background image

100

GB

4.4 installing several detectors in a network

It is possible to interconnect up to 40 detectors to enable alarm activation over the whole
range of smoke and fire detectors installed in the home.

Signal

Earth N

Cable
terminals

Not used

iMPoRtAnt: 155-21X heat detectors can only be connected with the same type of

detectors: e.g. a 155-21X can be connected with 155-21X heat detectors or 151-21X smoke

detectors.

For 15 mm

2

wires, the overall network length must not exceed 400 m.

3. 

Clip the connector block back in place.

4. 

Lock the detector onto the base (see Fixing the detector in place).

You can therefore be sure of being warned if smoke is detected in a room far away from the
room in which you are in.

1. 

Once the detector’s base has been fixed in place (see Fixing the detector in place),
unclip the connector block.

2. 

Then wire as follows: 

Connector block

Содержание 155-21X

Страница 1: ...Upgraded for e Nova applications...

Страница 2: ...an abnormal speed or when the room temperature reaches between 54 C and 70 C also refer to the table in the Technical Data section The heat detector is especially suitable for detecting res that spre...

Страница 3: ...r provided with this product Heat detector transmitting the heat detection signal other hard wired interconnected heat detectors the LED ashes quickly a built in modulated alarm sounds on a continuous...

Страница 4: ...und The red LED ashes for 15 sec then once every 10 sec to indicate that the detector is working normally 2 Power supply 3 Recognition programming iMPoRtAnt during recognition programming the product...

Страница 5: ...shim made of non magnetic material wood or plastic the detector must not be placed in rooms where a sudden and considerable rise in the room temperature would cause untimely triggering of the alarms...

Страница 6: ...t if there is no voice message move the heat detector closer to the control panel le 2 Put the control panel back in user mode by pressing in rooms where the relative humidity might rise above 95 with...

Страница 7: ...opriate plugs and screws Fixing with ush mounting box 1 For 60 mm diameter boxes use holes marked 2 For 85 mm diameter boxes use holes marked 3 Fix the base using suitable screws 60 85 60 85 optional...

Страница 8: ...e g a 155 21X can be connected with 155 21X heat detectors or 151 21X smoke detectors For 15 mm2 wires the overall network length must not exceed 400 m 3 Clip the connector block back in place 4 Lock...

Страница 9: ...perature measurement If the heat sensor is faulty the heat detector indicates that there is a technical fault see Indications section There is therefore no need to test the detector using a source of...

Страница 10: ...lephone dialler Stop the sirens and check that the control panel has memorised the alarm see Indications section iMPoRtAnt these tests should be carried out at least once a month and notably when you...

Страница 11: ...etector stops its built in sounding The LED indicating the status of the detector ashes every 2 sec Following the 15 min disable period the detector is automatically reset to normal operation with the...

Страница 12: ...stem command the control panel issues the following voice message beep fault battery detector n X 7 Indications iMPoRtAnt in order not to wake you up audible alarms resulting from power problems or te...

Страница 13: ...r head You should vacuum clean the detection head slots if there is a lot of dust in the room 8 Maintenance Heat detector transmitting the fault signal other hard wired interconnected heat detectors t...

Страница 14: ...ent reliability Dispose of the waste lithium power pack in an appropriate recycling bin 8 2 Changing the battery if the optional opening of the detector is not locked see Fixing 1 Remove the detector...

Страница 15: ...ctor status alerts triggered faults White LED safety lighting in case of detection Built in sounding 85 dB at 3 m in case of detection 75 dB at 3 m during testing or fault indication Hard wired interc...

Страница 16: ...6 00 3 7 13 16 00 5 4 09 10 00 10 2 00 5 30 20 1 00 3 13 30 0 40 2 25 or depending on the temperature rise speed A2 class detector response time according to EN 54 5 chapter 5 4 3 Examples if the temp...

Страница 17: ...the user Do not forget to remove the plastic cover when the work is finished Heat detection 1 All heat detectors the LED ashes once every 10 sec Red LeD indicating detector status White LeD Sounding H...

Страница 18: ...l the rst beep sounds You should contact your installation engineer within this same period in order to rectify the problem Following the 15 min disable period the detector is automatically reset to n...

Страница 19: ...95 eC in compliance with the following harmonised European standards This product can be used in all EU EEA Countries and Switzerland Crolles 02 01 2013 Signature Patrick Bernard Director of Research...

Страница 20: ...2280612004 01 2013...

Отзывы: