) used for refrigeration systems. They provide 

necessary information regarding safety and proper 
usage of this product. 

•   It is recommended not to open the packaging 

before the unit is at the final place for installation.

•   Handle the unit with care. The packaging allows 

the use of a forklift or pallet jack for handling. Use 
appropriate and safe lifting equipment. 

•   Store and transport the unit in an upright 

position.

•   Store the unit between -35 °C and 50 °C.
•   Don’t expose the packaging to rain or corrosive 

atmosphere.

•   After unpacking, check that the unit is complete 

and undamaged.

 Do not braze if the condensing unit is under 

pressure.

 Never place the unit in a flammable 

atmosphere. 

 Place the unit in such a way that it is not 

blocking or hindering walking areas, doors, 
windows or similar.
 •  Ensure adequate space around the unit for air 

circulation and to open doors. Refer to picture 1 
for minimal values of distance to walls. 

 •  Avoid installing the unit in locations which are 

daily exposed to direct sunshine for longer 
periods.

 •  Avoid installing the unit in aggressive and/or 

dusty environments.

 •  Ensure a foundation with horizontal surface (less 

than 3° slope), strong and stable enough to carry 
the entire unit weight and to eliminate vibrations 
and interference.

 •  The unit ambient temperature may not exceed 

50 °C during off-cycle.

 •  Ensure that the power supply corresponds to the 

unit characteristics (see nameplate).

 •  When installing units for HFC refrigerants, 

use equipment specifically reserved for HFC 
refrigerants which was never used for CFC or 
HCFC refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.
 •  The suction piping connected to the compressor 

must be flexible in 3 dimensions to dampen 
vibrations. Furthermore piping has to be done 
in such a way that oil return for the compressor 
is ensured and the risk of liquid slug over in 
compressor is eliminated.

 •  The unit must be securely installed on a stable 

and rigid support, and fix from the beginning. 

 •   It is recommended to install the unit on rubber 

grommets or vibration dampers (not supplied).

 •  Slowly release the nitrogen holding charge 

through the Schraeder port.

 •  Connect the unit to the system as soon as 

possible to avoid oil contamination from 
ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  Braze with great care using state-of-the-art 

techniques and vent piping with nitrogen gas 
flow.

 •  Connect the required safety and control devices. 

Remove the internal valve when using the 
Schraeder port for this. 

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 
insulation.

Introduction

Handling and storage

Installation precautions

Installation

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosions.
 •  Do not use dye for leak detection.
 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 32 bar.
 •  When a leak is discovered, repair the leak and 

repeat the leak detection test.

 •  Never use the compressor to evacuate the 

system.

 •  Connect a vacuum pump to both the LP and HP 

sides.

 •  Pull down the system under a vacuum of 500 µm 

Hg (0.67 mbar) absolute.

 •  Do not use an ohmmeter nor apply power to the 

compressor while it is under vacuum as this may 
cause internal damage.

Leak detection

Vacuum dehydration

4

FRCC.ES.013.A1.02

Manual

Содержание 0012345AU0116

Страница 1: ...Installation and maintenance condensing unit manual OP HJZ HJM HGM HNU HRU HGZ LJZ LGZ Manual http cc danfoss com...

Страница 2: ...Contents English version 4 Spanish version 14 2 FRCC ES 013 A1 ML Manual...

Страница 3: ...by qualified personnel only Follow these instructions and best practices on refrigeration engineering during installation commissioning maintenance and servicing tasks 2 The condensing unit must only...

Страница 4: ...d dehydrated refrigeration grade copper tubes and silver alloy brazing material Use clean and dehydrated system components The suction piping connected to the compressor must be flexible in 3 dimensio...

Страница 5: ...put liquid refrigerant through the suction line It is not allow to mix additives with the oil and or refrigerant The remaining charge is done until the installation has reached a level of stable nomi...

Страница 6: ...s are still adequately fastened Keep the unit clean and verify the absence of rust and oxidation on the unit components tubes and electrical connections The condenser must be checked at least once a y...

Страница 7: ...t View Top View Suction Line Liquid line X X X X X Y Suction Line Liquid Line Iso View H L D Fixation X mm Y mm Height H mm Depth D mm Length L mm OP HJ 018D 022D 16 126 463 310 1000 OP HJ 028D 036D 1...

Страница 8: ...Height H mm Depth D mm Length L mm OP HG 064D 100D 25 20 500 715 800 1200 OP HG 125D 160D 971 Drawing 2B version D40 reciprocating compressor 2 fans Fixation X1 mm X2 mm Y mm Height H mm Depth D mm L...

Страница 9: ...mm OP HNU 015D 021D 14 174 538 420 1150 OP HNU 030D 688 Air flow Drawing 3A version D40 Scroll Compressor 1 fan Weiguang Front View Left View Top View Suction Line Liquid line X X X X X Y Suction Line...

Страница 10: ...l compressor 2 fans Fixation X1 mm X2 mm Y mm Height H mm Depth D mm Length L mm OP HRU 038D 048D 25 20 500 715 800 1200 OP HRU 058D 076D 971 Fixation X1 mm X2 mm Y mm Height H mm Depth D mm Length L...

Страница 11: ...C Fan capacitor MP Motor protector K Contactor HP High pressure switch LP Low pressure switch CH Crankcase heater RL Relay F Fan Electrical code Q 230 V 3 ph 60 Hz units with reciprocating compressors...

Страница 12: ...Fan capacitor MP Motor protector K Contactor HP High pressure switch LP Low pressure switch CH Crankcase heater F1 F2 Fan Electrical code Q 230 V 3 ph 60 Hz units with scroll compressors POWER WHITE W...

Страница 13: ...WHITE WHITE RED RED RED RED RED RED RED BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK WHITE RED BLACK POWER PACK PRESSURE SWITCH FROM HIGH PRESSURE SWITCH FROM LOW PE GREEN BLACK BLACK SEQUEN...

Страница 14: ...los requisitos establecidos por la norma EN 378 o cualquier otro reglamento local vigente en materia de seguridad 4 Esta unidad condensadora se suministra con gas nitr geno a presi n 1 bar y por lo t...

Страница 15: ...caracter sticas La instalaci n de unidades destinadas al uso con refrigerantes HFC requiere del empleo de equipos dise ados espec ficamente para tales refrigerantes y que no hayan permanecido en conta...

Страница 16: ...dir aceite consulte la etiqueta del compresor para conocer el tipo de aceite que debe emplearse Utilice exclusivamente el refrigerante para el que se haya dise ado la unidad Llene el condensador o el...

Страница 17: ...inuci n de la presi n y el man metro de alta presi n deber indicar un aumento de presi n Arranque Compruebe el sentido de giro del ventilador Debe circular aire desde el condensador hacia el ventilado...

Страница 18: ...ntines de tubo y aletas Desconecte la unidad condensadora utilizando el interruptor principal antes de desmontar cualquier panel de la misma Elimine la suciedad las hojas las fibras etc de las superfi...

Страница 19: ...sta frontal Vista lateral izquierda Vista superior X X X X X Y Vista isom trica H L D L nea de aspiraci n L nea de aspiraci n L nea de l quido L nea de l quido Fijaciones X mm Y mm Altura H mm Profund...

Страница 20: ...dad D mm Longitud L mm OP HG 064D 100D 25 20 500 715 800 1200 OP HG 125D 160D 971 Dibujo 2B versi n D40 reciprocante herm tico 2 ventiladores Flujo de aire D L H Y Y Drawing 2B version D40 reciprocati...

Страница 21: ...nea de aspiraci n Flujo de aire Drawing 3B version D32 Scroll Compressor 1 fan Weiguang Vista frontal Vista lateral izquierda Vista superior X X X X X Y Vista isom trica D L H L nea de aspiraci n L ne...

Страница 22: ...adores Fijaciones X1 mm X2 mm Y mm Altura H mm Profundidad D mm Longitud L mm OP HRU 038D 048D 25 20 500 715 800 1200 OP HRU 058D 076D 971 Flujo de aire Drawing 4A version D40 Scroll Compressor 2 fan...

Страница 23: ...el ventilador GM Guardamotor K Contactor PH Presostato de alta PL Presostato de baja RC Resistencia de c rter RL Relay V Ventilador C digo El ctrico Q 230V 3F 60Hz Unidades con compresor reciprocante...

Страница 24: ...resor reciprocante herm tico Leyenda CP Compressor CV Capacitor del ventilador GM Guardamotor K Contator PH Presostato de alta PL Presostato de baja RC Resistencia de c rter V1 V2 Ventilador C digo El...

Страница 25: ...Instalaci n y el mantenimiento C digo El ctrico R 460V 3F 60Hz Unidades con compresor scroll 25 FRCC ES 013 A1 05 Manual...

Страница 26: ...ned us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spanning across three continents FRCC ES 013 A1 ML Danfoss DCS CC 2016 12 Our pr...

Отзывы: