Installation Mode 3 of the Tap Water Safety Valve (Inlet Water Pressure>0.5MPa)

A pressure maintaining valve is required in the installation mode 3 to make sure the water tank pressure keep 

within 0.3~0.5MPa. The arrow direction of the pressure maintaining valve should be the same as the water flow.

Note: the filter, safety valve, check valve, pressure maintaining valve, cut-off valve and hose for installation are 

not delivered with the main unit and should be prepared by the client.

7. Maintenance of the Water Tank

7.1 Water charging and draining

(1)

Operation process for water charging

Cut off the power supply and open the cut-off valve at the water inlet of the tap faucet;

Open the cut-off valve at the hot water drain outlet and valve in user water use site;

Close the valve in user water use site when water is flowing out from user water use site;

Complete water input operation and reenergize the unit.

(2)

Operation process for water draining

Cut off the power supply and close the cut-off valve at the water outlet of the tap faucet;

Open the cut-off valve at the hot water drain outlet and valve in user water use site;

Open the cut-off valve on the joint (3-way) pipe;

Close the drainage cut-off valve after draining water on the water tank to complete drainage operation.

7.2 Periodic cleaning for water tank

Please clean the water tank periodically to get good-quality water according to the following steps: 

(1)

Cut off the power supply.

(2)

Close the cut-off valve at the water inlet of the water tank.

(3)

Open the cut-off valve at the hot water drain outlet and valve in user water use site.

(4)

Open the cut-off valve in joint (3-way) connector, and wait for drainage of water inside water tank.

(5)

Close the cut-off valve in joint (3-way) connector, open the cut-off valve at the water inlet of the water tank,

close the cut-off valve at the water inlet when water flows from user water use site, then reopen the cut-
off valve in joint (3-way) connector, repeat the drainage operation, close the cut-off valve in joint (3-way)
connector when water discharged is clean.

(6)

Conduct water input for the water tank according to water input operation.

(7)

Water tank cleaning completed and energize it.

7.3 Requirements on water quality 

Paramete

Parametric value

Unit

pH( 25°C)

6.8~8.0

/

Cloudy

1

NTU

Chloride

50

mg/L

Fluoride

1

mg/L

Iron

0.3

mg/L

Sulphate

50

mg/L

SiO

2

30

mg/L

Hardness(count CaCO

3

)

70

mg/L

Содержание AQUATANK MB 300L

Страница 1: ...AQUATANK MB 300L Serie WITD AQUATANK MB 300 2 WITD AQUATANK MB 300 3 Edition 07 23 USER MANUAL...

Страница 2: ...nsible for their safety Children should be supervised to ensure that they do not play with the appliance 2 This product has gone through strict inspection and operational test before leaving the facto...

Страница 3: ...lation Instructions 7 4 Wiring Diagrams 8 5 Connection of the Waterway System 9 6 Safety Considerations 11 7 Maintenance of the Water Tank 12 7 1 Water charging and draining 12 7 2 Periodic cleaning f...

Страница 4: ...it for longer life and reliable operation If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The applianc...

Страница 5: ...circuit must be adopted for power supply to prevent fire Do not use octopus multipurpose plug or mobile terminal board for wire connection Be sure to pull out the power plug and drain the indoor unit...

Страница 6: ...ngerous If a stationary appliance is not fitted with a supply cord and a plug or with other means for disconnection from the supply mains having a contact separation in all poles that provides full di...

Страница 7: ...sons in order to avoid a hazard If any hot work is to be conducted on the equipment or any associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry powder or CO2...

Страница 8: ...of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection...

Страница 9: ...ine Dimensions Model WITD AQUATANK MB 300 2 SXTVD300LC B M Litre 300L 300L D mm 620 620 D1 mm 530 530 H mm 1585 1585 A mm 640 640 B mm 348 348 DHW Outlet Water Inlet Heat Pump Water Outlet Heat Pump D...

Страница 10: ...ust be installed vertically with the bottom on the ground never suspended Installation place must be firm enough and the water tank should be fixed on the wall with bolts to avoid vibration as shown i...

Страница 11: ...to be operated regularly to remove lime deposits and to verify that it is not blocked 4 The discharge pipe connected to the pressure relief device is to be installed in a continuously downward direct...

Страница 12: ...circulating water inlet outlet pipes connect the water inlet of the unit with circulating outlet of water tank and water outlet of unit with circulating inlet of water tank 4 Installation of water inl...

Страница 13: ...00502P Fixing strap 1 Fix the water tank to the wall Notes a Distance between indoor unit and water tank should not exceed 5m levelly and 3m vertically If higher please contact with us Water tank on l...

Страница 14: ...llation and should be securely fastened The drain hose should be led naturally downward into the floor drain without any convex bow intertwist or fold Extra length of the drain hose inside the floor d...

Страница 15: ...hot water drain outlet and valve in user water use site Open the cut off valve on the joint 3 way pipe Close the drainage cut off valve after draining water on the water tank to complete drainage oper...

Страница 16: ...e water heater is poor the Mg Stick lifespan will be shortened For Mg Stick replacement perform the following steps 2 Before removing the Mg Stick drain the water tank by following drainage operations...

Страница 17: ...Eurofred S A Marqu s de Sentmenat 97 08029 Barcelona www eurofred es...

Отзывы: