Water Tank

5

During repairs to sealed components, all electrical supplies shall be disconnected 

from the equipment being worked upon prior to any removal of sealed covers, etc. If 

it is absolutely necessary to have an electrical supply to equipment during servicing, 

then a permanently operating form of leak detection shall be located at the most 

critical point to warn of a potentially hazardous situation.

Particular attention shall be paid to the following to ensure that by working on 

electrical components, the casing is not altered in such a way that the level of 

protection is affected. This shall include damage to cables, excessive number of 

connections, terminals not made to original specification, damage to seals, incorrect 

fitting of glands, etc.

Ensure that apparatus is mounted securely.

Ensure that seals or sealing materials have not degraded such that they no longer 

serve the purpose of preventing the ingress of flammable atmospheres. Replacement 

parts shall be in accordance with the manufacturer’s specifications.

NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak 

detection equipment.

Intrinsically safe components do not have to be isolated prior to working on them.
Do not apply any permanent inductive or capacitance loads to the circuit without 

ensuring that this will not exceed the permissible voltage and current permitted for the 

equipment in use.

Intrinsically safe components are the only types that can be worked on while live in 

the presence of a flammable atmosphere. The test apparatus shall be at the correct 

rating.

Check that cabling will not be subject to wear, corrosion, excessive pressure, 

vibration, sharp edges or any other adverse environmental effects. The check shall 

also take into account the effects of ageing or continual vibration from sources such 

as compressors or fans.

Under no circumstances shall potential sources of ignition be used in the searching 

for or detection of refrigerant leaks. A halide torch (or any other detector using a naked 

flame) shall not be used.

Содержание AQUATANK MB 300L

Страница 1: ...AQUATANK MB 300L Serie WITD AQUATANK MB 300 2 WITD AQUATANK MB 300 3 Edition 07 23 USER MANUAL...

Страница 2: ...nsible for their safety Children should be supervised to ensure that they do not play with the appliance 2 This product has gone through strict inspection and operational test before leaving the facto...

Страница 3: ...lation Instructions 7 4 Wiring Diagrams 8 5 Connection of the Waterway System 9 6 Safety Considerations 11 7 Maintenance of the Water Tank 12 7 1 Water charging and draining 12 7 2 Periodic cleaning f...

Страница 4: ...it for longer life and reliable operation If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The applianc...

Страница 5: ...circuit must be adopted for power supply to prevent fire Do not use octopus multipurpose plug or mobile terminal board for wire connection Be sure to pull out the power plug and drain the indoor unit...

Страница 6: ...ngerous If a stationary appliance is not fitted with a supply cord and a plug or with other means for disconnection from the supply mains having a contact separation in all poles that provides full di...

Страница 7: ...sons in order to avoid a hazard If any hot work is to be conducted on the equipment or any associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry powder or CO2...

Страница 8: ...of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection...

Страница 9: ...ine Dimensions Model WITD AQUATANK MB 300 2 SXTVD300LC B M Litre 300L 300L D mm 620 620 D1 mm 530 530 H mm 1585 1585 A mm 640 640 B mm 348 348 DHW Outlet Water Inlet Heat Pump Water Outlet Heat Pump D...

Страница 10: ...ust be installed vertically with the bottom on the ground never suspended Installation place must be firm enough and the water tank should be fixed on the wall with bolts to avoid vibration as shown i...

Страница 11: ...to be operated regularly to remove lime deposits and to verify that it is not blocked 4 The discharge pipe connected to the pressure relief device is to be installed in a continuously downward direct...

Страница 12: ...circulating water inlet outlet pipes connect the water inlet of the unit with circulating outlet of water tank and water outlet of unit with circulating inlet of water tank 4 Installation of water inl...

Страница 13: ...00502P Fixing strap 1 Fix the water tank to the wall Notes a Distance between indoor unit and water tank should not exceed 5m levelly and 3m vertically If higher please contact with us Water tank on l...

Страница 14: ...llation and should be securely fastened The drain hose should be led naturally downward into the floor drain without any convex bow intertwist or fold Extra length of the drain hose inside the floor d...

Страница 15: ...hot water drain outlet and valve in user water use site Open the cut off valve on the joint 3 way pipe Close the drainage cut off valve after draining water on the water tank to complete drainage oper...

Страница 16: ...e water heater is poor the Mg Stick lifespan will be shortened For Mg Stick replacement perform the following steps 2 Before removing the Mg Stick drain the water tank by following drainage operations...

Страница 17: ...Eurofred S A Marqu s de Sentmenat 97 08029 Barcelona www eurofred es...

Отзывы: